Plan Review Details - Permit 17010255
Plan Review Stops For Permit 17010255
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-01-17 Cont ID  
Sent By tklarge Date 2017-01-17 Time 06:33 Rev Time 0.00
Received By tklarge Date 2017-01-17 Time 06:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-01-10 Cont ID  
Sent By tklarge Date 2017-01-10 Time 03:31 Rev Time 0.00
Received By tklarge Date 2017-01-10 Time 02:56 Sent To  
Notes
2017-01-10 03:31:331) THE SUBMITTED GAS PLAN NOTES AN "EXISTING " GAS
 METER. INDICATE ON THE PLAN IF THE TANKLESS WATER
 HEATER IS THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF
 NOT, SUBMIT A GAS RISER SHOWING ALL GAS APPLIANCES ON
 THE SYSTEM, THE BTU LOAD OF EACH APPLIANCE AND THE
 LONGEST LENGTH OF PIPING FROM THE POINT OF DELIVERY TO
 THE MOST REMOTE OUTLET AND THEBTU LOAD OF EACH SECTION
 OF PIPE.
 2) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER IN RELATION TO
 THE LOCATION OF ANY OPERABLE DOORS OR WINDOWS AND SHOW
 THE DISTANCES TO SUCH DOORS AND WINDOWS.THE LOCATION OF
 THE WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. SUBMIT TWO COPIES OF THE
 PAGE(S) FROM THE INSTALLATION MANUAL THAT SHOWS AND
 LIST(S) THE REQUIRED DISTANCES FROM THE WATER HEATER TO
 THE DOORS AND WINDOWS.
 3) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT
 REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT
 BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE
 ON THE APPLICATION IN THE DESCRIPTION OF WORK AND ON
 THE PLANS.
 4) IS THIS TANKLESS WATER HEATER BEING ADDED TO AN
 EXISTING GAS SYSTEM? IF SO, SUBMIT A COMPLETE GAS RISER
 SHOWING ALL GAS APPLIANCES CONNECTED TO THE SYSTEM
 ALONG WITH ALL PIPE SIZES, TYPE OF PIPE, THE DEVELOPED
 LENGTH TO THE FURTHEST GAS OUTLET, THE BTU LOAD OF EACH
 APPLIANCE, THE PSI OF THE SYSTEM, TYPE OF GAS AND THE
 TOTAL BTU LOAD ON THE SYSTEM.
 5) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. FGC SECS. 401.4, 401.8, 402.1, 402.2,
 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
 6) A SEPARATE PERMIT IS REQUIRED FOR ANY ELECTRIC WORK
 THAT MAY NEED TO BE DONE,
 7) A SEDIMENT TRAP IS REQD. ON THE GAS LINE TO THE
 WATER HEATER PER 2014 FBC-FUEL GAS 408.4, 2014
 FBCR-SEC. G2419.4.
 8) A SHUTOFF VALVE FOR THE APPLIANCE SHALL BE INSTALLED
 IN ACCORDANCE WITH 2014 FBCR SEC. G2420.5, 2014
 FBC-FUEL GAS SEC.409.5.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-17 Cont ID  
Sent By tklarge Date 2017-01-17 Time 06:33 Rev Time 0.00
Received By tklarge Date 2017-01-12 Time 11:07 Sent To  
Notes
2017-01-13 11:08:13RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-10 Cont ID  
Sent By tklarge Date 2017-01-10 Time 03:31 Rev Time 0.00
Received By tklarge Date 2017-01-10 Time 02:56 Sent To  
Notes
***NONE***