Plan Review Details - Permit 16120621
Plan Review Stops For Permit 16120621
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-01-13 Cont ID  
Sent By pleduc Date 2017-01-13 Time   Rev Time 0.00
Received By pleduc Date 2017-01-13 Time 13:41 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-12-21 Cont ID  
Sent By pleduc Date 2016-12-21 Time   Rev Time 0.00
Received By pleduc Date 2016-12-21 Time 10:55 Sent To M
Notes
2016-12-21 11:13:28THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13.
 ENSURE FIRE PUMP TEST PRESURE IS USED TO CALCULATE
 "WORKING PRESSURE"
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-24 Cont ID  
Sent By hmoser Date 2017-01-24 Time 14:51 Rev Time 0.00
Received By hmoser Date 2017-01-11 Time 15:13 Sent To  
Notes
2017-01-11 15:13:42RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-27 Cont ID  
Sent By ccole Date 2016-12-27 Time 13:39 Rev Time 0.00
Received By ccole Date 2016-12-16 Time 15:04 Sent To  
Notes
2016-12-16 15:04:24ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-01-24 Cont ID  
Sent By hmoser Date 2017-01-24 Time 14:47 Rev Time 0.00
Received By hmoser Date 2017-01-24 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-27 Cont ID  
Sent By ccole Date 2016-12-27 Time 13:39 Rev Time 0.00
Received By ccole Date 2016-12-27 Time 13:39 Sent To  
Notes
2016-12-27 13:45:353RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16120621
 12/27/16
  
 1) THE PLANS MUST BEAR THE SIGNATURE OF THE PERSON
 RESPONSUIBLE FOR THE DESIGN, OR BEAR THE SHOP DRAWING
 APPROVAL STAMP OF THE ENGINEER OF RECORD- WEST PALM
 BEACH AMENDMENTS TO THE FBC
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND
 DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN APPROVED BY THE
 BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF
 THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR
 THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 107.2.1.1 FIRE PROTECTION SYSTEM SHOP DRAWINGS. SHOP
 DRAWINGS FOR THE FIRE PROTECTION SYSTEM(S)
 SHALL BE SUBMITTED TO INDICATE CONFORMANCE WITH THIS
 CODE AND THE CONSTRUCTION DOCUMENTS AND SHALL
 BE APPROVED PRIOR TO THE START OF SYSTEM INSTALLATION.
 SHOP DRAWINGS SHALL CONTAIN ALL INFORMATION
 AS REQUIRED BY THE REFERENCED INSTALLATION STANDARDS IN
 CHAPTER 9.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  