Plan Review Details - Permit 16120363
Plan Review Stops For Permit 16120363
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-02-26 Cont ID  
Sent By jwitmer Date 2018-02-26 Time 15:40 Rev Time 0.00
Received By jwitmer Date 2018-02-26 Time 14:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-11-17 Cont ID  
Sent By jwitmer Date 2017-11-17 Time 09:49 Rev Time 0.00
Received By jwitmer Date 2017-11-17 Time   Sent To  
Notes
2017-11-17 09:49:36BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120363
 ADD: 3800 WASHINGTON RD.
 CONT: KCA CONSTRUCTION
 TEL: 561-361-0577
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. NOV. 17/ 2017
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST. SHEET S-1 STRUCTURAL STEEL NOTE 2( E )
 MAKES REFERENCE TO CODE SECTION R4408.5.3. PLEASE
 CORRECT THIS CODE SECTION. THIS IS FOR SINGLE FAMILY
 RESIDENCES, STEEL IN THE HIGH-VELOCITY HURRICANE ZONES.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3)BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS.
 2014 FBC-B 2204.1 WELDING
 201404.4.2 BOLTING.
  
 4) 2ND REQUEST. SHEET S-2 INDICATES THE REPLACEMENT
 COOLING TOWER CT-1 TO BE A MARLEY 23121. PLEASE PROVIDE
 MANUFACTURERS PRODUCT INFORMATION THAT THIS MECHANICAL
 EQUIPMENT THAT IS EXPOSED TO WIND WAS DESIGNED TO
 RESIST WIND PRESSURES FOR THIS WIND SPEED AND
 ELEVATION. 2014 FBC-M 301.15 WIND RESISTANCE.
  
 5) COMPLIED. ANCHOR OF UNIT TO STEEL BEAMS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 THE PLAN REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-15 Cont ID  
Sent By jwitmer Date 2016-12-15 Time 07:02 Rev Time 0.00
Received By jwitmer Date 2016-12-15 Time 06:03 Sent To  
Notes
2016-12-15 07:18:52BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120363
 ADD: 3800 WASHINGTON RD.
 CONT: KCA CONSTRUCTION
 TEL: 561-361-0577
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. DEC. 15/ 2016
 ACTION: DENIED
  
 1) ON THE PERMIT APPLICATION THE CONTRACTORS SIGNATURE
 IS A COPY, AN ORIGINAL SIGNATURE IS REQUIRED BEFORE
 PERMIT ISSUANCE. 2014 FLORIDA BUILDING CODE W 2014 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 105.3.1 ACTION ON
 APPLICATION. IF THE APPLICATION OR THE CONSTRUCTION
 DOCUMENTS DO NOT CONFORM TO THE REQUIREMENTS OF
 PERTINENT LAWS, THE BUILDING OFFICIAL SHALL REJECT SUCH
 APPLICATION IN WRITING, STATING THE REASONS THEREFORE.
 IF THE BUILDING OFFICIAL IS SATISFIED THAT THE PROPOSED
 WORK CONFORMS TO THE REQUIREMENTS OF THIS CODE AND LAWS
 AND ORDINANCES APPLICABLE THERETO.
  
 2) SHEET S-1 MAKES REFERENCE TO CODE SECTION R4408.5.3.
 PLEASE CORRECT THIS CODE SECTION. THIS IS FOR SINGLE
 FAMILY RESIDENCES, STEEL IN THE HIGH-VELOCITY HURRICANE
 ZONES. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS.
 2014 FBC-B 2204.1 WELDING
 201404.4.2 BOLTING.
  
 4) SHEET S-2 INDICATES THE REPLACEMENT COOLING TOWER
 CT-1 TO BE A MARLEY 23121. PLEASE PROVIDE MANUFACTURERS
 PRODUCT INFORMATION THAT THIS MECHANICAL EQUIPMENT THAT
 IS EXPOSED TO WIND WAS DESIGNED TO RESIST WIND
 PRESSURES FOR THIS WIND SPEED AND ELEVATION. 2014 FBC-M
 301.15 WIND RESISTANCE.
  
 5) SHEET S1 AND S2 SHOW THE STEEL FRAMING SUPPORT
 STRUCTURE THE REPLACEMENT COOLING TOWER WILL REST UPON.
 THESE SHEETS SHOW BOTH WELDED AND BOLTED CONNECTIONS
 FROM STEEL FRAMING TO THE BUILDING STRUCTURE AND THE
 FRAMEWORK. WHAT THIS PLAN DOESN?T INDICATE IS THE
 CONNECTION FROM THE SUPPORT STEEL FRAMING TO THE
 COOLING TOWER.
  
 LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 THE PLAN REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-17 Cont ID  
Sent By jpearson Date 2017-11-17 Time 10:45 Rev Time 0.00
Received By jpearson Date 2017-11-17 Time 10:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-29 Cont ID  
Sent By rlecky Date 2016-12-29 Time 13:52 Rev Time 0.00
Received By rlecky Date 2016-12-29 Time 12:39 Sent To  
Notes
2016-12-29 13:53:1916120363
 3800 WASHINGTON ROAD
 NEW COOLING TOWER
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 INDICATE SIZE OF EXISTING DISCONNECTS AND AND MOTOR
 CIRCUITS. VERIFY THE EXISTING CIRCUITS ARE ADEQUATE TO
 FEED THE NEW EQUIPMENT. PROVIDE A FEEDER DETAIL. NEC
 215.5. 430.22
  
 PROVIDE MOTOR OVERLOAD PROTECTION. NEC 430.32
  
 PROVIDE MOTOR BRANCH CIRCUIT SHORT CIRCUIT AND GROUND
 FAULT PROTECTION. NEC 430.51
  
 PROVIDE SAFE WORKING SPACE FOR DISCONNECTS. NEC 110.26
  
 EQUIPMENT LIKELY TO BE SERVICE WHILE ENERGIZED MUST
 HAVE SAFETY WARNING LABELS TO PROTECT FROM ARC FLASH
 HAZARD. NEC 110.16
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-02-27 Cont ID  
Sent By pleduc Date 2018-02-27 Time   Rev Time 0.00
Received By pleduc Date 2018-02-27 Time 13:02 Sent To  
Notes
2018-02-27 13:07:35FIRE COMMENTS WERE NOT SPECIFICALLY ADDRESS.
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS INSUFFICIENT DETAIL PROVIDING FOR THE
 COMPLIANCE OF THE REQUIREMENTS OF ANY NFPA FIRE CODES.
  
 NFPA CODES AND/OR STANDARDS WILL BE WHAT FIRE
 INSPECTIONS WILL BE BASED, PLEASE ENSURE COMPLAINCE.
  
  
  
 2) PLEASE PROVIDE DETAILED INFOMATION AND NOTE
 INDICATING COMPLIANCE WITH NFPA 780 - LIGHTNING
 PROTECTION SYSTEMS.
  
 5.7* LIGHTNING PROTECTION. LIGHTNING PROTECTION, WHERE
 PROVIDED, SHALL BE INSTALLED IN ACCORDANCE WITH THE
 PROVISIONS OF NFPA 780.
  
  
 3) PLEASE PROVIDE DETAILED INFORMATION INDICATING
 COMPLIANCE WITH NFPA 214 - WATER-COOLING TOWERS
  
 INCLUDING, BUT NO LIMITED TO:
  
 CHAPTER 4 LOCATION OF WATER-COOLING TOWERS
 4.1 CONSTRUCTION MATERIALS OF WATER-COOLING TOWERS.
 4.1.1 WHERE THE COOLING TOWER'S STRUCTURE, FAN,
 DISTRIBUTION SYSTEM, LOUVERS, AND FILL AND DRIFT
 ELIMINATOR MATERIALS ARE ALL OF NONCOMBUSTIBLE
 MATERIALS, A FIRE PROTECTION SYSTEM SHALL NOT BE
 REQUIRED.
 4.1.2 IF ANY OF THE CONSTRUCTION MATERIALS ARE
 COMBUSTIBLE AND THE FACTORS IN SECTION 4.2 NECESSITATE
 IT, FIRE PROTECTION SHALL BE PROVIDED IN ACCORDANCE
 WITH CHAPTER 5, AND TOWERS SHALL BE LOCATED IN
 ACCORDANCE WITH CHAPTER 4.
  
 4.2* FIRE RISK ANALYSIS. A FIRE RISK ANALYSIS SHALL BE
 CONDUCTED. THE FOLLOWING ARE SOME OF THE FACTORS THAT
 SHALL BE CONSIDERED IN DETERMINING THE EXTENT AND
 METHOD OF FIRE PROTECTION REQUIRED FOR INDUCED-DRAFT
 AND NATURAL-DRAFT WATER-COOLING TOWERS:
 (1) IMPORTANCE TO CONTINUITY OF OPERATION
 (2)*SIZE AND CONSTRUCTION OF TOWER
 (3) TYPE OF TOWER
 (4) LOCATION OF TOWER
 (5) WATER SUPPLY
 (6) VALUE OF TOWER
 (7) CLIMATE
 (8)*WATER DELIVERY TIME
 (9) ENVIRONMENT
 (10) ROOFTOP TOWERS
 (11) LIMITED ACCESS
 (12) MATERIALS OF CONSTRUCTION (SEE SECTION 4.1)
  
 4.3 COMBUSTIBLE EXTERIOR SURFACES. WATER-COOLING TOWERS
 WITH COMBUSTIBLE EXTERIOR SURFACES, INCLUDING THE DECK,
 DISTRIBUTION BASINS, AND SO FORTH, SHALL BE LOCATED AT
 LEAST 100 FT (30.5 M) FROM THE FOLLOWING HAZARDS:
 (1) STRUCTURES OR PROCESSES THAT EMIT SPARKS OR FLYING
 BRANDS UNDER ORDINARY CIRCUMSTANCES, SUCH AS CHIMNEYS,
 INCINERATORS, FLARE STACKS, OR COB BURNERS
 (2) MATERIALS OR PROCESSES OF SEVERE FIRE HAZARD, SUCH
 AS PETROLEUM PROCESSING AND STORAGE TANKS, EXPLOSIVES
 MANUFACTURING OR STORAGE, AND PETROLEUM PRODUCT
 PIPELINES AND PUMPING STATIONS
  
 4.4 COMBUSTIBLE SURFACES WITH FIXED PROTECTION. TOWERS
 WITH COMBUSTIBLE EXTERIOR SURFACES THAT ARE PROVIDED
 WITH FIXED EXPOSURE PROTECTION IN ACCORDANCE WITH
 5.2.10 SHALL BE PERMITTED TO BE LOCATED CLOSER THAN 100
 FT (30.5 M) FROM THE HAZARDS
 LISTED IN SECTION 4.3.
  
 4.5 NONCOMBUSTIBLE EXTERIOR SURFACES. TOWERS WITH
 NONCOMBUSTIBLE EXTERIOR SURFACES SHALL BE LOCATED 40 FT
 (12 M) OR MORE FROM THE HAZARDS LISTED IN SECTION 4.3.
  
 4.6 NONCOMBUSTIBLE SURFACES WITH FIXED PROTECTION.
 TOWERS WITH NONCOMBUSTIBLE EXTERIOR SURFACES THAT ARE
 PROVIDED WITH FIXED INTERIOR FIRE PROTECTION INSTALLED
 IN ACCORDANCE WITH CHAPTER 5 SHALL BE PERMITTED TO BE
 LOCATED CLOSER THAN 40 FT (12 M) FROM THE HAZARDS
 LISTED IN SECTION 4.3.
  
 4.7 COMBUSTIBLE TOWERS ON BUILDING ROOFS. COMBUSTIBLE
 WATER-COOLING TOWERS LOCATED ON BUILDING ROOFS OR OTHER
 LOCATIONS TO WHICH ACCESS FOR MANUAL FIRE FIGHTING IS
 RESTRICTED OR DIFFICULT SHALL BE PROVIDED WITH A
 PROTECTION SYSTEM IN ACCORDANCE WITH CHAPTER 5.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-11-13 Cont ID  
Sent By pleduc Date 2017-11-13 Time   Rev Time 0.00
Received By pleduc Date 2017-11-13 Time 12:26 Sent To  
Notes
2017-11-13 13:02:062ND REVIEW
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATIONS EITHER ON THE PLAN SHEETS
 NOR A WRITTEN NARRATIVE ADDRESSING ANY OF FIRE
 COMMENTS.
  
 THEY ARE RE-POSTED BELOW:
  
  
  
 1) THERE IS INSUFFICIENT DETAIL PROVIDING FOR THE
 COMPLIANCE OF THE REQUIREMENTS OF ANY NFPA FIRE CODES.
  
  
  
 2) PLEASE PROVIDE DETAILED INFOMATION AND NOTE
 INDICATING COMPLIANCE WITH NFPA 780 - LIGHTNING
 PROTECTION SYSTEMS.
  
 5.7* LIGHTNING PROTECTION. LIGHTNING PROTECTION, WHERE
 PROVIDED, SHALL BE INSTALLED IN ACCORDANCE WITH THE
 PROVISIONS OF NFPA 780.
  
  
 3) PLEASE PROVIDE DETAILED INFORMATION INDICATING
 COMPLIANCE WITH NFPA 214 - WATER-COOLING TOWERS
  
 INCLUDING, BUT NO LIMITED TO:
  
 CHAPTER 4 LOCATION OF WATER-COOLING TOWERS
 4.1 CONSTRUCTION MATERIALS OF WATER-COOLING TOWERS.
 4.1.1 WHERE THE COOLING TOWER'S STRUCTURE, FAN,
 DISTRIBUTION SYSTEM, LOUVERS, AND FILL AND DRIFT
 ELIMINATOR MATERIALS ARE ALL OF NONCOMBUSTIBLE
 MATERIALS, A FIRE PROTECTION SYSTEM SHALL NOT BE
 REQUIRED.
 4.1.2 IF ANY OF THE CONSTRUCTION MATERIALS ARE
 COMBUSTIBLE AND THE FACTORS IN SECTION 4.2 NECESSITATE
 IT, FIRE PROTECTION SHALL BE PROVIDED IN ACCORDANCE
 WITH CHAPTER 5, AND TOWERS SHALL BE LOCATED IN
 ACCORDANCE WITH CHAPTER 4.
  
 4.2* FIRE RISK ANALYSIS. A FIRE RISK ANALYSIS SHALL BE
 CONDUCTED. THE FOLLOWING ARE SOME OF THE FACTORS THAT
 SHALL BE CONSIDERED IN DETERMINING THE EXTENT AND
 METHOD OF FIRE PROTECTION REQUIRED FOR INDUCED-DRAFT
 AND NATURAL-DRAFT WATER-COOLING TOWERS:
 (1) IMPORTANCE TO CONTINUITY OF OPERATION
 (2)*SIZE AND CONSTRUCTION OF TOWER
 (3) TYPE OF TOWER
 (4) LOCATION OF TOWER
 (5) WATER SUPPLY
 (6) VALUE OF TOWER
 (7) CLIMATE
 (8)*WATER DELIVERY TIME
 (9) ENVIRONMENT
 (10) ROOFTOP TOWERS
 (11) LIMITED ACCESS
 (12) MATERIALS OF CONSTRUCTION (SEE SECTION 4.1)
  
 4.3 COMBUSTIBLE EXTERIOR SURFACES. WATER-COOLING TOWERS
 WITH COMBUSTIBLE EXTERIOR SURFACES, INCLUDING THE DECK,
 DISTRIBUTION BASINS, AND SO FORTH, SHALL BE LOCATED AT
 LEAST 100 FT (30.5 M) FROM THE FOLLOWING HAZARDS:
 (1) STRUCTURES OR PROCESSES THAT EMIT SPARKS OR FLYING
 BRANDS UNDER ORDINARY CIRCUMSTANCES, SUCH AS CHIMNEYS,
 INCINERATORS, FLARE STACKS, OR COB BURNERS
 (2) MATERIALS OR PROCESSES OF SEVERE FIRE HAZARD, SUCH
 AS PETROLEUM PROCESSING AND STORAGE TANKS, EXPLOSIVES
 MANUFACTURING OR STORAGE, AND PETROLEUM PRODUCT
 PIPELINES AND PUMPING STATIONS
  
 4.4 COMBUSTIBLE SURFACES WITH FIXED PROTECTION. TOWERS
 WITH COMBUSTIBLE EXTERIOR SURFACES THAT ARE PROVIDED
 WITH FIXED EXPOSURE PROTECTION IN ACCORDANCE WITH
 5.2.10 SHALL BE PERMITTED TO BE LOCATED CLOSER THAN 100
 FT (30.5 M) FROM THE HAZARDS
 LISTED IN SECTION 4.3.
  
 4.5 NONCOMBUSTIBLE EXTERIOR SURFACES. TOWERS WITH
 NONCOMBUSTIBLE EXTERIOR SURFACES SHALL BE LOCATED 40 FT
 (12 M) OR MORE FROM THE HAZARDS LISTED IN SECTION 4.3.
  
 4.6 NONCOMBUSTIBLE SURFACES WITH FIXED PROTECTION.
 TOWERS WITH NONCOMBUSTIBLE EXTERIOR SURFACES THAT ARE
 PROVIDED WITH FIXED INTERIOR FIRE PROTECTION INSTALLED
 IN ACCORDANCE WITH CHAPTER 5 SHALL BE PERMITTED TO BE
 LOCATED CLOSER THAN 40 FT (12 M) FROM THE HAZARDS
 LISTED IN SECTION 4.3.
  
 4.7 COMBUSTIBLE TOWERS ON BUILDING ROOFS. COMBUSTIBLE
 WATER-COOLING TOWERS LOCATED ON BUILDING ROOFS OR OTHER
 LOCATIONS TO WHICH ACCESS FOR MANUAL FIRE FIGHTING IS
 RESTRICTED OR DIFFICULT SHALL BE PROVIDED WITH A
 PROTECTION SYSTEM IN ACCORDANCE WITH CHAPTER 5.
  
  
  
 4) PROVIDE MANUFACTURES SPECIFICATION / PRODUCTS SHEETS
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-12-21 Cont ID  
Sent By pleduc Date 2016-12-21 Time   Rev Time 0.00
Received By pleduc Date 2016-12-21 Time 13:17 Sent To  
Notes
2016-12-21 13:29:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT DETAIL PROVIDING FOR THE
 COMPLIANCE OF THE REQUIREMENTS OF ANY NFPA FIRE CODES.
  
  
  
 2) PLEASE PROVIDE DETAILED INFOMATION AND NOTE
 INDICATING COMPLIANCE WITH NFPA 780 - LIGHTNING
 PROTECTION SYSTEMS.
  
 5.7* LIGHTNING PROTECTION. LIGHTNING PROTECTION, WHERE
 PROVIDED, SHALL BE INSTALLED IN ACCORDANCE WITH THE
 PROVISIONS OF NFPA 780.
  
  
 3) PLEASE PROVIDE DETAILED INFORMATION INDICATING
 COMPLIANCE WITH NFPA 214 - WATER-COOLING TOWERS
  
 INCLUDING, BUT NO LIMITED TO:
  
 CHAPTER 4 LOCATION OF WATER-COOLING TOWERS
 4.1 CONSTRUCTION MATERIALS OF WATER-COOLING TOWERS.
 4.1.1 WHERE THE COOLING TOWER'S STRUCTURE, FAN,
 DISTRIBUTION SYSTEM, LOUVERS, AND FILL AND DRIFT
 ELIMINATOR MATERIALS ARE ALL OF NONCOMBUSTIBLE
 MATERIALS, A FIRE PROTECTION SYSTEM SHALL NOT BE
 REQUIRED.
 4.1.2 IF ANY OF THE CONSTRUCTION MATERIALS ARE
 COMBUSTIBLE AND THE FACTORS IN SECTION 4.2 NECESSITATE
 IT, FIRE PROTECTION SHALL BE PROVIDED IN ACCORDANCE
 WITH CHAPTER 5, AND TOWERS SHALL BE LOCATED IN
 ACCORDANCE WITH CHAPTER 4.
  
 4.2* FIRE RISK ANALYSIS. A FIRE RISK ANALYSIS SHALL BE
 CONDUCTED. THE FOLLOWING ARE SOME OF THE FACTORS THAT
 SHALL BE CONSIDERED IN DETERMINING THE EXTENT AND
 METHOD OF FIRE PROTECTION REQUIRED FOR INDUCED-DRAFT
 AND NATURAL-DRAFT WATER-COOLING TOWERS:
 (1) IMPORTANCE TO CONTINUITY OF OPERATION
 (2)*SIZE AND CONSTRUCTION OF TOWER
 (3) TYPE OF TOWER
 (4) LOCATION OF TOWER
 (5) WATER SUPPLY
 (6) VALUE OF TOWER
 (7) CLIMATE
 (8)*WATER DELIVERY TIME
 (9) ENVIRONMENT
 (10) ROOFTOP TOWERS
 (11) LIMITED ACCESS
 (12) MATERIALS OF CONSTRUCTION (SEE SECTION 4.1)
  
 4.3 COMBUSTIBLE EXTERIOR SURFACES. WATER-COOLING TOWERS
 WITH COMBUSTIBLE EXTERIOR SURFACES, INCLUDING THE DECK,
 DISTRIBUTION BASINS, AND SO FORTH, SHALL BE LOCATED AT
 LEAST 100 FT (30.5 M) FROM THE FOLLOWING HAZARDS:
 (1) STRUCTURES OR PROCESSES THAT EMIT SPARKS OR FLYING
 BRANDS UNDER ORDINARY CIRCUMSTANCES, SUCH AS CHIMNEYS,
 INCINERATORS, FLARE STACKS, OR COB BURNERS
 (2) MATERIALS OR PROCESSES OF SEVERE FIRE HAZARD, SUCH
 AS PETROLEUM PROCESSING AND STORAGE TANKS, EXPLOSIVES
 MANUFACTURING OR STORAGE, AND PETROLEUM PRODUCT
 PIPELINES AND PUMPING STATIONS
  
 4.4 COMBUSTIBLE SURFACES WITH FIXED PROTECTION. TOWERS
 WITH COMBUSTIBLE EXTERIOR SURFACES THAT ARE PROVIDED
 WITH FIXED EXPOSURE PROTECTION IN ACCORDANCE WITH
 5.2.10 SHALL BE PERMITTED TO BE LOCATED CLOSER THAN 100
 FT (30.5 M) FROM THE HAZARDS
 LISTED IN SECTION 4.3.
  
 4.5 NONCOMBUSTIBLE EXTERIOR SURFACES. TOWERS WITH
 NONCOMBUSTIBLE EXTERIOR SURFACES SHALL BE LOCATED 40 FT
 (12 M) OR MORE FROM THE HAZARDS LISTED IN SECTION 4.3.
  
 4.6 NONCOMBUSTIBLE SURFACES WITH FIXED PROTECTION.
 TOWERS WITH NONCOMBUSTIBLE EXTERIOR SURFACES THAT ARE
 PROVIDED WITH FIXED INTERIOR FIRE PROTECTION INSTALLED
 IN ACCORDANCE WITH CHAPTER 5 SHALL BE PERMITTED TO BE
 LOCATED CLOSER THAN 40 FT (12 M) FROM THE HAZARDS
 LISTED IN SECTION 4.3.
  
 4.7 COMBUSTIBLE TOWERS ON BUILDING ROOFS. COMBUSTIBLE
 WATER-COOLING TOWERS LOCATED ON BUILDING ROOFS OR OTHER
 LOCATIONS TO WHICH ACCESS FOR MANUAL FIRE FIGHTING IS
 RESTRICTED OR DIFFICULT SHALL BE PROVIDED WITH A
 PROTECTION SYSTEM IN ACCORDANCE WITH CHAPTER 5.
  
  
  
 4) PROVIDE MANUFACTURES SPECIFICATION / PRODUCTS SHEETS
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-08 Cont ID  
Sent By gjohnson Date 2018-03-08 Time 14:25 Rev Time 0.00
Received By gjohnson Date 2018-02-22 Time 10:49 Sent To  
Notes
2018-02-23 10:49:19B29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 16:16 Rev Time 0.00
Received By gjohnson Date 2017-11-08 Time 13:12 Sent To  
Notes
2017-11-09 13:12:59B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 17:28 Rev Time 0.00
Received By gjohnson Date 2016-12-09 Time 11:21 Sent To  
Notes
2016-12-13 11:21:36B02

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-03-05 Cont ID  
Sent By ccole Date 2018-03-05 Time 13:48 Rev Time 0.00
Received By ccole Date 2018-03-05 Time 13:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-14 Cont ID  
Sent By ccole Date 2017-11-14 Time 07:52 Rev Time 0.00
Received By ccole Date 2017-11-13 Time 17:27 Sent To  
Notes
2017-11-14 07:55:152ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16120363
 11/14/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 SOME OF THE COMMENTS FROM THE 1ST REVIEW WERE ADDRESSED
 AND STILL EXIST. I HAVE REPRINTED THOSE COMMENTS BELOW
 WITH ADDITIONAL REMARKS BASED ON THE NARRATIVE RESPONSE
 FROM KAMM ENGINEERING
  
 2) S-2: REFER TO TABLE 1509.6.5 FBC-14 BUILDING:
 MINIMUM 48 INCHES CLEARANCE DISTANCE REQUIRED BELOW THE
 NEW TOWER. (KAMM'S RESPONSE- "TO BE PROVIDED BY
 STRUCTURAL ENGINEER").
  
 4) PROVIDE DETAILS AND DRAWINGS FOR THE ACCESS LADDER
 AND SERVICE PLATFORM- SEE SECTIONS 304.11, 306.1, &
 306.5. *(KAMM'S RESPONSE- "NOT REQUIRED PER
 MANUFACTURER'S DRAWINGS".)
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE TOWER.
 (KAMM'S RESPONSE- "TO BE PROVIDED BY THE CONTRACTOR").
  
 6) COMMISSIONING OF THE SYSTEM IS REQUIRED IN
 ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY
 CONSERVATION. PLEASE SUBMIT A COMMISSIONING PLAN IN
 COMPLIANCE WITH SECTION C408.2.1. (KAMM'S RESPONSE-
 "COMMISSIONING IS NOT REQUIRED PER SECTION C101.4.8
 FBC-14 ENERGY CONSERVATION"). IT IS AGREED THAT THE
 BUILDING IS EXEMPT, HOWEVER THE NEW COOLING TOWER,
 PUMPS, TREATMENT
  
 SYSTEM, AND NEW PIPINGS MUST BE TESTED TO VERIFY WATER
 TEMPERATURES AND FLOWS ARE PER PLAN AND SPECIFICATIONS.
 PLEASE PROVIDE A NARRATIVE CLARIFYING WHAT TESTING WILL
 BE PERFORMED ON THE NEW EQUIPMENT- SECTION C408.2
 MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION
 REQUIREMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-19 Cont ID  
Sent By ccole Date 2016-12-19 Time 08:46 Rev Time 0.00
Received By ccole Date 2016-12-19 Time 07:45 Sent To  
Notes
2016-12-19 09:03:441ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16120363
 12/19/16
  
 1) SHEETS S-2 & M6.1: DIMENSIONS OF THE TOWER DON'T
 MATCH.
  
 2) S-2: REFER TO TABLE 1509.6.5 FBC-14 BUILDING:
 MINIMUM 48 INCHES CLEARANCE DISTANCE REQUIRED BELOW THE
 NEW TOWER.
  
 3) PROVIDE PIPING AND PIPE INSULATION SPECIFICATIONS.
  
 4) PROVIDE DETAILS AND DTRAWINGS FOR THE ACCESS LADDER
 AND SERVICE PLATFORM- SEE SECTIONS 304.11, 306.1, &
 306.5
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE TOWER.
  
 6) COMMISSIONING OF THE SYSTEM IS REQUIRED IN
 ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY
 CONSERVATION. PLEASE SUBMIT A COMMISSIONING PLAN IN
 COMPLIANCE WITH SECTION C408.2.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-03-08 Cont ID  
Sent By gjohnson Date 2018-03-08 Time 14:24 Rev Time 0.00
Received By gjohnson Date 2018-03-08 Time 14:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 16:16 Rev Time 0.00
Received By gjohnson Date 2017-11-21 Time 15:31 Sent To  
Notes
2017-11-21 16:16:361ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. M2.1 NOTE ON 2" DRAIN AND OVERFLOW REF TO SHT.
 P0.1 THE PLAN SET IS MISSING SHT. P0.1 PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
 2. IS THE 2" DRAIN AND OVER FLOW NEW OR EXISTING PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 17:28 Rev Time 0.00
Received By gjohnson Date 2017-01-12 Time 17:28 Sent To  
Notes
***NONE***

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2017-11-08 Cont ID  
Sent By rbrown Date 2017-11-08 Time 11:27 Rev Time 0.00
Received By rbrown Date 2017-11-08 Time 11:27 Sent To  
Notes
2017-11-08 11:31:39CONTRACTOR REQUESTS EXTENSION OF PERMIT APPLICATION
 BASED ON CONDO ASSOCIATION DECISION ONJANUARY 17, 2017,
 TO DEFER INSTALLATION UNTIL JANUARY 2018. CONTRACTOR
 PROVIDED A COPY OF THE JANUARY 17, 2017 MINUTES OF
 CONDO ASSOCIATION BOARD OF DIRECTOR'S MEETING. OK TO
 EXTEND PERMIT APPLICATION.