Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-02-27 Cont ID  
Sent By tklarge Date 2017-02-27 Time 10:37 Rev Time 0.00
Received By tklarge Date 2017-02-27 Time 10:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-12-17 Cont ID  
Sent By tklarge Date 2016-12-17 Time 04:17 Rev Time 0.00
Received By tklarge Date 2016-12-17 Time 04:05 Sent To  
Notes
2016-12-17 04:17:071) THE GAS SIZING TABLE THAT HAS BEEN SUBMITTED NOTES
 THAT IT IS FOR A SUPPLY PRESSURE OF 11.0 INCHES W.C OR
 GREATER YET THE GAS RISER SHOWS THE SUPPLY PRESSURE
 GOING FROM 11INCHES W.C. TO 7 INCHES W.C. AND THEN TO
 11 INCHES W.C. CLARIFY.
 2) SUBMIT MANUF. SPECS FOR THE NEW RANGE. THE
 SPECIFICATIONS SHALL SHOW THAT THE RANGE IS LISTED AND
 LABELED PER 2014 FGC SEC.301.3.
 3) SUBMIT CALCULATIONS FOR COMBUSTION AIR.2014 FGC
 SEC.304.
 4) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE NEW
 RANGE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-27 Cont ID  
Sent By tklarge Date 2017-02-27 Time 10:37 Rev Time 0.00
Received By tklarge Date 2017-02-22 Time 10:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-17 Cont ID  
Sent By tklarge Date 2016-12-17 Time 04:17 Rev Time 0.00
Received By tklarge Date 2016-12-14 Time 09:50 Sent To  
Notes
2016-12-15 09:50:32PLUMB <5K


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved