Plan Review Details - Permit 17010155
Plan Review Stops For Permit 17010155
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2017-01-18 Cont ID  
Sent By mvaldes Date 2017-01-18 Time 15:06 Rev Time 0.00
Received By mvaldes Date 2017-01-18 Time 14:41 Sent To  
Notes
2017-01-18 15:10:45MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] ELECTRICAL REVIEW UNDER 16120490
  
 2] CONDENSER UNIT REQUIRESA SERVICE GFCI RECEPTACLE
 OUTLET WITHIN 25' OF EQUIPMENT PER FBC-R SEC E3901.11
 (PROVISO COMMENT)
  
 3] PROVIDE A DISCONNECT WITHIN SIGHT OF THE CONDENSER
 UNIT PER FBC-R SEC E4101.5 (PROVISO COMMENT)

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-03-09 Cont ID  
Sent By hmoser Date 2017-03-09 Time 14:05 Rev Time 0.00
Received By hmoser Date 2017-03-09 Time 09:36 Sent To  
Notes
2017-03-09 09:36:19RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-07 Cont ID  
Sent By cpuell Date 2017-03-07 Time 08:43 Rev Time 0.00
Received By cpuell Date 2017-03-01 Time 10:45 Sent To  
Notes
2017-03-02 10:45:44RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-15 Cont ID  
Sent By lmarchan Date 2017-02-15 Time 07:47 Rev Time 0.00
Received By lmarchan Date 2017-02-07 Time 11:24 Sent To  
Notes
2017-02-08 11:24:18RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-18 Cont ID  
Sent By mvaldes Date 2017-01-18 Time 15:14 Rev Time 0.00
Received By mvaldes Date 2017-01-06 Time 16:33 Sent To  
Notes
2017-01-06 16:33:18ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-03-09 Cont ID  
Sent By hmoser Date 2017-03-09 Time 14:05 Rev Time 0.00
Received By hmoser Date 2017-03-09 Time 14:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-03-06 Cont ID  
Sent By jvalido Date 2017-03-06 Time 17:40 Rev Time 0.00
Received By jvalido Date 2017-03-06 Time 16:18 Sent To  
Notes
2017-03-06 17:24:46CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) TOTAL CFM OF SUPPLY OUTLETS ON PLANS IS MORE THAN
 MANUFACTURER SPECIFICATIONS PER 39500 BTUH. (I WILL
 PROVIDE DATA FROM MANUFACTURE ON EMAIL)
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-02-14 Cont ID  
Sent By jvalido Date 2017-02-14 Time 17:20 Rev Time 0.00
Received By jvalido Date 2017-02-14 Time 16:50 Sent To  
Notes
2017-02-14 17:02:26CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE BALANCED RETURN FROM ALL BEDROOMS.
 (2) PROVIDE ORIGINAL ENGINEER OR ARCHITECT SIGNATURE
 AND SEAL.
 (3) TOTAL CFM FOR ALL SUPPLY GRILLS ARE MORE THAN TOTAL
 CFM AHU CAN SUPPLY. CONFIRM CORRECT CFM AND MAKE
 CORRECTIONS.
 (4) VENTILATION, A/C, HEAT IN OFFICE ?????
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-10 Cont ID  
Sent By jvalido Date 2017-01-10 Time 17:28 Rev Time 0.00
Received By jvalido Date 2017-01-10 Time 16:18 Sent To E
Notes
2017-01-10 17:21:57CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE INFORMATION ON PLANS. ENGINEER OR ARCHITECT
 STAMP AND SIGNATURE. (AS PER 107.1 GENERAL) SEE BELOW
  
 107.1 GENERAL.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT, INTERIOR
 DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER LEGALLY
 REGISTERED UNDER THE LAWS OF THIS STATE REGULATING THE
 PRACTICE OF ARCHITECTURE OR INTERIOR DESIGN AS
 PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART I,
 OR LANDSCAPE ARCHITECTURE AS PROVIDED FOR IN
 CHAPTER 481, FLORIDA STATUTES, PART II, OR ENGINEERING
 AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 (2) PROVIDE EQUIPMENT SCHEDULE ON PLANS. ( BRAND, AHU
 MODEL #, CONDENSER MODEL #, TOTAL BTUH, KW HEATER,
 SEER)
 (3) PROVIDE BALANCE RETURN FROM ALL HABITABLE ROOMS (AS
 PER M1602.4 BALANCED RETURN AIR)
 (4) PROVIDE EXHAUST IN ALL BATHROOMS. (MINIMUN 50 CFM)
 (5) KITCHEN EXHAUST ?????
 (6) PROVIDE CONDENSER TIE DOWN DETAIL. (AS PER
 MANUFACTURER, IF APPLICABLE)
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  
  
  