Plan Review Details - Permit 16120848
Plan Review Stops For Permit 16120848
Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-01-07 Cont ID  
Sent By tklarge Date 2017-01-07 Time 03:27 Rev Time 0.00
Received By tklarge Date 2017-01-07 Time 02:04 Sent To  
Notes
2017-01-07 03:10:57 
 1) A PLAN REVIEW COULD NOT BE PERFORMED BEACAUSE THE
 SIZING TABLE BEING USED IS UNKNOWN.SUBMIT TWO COPIES OF
 THE SIZING TABLES USED IN THE DESIGN FOR THIS GAS
 SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING
 THE SIZING TABLES FROM THE GAS CODE THAT WERE USED IN
 THE DESIGN OF THIS SYSTEM. FGC SEC.402.3, FBCR SEC. G
 2413.3.
 2) SHOW THE TOTAL DISTANCE FROM THE POINT OF DELIVERY,
 (GAS METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 4) SHUTOFF VALVES ARE REQUIRED IMMEDIATELY AHEAD OF
 EACH MP REGVULATOR. 2014 FBC - FUEL GAS SEC.409.4.
  
 NOTE : DO NOT RESUBMIT THESE PLANS UNTIL ALL OF THE
 PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED. IF THE PLANS
 GET REJECTED AGAIN FOR ANY REPEAT COMMENT, A FEE OF
 FOUR TIMES THE AMOUNT OF THE PROPORTION ATTRIBUTED TO
 PLANS REVIEW SHALL BE PAID PER FL. STATUTE 553.80 (2)
 (B).
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-12-27 Cont ID  
Sent By tklarge Date 2016-12-27 Time 06:54 Rev Time 0.00
Received By tklarge Date 2016-12-27 Time 06:36 Sent To  
Notes
2016-12-27 06:54:051) A PLAN REVIEW COULD NOT BE PERFORMED BEACAUSE THE
 SIZING TABLE BEING USED IS UNKNOWN.SUBMIT TWO COPIES OF
 THE SIZING TABLES USED IN THE DESIGN FOR THIS GAS
 SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING
 THE SIZING TABLES FROM THE GAS CODE THAT WERE USED IN
 THE DESIGN OF THIS SYSTEM. FGC SEC.402.3, FBCR SEC. G
 2413.3.
 2) SHOW THE TOTAL DISTANCE FROM THE POINT OF DELIVERY,
 (GAS METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 3) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 5) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-07 Cont ID  
Sent By tklarge Date 2017-01-07 Time 03:27 Rev Time 0.00
Received By tklarge Date 2017-01-05 Time 10:22 Sent To  
Notes
2017-01-06 10:22:47RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-27 Cont ID  
Sent By tklarge Date 2016-12-27 Time 06:54 Rev Time 0.00
Received By tklarge Date 2016-12-22 Time 16:05 Sent To  
Notes
2016-12-22 16:05:33PLUMB <5K


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved