Plan Review Details - Permit 16120669
Plan Review Stops For Permit 16120669
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2017-04-27 Cont ID  
Sent By mgonzale Date 2017-04-27 Time   Rev Time 1.00
Received By mgonzale Date 2017-04-27 Time   Sent To  
Notes
2017-04-27 13:51:40LEAD FREE DEVICES ONLY

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-01-11 Cont ID  
Sent By mgonzale Date 2017-01-11 Time   Rev Time 0.50
Received By mgonzale Date 2017-01-11 Time   Sent To  
Notes
2017-01-11 09:46:55ADDRESS FIRE REVIEW COMMENTS. RESUBMIT
 DCDA SHALL BE USC APPROVED AND LEAD FREE TYPE, SUBMIT
 SPECIFICATION SHEETS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 818-1322
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-17 Cont ID  
Sent By pleduc Date 2017-04-17 Time   Rev Time 0.00
Received By pleduc Date 2017-04-14 Time 16:17 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-12-20 Cont ID  
Sent By wjolin Date 2016-12-20 Time 12:24 Rev Time 0.00
Received By wjolin Date 2016-12-20 Time 12:14 Sent To M
Notes
2016-12-20 12:24:143501 PARKER AVENUE
 PERMIT #16120669
 MASTER #16050249
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO PLANS SUBMITTED.
  
 PRODUCT CUTSHEETS ARE FOR PVC GRAVITY SEWER PIPING.
 SUBMIT CUTSHEETS PERTAINING TO UNDERGROUND FIRE LINE
 AND JOINT RESTRAINT. IF APPLICABLE, PROVIDE JOINT
 RESTRAINT INFORMATION INDICATING PROPER BOLT TORQUES.
  
 JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1,
 ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND
 HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT
 BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS.
  
 CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION
 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS,
 WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE
 CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR
 OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL.
  
 ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION
 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY
 TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE
 SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE
 CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM
 PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN
 THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER
 SECOND.
  
 FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1, THE
 INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE
 COMPLETING AND SIGNING THE CONTRACTOR?S MATERIAL AND
 TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1.
  
 HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION
 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES
 SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE
 HYDROSTATICALLY TESTED AT 200 PSI OR 50 PSI IN EXCESS
 OF THE SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER,
 AND SHALL MAINTAIN THAT PRESSURE +/-5 PSI FOR 2 HOURS.
  
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-04-12 Time 11:35 Sent To  
Notes
2017-04-13 11:36:09RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-11 Cont ID  
Sent By lmarchan Date 2017-01-11 Time 10:08 Rev Time 0.00
Received By lmarchan Date 2016-12-19 Time 15:21 Sent To  
Notes
2016-12-19 15:21:39ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-04-19 Cont ID  
Sent By hmoser Date 2017-04-19 Time 11:03 Rev Time 0.00
Received By hmoser Date 2017-04-19 Time 10:44 Sent To ENG
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-03 Cont ID  
Sent By jvalido Date 2017-01-03 Time 17:17 Rev Time 0.00
Received By jvalido Date 2017-01-03 Time 17:09 Sent To ENG
Notes
2017-01-03 17:12:14CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE PLANS.
 (2) REFER TO FIRE DEPT. PLAN REVIEW NOTES.
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  