Plan Review Details - Permit 17010218
Plan Review Stops For Permit 17010218
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-06 Cont ID  
Sent By vperez Date 2017-02-06 Time 11:23 Rev Time 0.00
Received By vperez Date 2017-02-06 Time 11:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-13 Cont ID  
Sent By vperez Date 2017-01-13 Time 12:01 Rev Time 0.00
Received By vperez Date 2017-01-13 Time 12:01 Sent To  
Notes
2017-01-13 12:02:20PLEASE ADDRESS FIRE COMMENTS FOR AN ELECTRICAL
 APPROVAL.
  
 V. PEREZ
 *6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-02-02 Cont ID  
Sent By pleduc Date 2017-02-02 Time   Rev Time 0.00
Received By pleduc Date 2017-02-02 Time 16:22 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-01-12 Cont ID  
Sent By vperez Date 2017-01-13 Time 12:02 Rev Time 0.00
Received By wjolin Date 2017-01-12 Time 14:11 Sent To E
Notes
2017-01-12 14:18:19560 VILLAGE BOULEVARD #120
 PERMIT #17010218
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PERMIT VALUE APPEARS TOO LOW. VALUE SHALL INCLUDE LABOR
 AND MATERIALS.
  
 SUBMIT PRODUCT CUTSHEETS.
  
 PLANS LACK SUFFICIENT DETAILS INCLUDING OCCUPANCY TYPE
 AND INDIVIDUAL ROOM USE AND NUMBERS.
  
 PER SECTION 7.2.1.6.2, ACCESS-CONTROLLED EGRESS DOORS
 ARE PERMITTED PROVIDED THAT ALL SEVEN OF THE FOLLOWING
 CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-06 Cont ID  
Sent By vperez Date 2017-02-06 Time 11:23 Rev Time 0.00
Received By vperez Date 2017-02-06 Time 11:23 Sent To  
Notes
2017-02-01 15:21:27RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-13 Cont ID  
Sent By vperez Date 2017-01-13 Time 12:02 Rev Time 0.00
Received By vperez Date 2017-01-13 Time 12:02 Sent To FIRE
Notes
***NONE***