Plan Review Details - Permit 16120671
Plan Review Stops For Permit 16120671
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-06-21 Cont ID  
Sent By jwitmer Date 2017-06-21 Time 14:29 Rev Time 0.00
Received By jwitmer Date 2017-06-21 Time 13:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-06 Cont ID  
Sent By shill Date 2017-01-06 Time 08:38 Rev Time 0.00
Received By jwitmer Date 2017-01-06 Time 06:45 Sent To  
Notes
2017-01-06 08:08:02BUILDING PLAN REVIEW
 W. P. B. REVISION: 16120671
 W. P. B. PERMIT: 16050249
 ADD: 3501 PARKER AVE.
 CONT: HEDRICK BROTHERS
 TEL: 561-324-1127
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 06/ 2017
 ACTION: DENIED
  
 1) PLEASE PROVIDE A NARRATIVE DESCRIBING WHAT REVISION
 # 5 IS.
 EXAMPLES LS101 VERSES AE111. AE111 SHOWS A REVISION # 5
 IN THE WET ROOM 165B WHEREAS LS101 DOESN?T. ON THE SAME
 TWO SHEETS ON SHEET LS101 IN THE SAME AREA CORRIDOR 164
 THERE IS A REVISION # 5 IT APPEARS TO BE A DIMENSION
 LINE TO THE CENTERLINE OF AN FEC (FIRE EXTINGUISHER IN
 CABINET). 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 ANOTHER AREA OF QUESTION IS FOUND ON SHEET AE112
 REVISION # 5 STORAGE ROOM 124 & CORRIDOR 130, THE
 REVISION APPEARS TO BE THE SAME AS REVISION # 4.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
  
 2) SHEET AE320 REVISION # 5;
 2A) WALL SECTION # 1 SHOWS A ROOF TOP REVISION TO
 LIGHTWEIGHT CONCRETE R-20 MIN. AT LOW POINT, ON
 CORRUGATED STEEL DECK. WILL REQUIRE A CHANGE OF ROOFING
 ASSEMBLIES PRODUCT APPROVALS, AND BE REVIEWED BY THE
 DESIGNER OF RECORD BEFORE SUBMITTING TO THE BUILDING
 DEPARTMENT.
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.?
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 2B) WALL SECTION # 2 SHOWS FABRIC COVERED ACOUSTIC
 PANELS MECHANICALLY ANCHORED TO WALL/ SOLID BLOCKING
 PER MANUFACTURERS SPECIFICATION. TO DATE THERE HAS BEEN
 NO PRODUCT DATA SHEETS SHOWING COMPLIANCE OF MATERIALS
 FOR THE FABRIC OR ACOUSTICAL PANELS.
 PLEASE SHOW COMPLIANCE WITH 803.5 TEXTILE WALL
 COVERINGS. WHERE USED AS INTERIOR WALL FINISH
 MATERIALS, TEXTILE WALL COVERINGS, INCLUDING MATERIALS
 HAVING WOVEN OR NONWOVEN, NAPPED, TUFTED, LOOPED OR
 SIMILAR SURFACE AND CARPET AND SIMILAR TEXTILE
 MATERIALS, SHALL BE TESTED IN THE MANNER INTENDED FOR
 USE, USING THE PRODUCT MOUNTING SYSTEM, INCLUDING
 ADHESIVE, AND SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTION 803.1.2, 803.1.3 OR 803.1.4.
  
 ACOUSTICAL PANELS: PLEASE PROVIDE THE MANUFACTURERS
 SPEC FOR INSTALLATION AND COMPLIANCE WITH FBC-B TABLE
 803.9 INTERIOR WALL AND CEILING FINISHES REQUIRED BY
 OCCUPANCY. MOUNTING DETAILS ARE LOCATED DETAIL 5 SHEET
 AE 712.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-12-27 Cont ID  
Sent By vperez Date 2016-12-27 Time 13:10 Rev Time 0.00
Received By rlecky Date 2016-12-27 Time 12:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-19 Cont ID  
Sent By pleduc Date 2017-06-19 Time   Rev Time 0.00
Received By pleduc Date 2017-06-16 Time 13:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-12-22 Cont ID  
Sent By pleduc Date 2016-12-22 Time   Rev Time 0.00
Received By pleduc Date 2016-12-22 Time 11:21 Sent To  
Notes
2016-12-22 11:38:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET LS101 - THERE ARE REVISION CLOUDS INDICATED AS
 # 5; HOWEVER, THERE IS NOT NOTE OF SYMBOL INDICATOR AS
 TO WHAT THE REVISION IS.
  
 PLEASE IDENTIFY WHAT THE REVISON IS AND ITS FUNCTION.
  
  
  
  
 2) SHEET AE412 - THERE IS A REVISION CLOUD INDICATING A
 FABRIC COVERED PANEL SECURED TO THE WALL. THERE ARE NO
 MANUFUACTURES SPEC/PRODUCT SHEETS PROVIDED IDENTIFYING
 ANY FIRE RETARDENT - FLAME SPREAD - SMOKE TOXICITY.
  
 PLEASE PROVIDE ALL APPLICABLE PRODUCTS SPECIFICATION
 SHEETS FOR THE RECORD AND ALSO TO ENSURE FIRE CODE
 COMPLIANCE.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-29 Cont ID  
Sent By jroach Date 2017-06-29 Time 10:14 Rev Time 0.00
Received By jroach Date 2017-06-09 Time 09:55 Sent To  
Notes
2017-06-13 09:55:31C12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-20 Cont ID  
Sent By gjohnson Date 2017-01-20 Time 15:43 Rev Time 0.00
Received By gjohnson Date 2016-12-19 Time 14:03 Sent To  
Notes
2016-12-20 14:03:31C08

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-01-20 Cont ID  
Sent By tklarge Date 2017-01-20 Time 15:42 Rev Time 0.00
Received By gjohnson Date 2017-01-20 Time 15:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-06-29 Cont ID  
Sent By jroach Date 2017-06-29 Time 10:14 Rev Time 0.00
Received By jroach Date 2017-06-29 Time 10:14 Sent To  
Notes
2017-06-29 10:14:44ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.18.2017
 PERMIT NO.: 16050249
 ADDRESS: 3501 PARKER AVENUE
 CONTRACTOR/CONTACT: BRETT
 TELEPHONE NO.: 561.324.1127
 SCOPE OF REVIEW: NEW RECREATION BUILDING.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. SEPARATE PERMITS SHALL BE OBTAINED FOR LANDSCAPING
 AND IRRIGATION. ALL LANDSCAPING SHALL BE PERMITTED,
 INSTALLED AND PASSED INSPECTION PRIOR TO THE ISSUANCE
 OF A CERTIFICATE OF OCCUPANCY (CO).
  
 2. ALL OUTSTANDING LANDSCAPING AND SCREENING ENCLOSURES
 FOR THE ENTIRE PBAU ATHLETIC COMPLEX WILL BE REQUIRED
 TO BE INSTALLED PRIOR TO ISSUANCE OF A CO FOR THE
 RECREATION BUILDING.
  
 3. ALL ABOVE-GROUND UTILITIES (BACKFLOW, DCDAS, ETC.)
 SHALL BE SCREENED WITH LANDSCAPING.
  
 4. ALL SIGNAGE (WALL MOUNTED, FREESTANDING, ETC.) SHALL
 BE SUBMITTED UNDER A SEPARATE PERMIT APPLICATION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-01-18 Cont ID  
Sent By jroach Date 2017-01-18 Time 14:08 Rev Time 0.00
Received By jroach Date 2017-01-18 Time 14:08 Sent To  
Notes
2017-01-18 14:09:05ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.18.2017
 PERMIT NO.: 16050249
 ADDRESS: 3501 PARKER AVENUE
 CONTRACTOR/CONTACT: BRETT
 TELEPHONE NO.: 561.324.1127
 SCOPE OF REVIEW: NEW RECREATION BUILDING.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO INSTALLATION, A REVISION SHALL BE SUBMITTED
 FOR APPROVAL OF THE BIKE RACK DETAIL.
  
 2. SEPARATE PERMITS SHALL BE OBTAINED FOR LANDSCAPING
 AND IRRIGATION. ALL LANDSCAPING SHALL BE PERMITTED,
 INSTALLED AND PASSED INSPECTION PRIOR TO THE ISSUANCE
 OF A CERTIFICATE OF OCCUPANCY (CO).
  
 3. ALL OUTSTANDING LANDSCAPING AND SCREENING ENCLOSURES
 FOR THE ENTIRE PBAU ATHLETIC COMPLEX WILL BE REQUIRED
 TO BE INSTALLED PRIOR TO ISSUANCE OF A CO FOR THE
 RECREATION BUILDING.
  
 4. ALL ABOVE-GROUND UTILITIES (BACKFLOW, DCDAS, ETC.)
 SHALL BE SCREENED WITH LANDSCAPING.
  
 5. ALL SIGNAGE (WALL MOUNTED, FREESTANDING, ETC.) SHALL
 BE SUBMITTED UNDER A SEPARATE PERMIT APPLICATION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved