Plan Review Details - Permit 16120632
Plan Review Stops For Permit 16120632
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-12-21 Cont ID  
Sent By jwitmer Date 2016-12-21 Time 10:24 Rev Time 0.00
Received By jwitmer Date 2016-12-21 Time 09:37 Sent To  
Notes
2016-12-21 10:04:22BUILDING PROVISO:
  
 SHEETS A1.1.1 & A2.0 ARE MISSING SAFETY GLAZING NOTES,
 RED LINED!!!!!
 1) REQUIREMENTS FOR SAFETY GLAZING FBC-B 2406.4
 2) FBC-B 2406.4.1 GLAZING IN DOORS
 3) FBC-B 2406.4.2 GLAZING ADJACENT TO DOORS.
  
 JAMES A. WITMER BN, PX,CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-01-09 Cont ID  
Sent By mvaldes Date 2017-01-09 Time 15:21 Rev Time 0.00
Received By mvaldes Date 2017-01-09 Time 14:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-12-22 Cont ID  
Sent By pleduc Date 2016-12-22 Time   Rev Time 0.00
Received By pleduc Date 2016-12-22 Time 12:36 Sent To  
Notes
2016-12-22 12:41:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET ALS 1.1 - THERE IS NO INDICATION OF FIRE
 SPRINKLER OR FIRE ALARM WORK.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
  
 2) SHEET E 2.1 - THERE IS NO EXIT SIGN AT THE NEW DOOR
 100 LOCATION LEADING TO THE EXISTING EXIT.
  
 PLEASE ADD A NEW EXIT SIGN AT THAT LOCATION LEADING TO
 THE EXISTING EXIT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-09 Cont ID  
Sent By mvaldes Date 2017-01-09 Time 15:23 Rev Time 0.00
Received By mvaldes Date 2016-12-16 Time 10:12 Sent To  
Notes
2016-12-19 10:12:49B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2016-12-21 Time   Rev Time 0.00
Received By jwitmer Date 2016-12-21 Time 09:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-01-17 Cont ID  
Sent By skennedy Date 2017-01-17 Time 11:59 Rev Time 0.00
Received By skennedy Date 2017-01-17 Time 11:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-28 Cont ID  
Sent By ccole Date 2016-12-28 Time 11:59 Rev Time 0.00
Received By ccole Date 2016-12-28 Time 11:58 Sent To  
Notes
2016-12-28 12:02:521ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16120632
 12/28/16
  
 1) M2.1: SHOW THE BRANCH DUCT SIZES FROM THE EXISTING
 TRUNKS TO THE NEW VAV BOXES, AND THE FLEX DUCT SIZES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-01-09 Cont ID  
Sent By gjohnson Date 2017-01-09 Time 13:58 Rev Time 0.00
Received By gjohnson Date 2017-01-09 Time 13:58 Sent To  
Notes
***NONE***