Plan Review Details - Permit 16120847
Plan Review Stops For Permit 16120847
Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-01-07 Cont ID  
Sent By tklarge Date 2017-01-07 Time 05:31 Rev Time 0.00
Received By tklarge Date 2017-01-07 Time 03:47 Sent To  
Notes
2017-01-07 05:12:40 
 1) A PLAN REVIEW COULD NOT BE PERFORMED BEACAUSE THE
 SIZING TABLE(S) BEING USED IS UNKNOWN.SUBMIT TWO COPIES
 OF THE SIZING TABLES USED IN THE DESIGN FOR THIS GAS
 SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING
 THE SIZING TABLES FROM THE GAS CODE THAT WERE USED IN
 THE DESIGN OF THIS SYSTEM. FGC SEC.402.3, FBCR SEC. G
 2413.3.
 2) SHOW THE TOTAL DISTANCE FROM THE POINT OF DELIVERY,
 ( GAS METER / MP REGULATOR ) TO THE MOST REMOTE OUTLET
 IN THE BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL
 GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 4) SUBMIT AN EXPANDED GAS RISER THAT CLEARLY SHOWS THE
 PIPE SIZES, ETC. WPB AMEND. TO FBC SEC. 107.2.1. SOME
 PIPE SIZES ARE STILL DIFFICULT TO READ.
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.
 6) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. THE GAS RISER
 APPEARS TO SHOW THE SHUTOFF VALVES DOWNSTREAM OF THE
 REGULATORS.
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS. WPB AMEND. TO FBC SEC. 107.2.1, 2014
 FBC-FUEL GAS SEC.410.1, 410.2.
 8) SHOW THE PIPE SIZE OF THE PE PIPE TO THE FIRE PIT.
 9) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS (IF APPLICABLE) PER 2014
 FBC-FUEL GAS SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G
 2426.
  
 NOTE : DO NOT RESUBMIT THESE PLANS UNTIL ALL OF THE
 PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED. IF THE PLANS
 GET REJECTED AGAIN FOR ANY REPEAT COMMENT, A FEE OF
 FOUR TIMES THE AMOUNT OF THE PROPORTION ATTRIBUTED TO
 PLANS REVIEW SHALL BE PAID PER FL. STATUTE 553.80 (2)
 (B).
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-12-30 Cont ID  
Sent By tklarge Date 2016-12-30 Time 08:54 Rev Time 0.00
Received By tklarge Date 2016-12-30 Time 06:25 Sent To  
Notes
2016-12-30 07:08:041) SUBMIT AN EXPANDED GAS RISER THAT CLEARLY SHOWS THE
 PIPE SIZES, PSI, TYPE OF PIPE, ETC. WPB AMEND. TO FBC
 SEC. 107.2.1.
 2) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.SHOW THIS FOR THE 2 PSI SYSTEM AND ALSO THE LOW
 PRESSURE SYSTEM.
 3.) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 FIREPLACE PER THE 2014 FBC-FUEL GAS CODE SEC.304.1 OR
 2014 FBC-RES. SEC. G 2407.
 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.
 6) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. THE GAS RISER
 APPEARS TO SHOW THE SHUTOFF VALVES DOWNSTREAM OF THE
 REGULATORS.
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS. WPB AMEND. TO FBC SEC. 107.2.1, 2014
 FBC-FUEL GAS SEC.410.1, 410.2.
 8) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN OF THIS SYSTEM OR PLACE THE NUMBER OF THE SIZING
 TABLES ON THE PLAN AND THE CODE STANDARD THAT WAS USED
 FOR THE SIZING OF THE SYSTEM. WPB AMEND. TO FBC SEC.
 107.2.1, FBC-FUEL GAS SEC.402.3.
 9) SHOW THE PIPE SIZE OF THE PE PIPE TO THE FIRE PIT.
 10) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS (IF APPLICABLE) PER
 2014 FBC-FUEL GAS SECS. 502 THRU 505 OR 2014 FBC-RES.
 SEC.G2426.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-07 Cont ID  
Sent By tklarge Date 2017-01-07 Time 05:32 Rev Time 0.00
Received By tklarge Date 2017-01-05 Time 10:37 Sent To  
Notes
2017-01-06 10:37:14RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-30 Cont ID  
Sent By tklarge Date 2016-12-30 Time 08:54 Rev Time 0.00
Received By tklarge Date 2016-12-22 Time 16:05 Sent To  
Notes
2016-12-22 16:05:56PLUMB <5K