2016-12-22 06:10:17 | THERE ARE TWO SEPARATE APPLICATIONS THAT HAVE BEEN |
| SUBMITTED THAT DO NOT MAKE ANY SENSE. ONE APPLICATION |
| IS FOR A GAS LINE TO A KITCHEN STOVE AND THEN A |
| SEPARATE APPLICATION FOR THE GAS WATER HEATER.HERE IS |
| THE PROCESS: |
| 1) SUBMIT ONE APPLICATION FOR THE GAS THAT DESCRIBES |
| ALL THE GAS WORK TO BE DONE AND LISTS ALL THE GAS |
| APPLIANCES TO BE INSTALLED. |
| 2) SUBMIT A SECOND APPLICATION FOR ANY PLUMBING WORK TO |
| BE DONE ( SUCH AS THE WATER PIPING FOR A TANKLESS WATER |
| HEATER). |
| 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014 |
| FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G |
| 2413.3. |
| 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. |
| SEC. G2413.2. . |
| 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. IF THE |
| STOVE IS EXISTING, INDICATE SO ON THE PLANS. IF NEW, |
| SUBMIT THE MANUFACTURER'S SPECIFICATION SHEETS SHOWING |
| IT IS LISTED AND LABELED. |
| 6) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE |
| DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE |
| THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC |
| SEC.402.3, FBCR SEC. G 2413.3. |
| 7) . SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE |
| WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS.SUBMIT A COPY OF THE PAGE |
| FROM THE INSTALLATION MANUAL SHOWING THE REQUIRED |
| DISTANCES. |
| 8) A SEPARATE PERMIT IS REQUIRED FOR ANY ELECTRIC WORK |
| TO BE DONE. |
| |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |