Plan Review Details - Permit 17010073
Plan Review Stops For Permit 17010073
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-02-06 Cont ID  
Sent By dharvey Date 2017-02-06 Time 13:26 Rev Time 0.00
Received By dharvey Date 2017-02-06 Time 13:26 Sent To  
Notes
2017-02-06 13:27:49CONTRSCTOR STATED THE SERVICE CONDUCTORS WILL KEPT
 OUTSIDE AND PENETRATE ONLY TO ENTER THE PANEL
 CONTAINING THE MAIN DISCONNECT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-01-25 Cont ID  
Sent By mvaldes Date 2017-01-25 Time 18:28 Rev Time 0.00
Received By mvaldes Date 2017-01-25 Time 18:25 Sent To  
Notes
2017-01-25 18:31:413RD REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] MAIN DISCONNECT SHALL BE LOCATED OUTSIDE AT THE
 NEAREST POINT OF ENTRANCE TO THE SERVICE CONDUCTORS.
 NEC 230.70(A)(1)
 - UNFUSED SERVICE WIRES CANNOT PASS BY THE INSIDE OF
 THE BUILDING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-05 Cont ID  
Sent By mvaldes Date 2017-01-05 Time 18:42 Rev Time 0.00
Received By mvaldes Date 2017-01-05 Time 18:21 Sent To  
Notes
2017-01-05 18:47:541ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] IN ADDITION TO THE RISER DIAGRAM PROVIDE LOAD
 CALCULATIONS & PANEL SCHEDULE. FBC 107.3.5.3
  
 2] CLARIFY IF MAIN DISCONNECT IS LOCATED INSIDE OR
 OUTSIDE NEAREST THE POINT OF ENTRANCE OF THE SERVICE
 CONDUCTORS PER NEC 230.70(A)(1).
  
 3] ADD AN INTERSYSTEM BONDING TERMINAL IN ACCORDANCE
 WITH NEC 250.94.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-25 Cont ID  
Sent By mvaldes Date 2017-01-25 Time 18:31 Rev Time 0.00
Received By mvaldes Date 2017-01-23 Time 14:21 Sent To  
Notes
2017-01-24 14:21:48ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-05 Cont ID  
Sent By mvaldes Date 2017-01-05 Time 18:48 Rev Time 0.00
Received By mvaldes Date 2017-01-04 Time 14:55 Sent To  
Notes
2017-01-04 14:55:51ELEC <5K