Plan Review Details - Permit 16120345
Plan Review Stops For Permit 16120345
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-24 Cont ID  
Sent By shill Date 2017-03-24 Time 17:11 Rev Time 0.00
Received By shill Date 2017-03-24 Time 17:11 Sent To  
Notes
2017-03-24 17:12:57PROVISO
  
 "BUILDING UNDER CONSTRUCTION" ELEVATION
 CERTIFICATE REQUIRED PRIOR TO CONCRETE POUR
  
 "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE
 REQUIRED PRIOR TO FINAL INSPECTION
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-27 Cont ID  
Sent By jwitmer Date 2016-12-27 Time 07:42 Rev Time 0.00
Received By jwitmer Date 2016-12-27 Time 07:40 Sent To  
Notes
2016-12-27 07:41:52BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120345
 ADD: 1301 SUMMIT BLVD. / PHASE 2 / WEST TICKET BOOTH
 CONT: GAST CONSTRUCTION
 TEL: 561-797-5907
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. DEC. 27/2016
 ACTION: DENIED
  
 1) PLEASE NOTE THIS PROPERTY IS LOCATED WITHIN THE
 FLOOD ZONE TYPE A7 BASE FLOOD ELEVATION 12 FEET NGVD.
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION
 IF PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. NOTE FOR PLAN REVIEW DOCUMENTS LINE C1OF THE
 FLOOD ZONE CERTIFICATE, THE CONSTRUCTION DRAW BOX
 SHOULD BE CHECKED!!!!!
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) SHEET E-1.1 SHOWS EXTERIOR YARD LIGHTING. SHEET A2.0
 DETAILS 2 & 3 BOTH SHOW NEW A/C COMPRESSOR PADS PLEASE
 PROVIDE THE PROPOSED HEIGHTS OF THESE ELEMENTS AND
 COMPLIANCE WITH THE FLOOD ZONE CERTIFICATE LINE C2 (E).
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.5.1 DESIGN FLOOD ELEVATIONS. WHERE
 DESIGN FLOOD ELEVATIONS ARE NOT SPECIFIED, THEY SHALL
 BE ESTABLISHED IN ACCORDANCE WITH SECTION 1612.3.1.
 2014 FBC-B 1612.3.1 DESIGN FLOOD ELEVATIONS.
  
 3) SHEET A2.0 DOES NOT PROVIDE WHAT THE FINISH FLOOR
 ELEVATIONS OF EITHER TICKET BOOTHS ARE? SHEET A5.0
 SHOWS AN EXTERIOR VIEW OF THE TICKET BOOTHS AND THE
 PROPOSED PATHWAY AT AN ELEVATION OF 0 FEET- 0 INCHES
 FINISH FLOOR ELEVATION. SHEET S-2.1 ALSO SHOWS A FINISH
 FLOOR ELEVATION OF 0 FEET. PLEASE PROVIDE THE FINISH
 FLOOR ELEVATION OF THE TICKET BOOTHS IN NGVD AND
 COMPLIANCE WITH 1612.3.1. 2014 FBC-B 1612.3.1 DESIGN
 FLOOD ELEVATIONS AND TTHE CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546.
  
 4) KAWNEER PRODUCT APPROVALS FOR 350/500 -IR OUTSWING
 DOORS AND KAWNEER PRODUCT APPROVAL REPORT FOR 8400
 LARGE MISSILE IMPACT SLIDING GLASS WINDOWS BOTH NEED TO
 APPLY FOR A LOCAL PRODUCT APPROVAL COMPLETING THE CITY
 OF WEST PALM BEACH LOCAL PRODUCT APPROVAL FORMS AND BE
 RETURNED TO THE BUILDING DEPARTMENT FOR REVIEW BY THE
 W. P. B. BUILDING OFFICIAL.
  
 FORMS SENT TO JEFF/ [email protected]
 12/27/2016 08:02 AM. ,
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-24 Cont ID  
Sent By vperez Date 2017-03-24 Time 10:44 Rev Time 0.00
Received By vperez Date 2017-03-24 Time 10:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-28 Cont ID  
Sent By vperez Date 2016-12-28 Time 13:42 Rev Time 0.00
Received By vperez Date 2016-12-28 Time 13:42 Sent To  
Notes
2016-12-28 13:53:13INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 SITE LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE
 SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM, SOLAR
 PANELS, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, ETC. A
 NOTE WILL SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 AND COMPLETIONS DOCUMENTS.
 3. PROVIDE A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT
 AND APPARATUSES ABOVE THE FLOOD PLAIN LEVEL.
 4. PLEASE ADDRESS FIRE COMMENTS RELATED TO EM LIGHTING
 REQUIREMENTS.
 5. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 6. SOLAR SYSTEM SHOWN ON THESE DOCUMENTS WILL BE
 SUBJECT TO A COMPLETE REVIEW UPON SEPARATE PERMIT
 APPLICATION. NOTE THAT ALL NEC 690 REQUIREMENTS MUST BE
 MET, EXAMPLE: GROUNDING SCHEME, BACK FED BREAKER SHOWN
 ON LOAD CENTER P2, SIGNAGE ETC.?
 7. SHEET E2: LABEL ALL W/P RECEPTACLES TO BE GFCI
 PROTECTED PER NEC 210.8B
 8. PROVIDE A GENERAL NOTE TO INDICATE NEC 300.5 BURIAL
 DEPTH REQUIREMENTS FOR ALL U/G CONDUITS.
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-02-21 Cont ID  
Sent By Mgonzale Date 2017-02-21 Time   Rev Time 0.50
Received By mgonzale Date 2017-02-21 Time   Sent To I
Notes
2017-02-21 13:01:47NO CONFLICTS WITH CITY OF WPB PUBLIC UTILITIES.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-14 Cont ID  
Sent By pleduc Date 2017-03-14 Time   Rev Time 0.00
Received By pleduc Date 2017-03-13 Time 15:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-12-20 Cont ID  
Sent By pleduc Date 2016-12-20 Time   Rev Time 0.00
Received By pleduc Date 2016-12-19 Time 15:50 Sent To  
Notes
2016-12-20 13:40:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 8.0 - A DOOR AND GATE SCHEDULE IS INDICATED;
 HOWEVER, THE EXIT DOORS, LATCHING AND LOCKING EQUIPMENT
 IS UNCLEAR. A SCHLAGE D LOCKSET IS INDICATED; HOWEVER,
 NO FURTHER INFORMATION IS INDICATED.
  
 PER NFPA 101, CHAPTER 7, 7.2.1.5.5 KEY-OPERATED LOCKS
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEY-OPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET.
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY. ( IT IS
 PERMITTED UNDER CHAPTER 38, NEW BUSINESS OCCUPANCY)
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. HIGH ON A CONTRASTING BACKGROUND THAT READS
 AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF.
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
  
 SHOULD ALL OF THE ABOVE NOT BE POSSIBLE:
  
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.10 A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS
 AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY
 OPERATED UNDER ALL LIGHTING CONDITIONS.
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF WITH NOT MORE THAN ONE RELEASING OPERATION.
  
 PLEASE PROVIDE COMPLIANCE WITH THE ABOVE REQUIREMENTS.
  
  
  
 2) SHEET A 8.0, A 5.1, & A 2.1 - A DOOR AND GATE
 SCHEDULE IS INDICATED; HOWEVER, THE EXIT GATES,
 LATCHING, LOCKING EQUIPMENT, IS UNCLEAR. THE ZOO AREA
 IS AN EXISTING ASSEMBLY AREA AND SHALL COMPLY WITH NFPA
 101, CHAPTER 13, EXISTING ASSEMBLY OCCUPANCIES. THOUGH
 IT IS AN OPEN SPACE, THE EXITS FROM THE SPACE SHALL
 COMPLY WITH THE CODE.
  
 13.2 MEANS OF EGRESS REQUIREMENTS.
 13.2.1 GENERAL. ALL MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH CHAPTER 7 AND THIS CHAPTER.
 13.2.2 MEANS OF EGRESS COMPONENTS.
 13.2.2.1 COMPONENTS PERMITTED. COMPONENTS OF MEANS OF
 EGRESS SHALL BE LIMITED TO THE TYPES DESCRIBED IN
 13.2.2.2 THROUGH
 13.2.2.12.
 13.2.2.2 DOORS
 13.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR FIRE
 EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS OTHERWISE
 PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS PERMITTED IN 13.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS AS PERMITTED IN
 13.2.2.2.6. 13.2.2.2.4 LOCKING DEVICES COMPLYING WITH
 7.2.1.5.5 SHALL BE PERMITTED TO BE USED ON A SINGLE
 DOOR OR A SINGLE PAIR OF DOORS IF BOTH OF THE FOLLOWING
 CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 FROM ASSEMBLY OCCUPANCIES HAVING AN OCCUPANT LOAD NOT
 GREATER THAN 600.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR
 MORE ARE RELEASED BY PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 PLEASE PROVIDE SPECIFIC DETAIL OF HOW THE LOCKS AND
 LATCHES TO THE EXIT GATES OF THE PROPOSED PROJECT
 COMPLY WITH ABOVE NOTED REQUIRERMENTS.
  
  
  
  
 3) SHEET A 1.0 - EXIT SIGNAGE IS NOT INDICATED.
  
 13.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF
 EGRESS, OTHER THAN FOR PRIVATE PARTY TENTS NOT
 EXCEEDING 1200 FT2 (112 M2), SHALL BE ILLUMINATED IN
 ACCORDANCE WITH SECTION 7.8.
 13.2.9 EMERGENCY LIGHTING.
 13.2.9.1 EMERGENCY LIGHTING, OTHER THAN THAT PERMITTED
 BY 13.2.9.3, SHALL BE PROVIDED IN ACCORDANCE WITH
 SECTION 7.9.
 13.2.9.2 PRIVATE PARTY TENTS NOT EXCEEDING 1200 FT2
 (112 M2) SHALL NOT BE REQUIRED TO HAVE EMERGENCY
 LIGHTING.
 13.2.9.3 ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD NOT
 EXCEEDING 300 AND USED EXCLUSIVELY FOR A PLACE OF
 WORSHIP SHALL NOT BE REQUIRED TO HAVE EMERGENCY
 LIGHTING.
 13.2.10 MARKING OF MEANS OF EGRESS.
 13.2.10.1 MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS
 IN ACCORDANCE WITH SECTION 7.10.
 13.2.10.2 EXIT MARKINGS SHALL NOT BE REQUIRED ON THE
 SEATING SIDE OF VOMITORIES FROM SEATING AREAS WHERE
 EXIT MARKING IS PROVIDED IN THE CONCOURSE AND WHERE
 SUCH MARKING IS READILY APPARENT FROM THE VOMITORIES.
 13.2.10.3 EVACUATION DIAGRAMS IN ACCORDANCE WITH
 7.10.8.5 SHALL BE PROVIDED.
  
 PLEASE SPECIFIC DETAIL HOW YOU WILL COMPLY WITH THE
 ABOVE REQUIREMENTS.
  
  
  
 4) SHEET A 10.0 - A GREEN SCEEN IS INDICATED.
 INFORMATION REGARDING THE SCEEN PRODUCT WAS NOT EASILY
 INDENTIFIABLE.
  
 PLEASE PROVIDE PRODUCT SPECIFICATIONS REGARDING FIRE
 RETARDENT, FLAMMABILITY AND/OR SMOKE GENERATION.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-28 Cont ID  
Sent By cpuell Date 2017-03-28 Time 14:59 Rev Time 0.00
Received By cpuell Date 2017-03-01 Time 12:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-01 Cont ID  
Sent By skennedy Date 2017-03-01 Time 11:12 Rev Time 0.00
Received By skennedy Date 2016-12-09 Time 15:50 Sent To  
Notes
2016-12-12 15:51:07C19
 **TRAVELLING WITH 16120343 & 16120344**

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-12-27 Cont ID  
Sent By jwitmer Date 2016-12-27 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2016-12-27 Time 07:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-12-29 Cont ID  
Sent By ccole Date 2016-12-29 Time 17:12 Rev Time 0.00
Received By ccole Date 2016-12-29 Time 17:12 Sent To  
Notes
2016-12-29 17:17:08MECHANICAL PROVISO
  
 1) COMPLY WITH NFIP REQUIRMENTS.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2017-03-24 Cont ID  
Sent By shill Date 2017-03-24 Time 17:13 Rev Time 0.00
Received By shill Date 2017-03-24 Time 17:13 Sent To  
Notes
2017-03-24 17:13:29PROVISO
  
 "BUILDING UNDER CONSTRUCTION" ELEVATION
 CERTIFICATE REQUIRED PRIOR TO CONCRETE POUR
  
 "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE
 REQUIRED PRIOR TO FINAL INSPECTION
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2016-12-27 Cont ID  
Sent By jwitmer Date 2016-12-27 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2016-12-27 Time 07:41 Sent To  
Notes
2016-12-27 07:42:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120345
 ADD: 1301 SUMMIT BLVD. / PHASE 2 / WEST TICKET BOOTH
 CONT: GAST CONSTRUCTION
 TEL: 561-797-5907
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. DEC. 27/2016
 ACTION: DENIED
  
 1) PLEASE NOTE THIS PROPERTY IS LOCATED WITHIN THE
 FLOOD ZONE TYPE A7 BASE FLOOD ELEVATION 12 FEET NGVD.
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION
 IF PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. NOTE FOR PLAN REVIEW DOCUMENTS LINE C1OF THE
 FLOOD ZONE CERTIFICATE, THE CONSTRUCTION DRAW BOX
 SHOULD BE CHECKED!!!!!
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) SHEET E-1.1 SHOWS EXTERIOR YARD LIGHTING. SHEET A2.0
 DETAILS 2 & 3 BOTH SHOW NEW A/C COMPRESSOR PADS PLEASE
 PROVIDE THE PROPOSED HEIGHTS OF THESE ELEMENTS AND
 COMPLIANCE WITH THE FLOOD ZONE CERTIFICATE LINE C2 (E).
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.5.1 DESIGN FLOOD ELEVATIONS. WHERE
 DESIGN FLOOD ELEVATIONS ARE NOT SPECIFIED, THEY SHALL
 BE ESTABLISHED IN ACCORDANCE WITH SECTION 1612.3.1.
 2014 FBC-B 1612.3.1 DESIGN FLOOD ELEVATIONS.
  
 3) SHEET A2.0 DOES NOT PROVIDE WHAT THE FINISH FLOOR
 ELEVATIONS OF EITHER TICKET BOOTHS ARE? SHEET A5.0
 SHOWS AN EXTERIOR VIEW OF THE TICKET BOOTHS AND THE
 PROPOSED PATHWAY AT AN ELEVATION OF 0 FEET- 0 INCHES
 FINISH FLOOR ELEVATION. SHEET S-2.1 ALSO SHOWS A FINISH
 FLOOR ELEVATION OF 0 FEET. PLEASE PROVIDE THE FINISH
 FLOOR ELEVATION OF THE TICKET BOOTHS IN NGVD AND
 COMPLIANCE WITH 1612.3.1. 2014 FBC-B 1612.3.1 DESIGN
 FLOOD ELEVATIONS AND TTHE CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-01-20 Cont ID  
Sent By gjohnson Date 2017-01-17 Time 10:44 Rev Time 0.00
Received By gjohnson Date 2017-01-17 Time 15:49 Sent To  
Notes
2017-01-17 15:56:39PLUMBING AND IRRIGATION APPROVED /GPJ

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2017-03-24 Cont ID  
Sent By shill Date 2017-03-24 Time 18:08 Rev Time 0.00
Received By shill Date 2017-03-24 Time 18:08 Sent To  
Notes
2017-03-24 18:08:44PORTICO - NOA 16-0510.23 SUBMITTED (OK)
  
 NOA 15-1026.10 WAS SUBMITTED FOR THE TICKET BOOTH
 ROOFS. THE ASSEMBLY PROPOSED WAS NOT SELECTED, AND
 ENGINEERING (IF APPLICABLE) WAS NOT SUBMITTED.
  
 A SEPARATE ROOF PERMIT IS REQUIRED. WHEN SUBMITTING,
 INDICATE PROPOSED ASSEMBLY FOR THE FLAT ROOFS.
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-03-28 Cont ID  
Sent By jroach Date 2017-03-28 Time 11:49 Rev Time 0.00
Received By jroach Date 2017-03-28 Time 11:49 Sent To  
Notes
2017-03-28 11:50:01ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.28.2017
 PERMIT NO.: 16120343, 16120344, 16120345
 ADDRESS: 1301 SUMMIT BOULEVARD
 CONTRACTOR/CONTACT: ALLEN GAST
 TELEPHONE NO.: 561.281.1001
 SCOPE OF REVIEW: NEW ENTRY.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. ALL LANDSCAPING SHALL BE INSTALLED UNDER A SEPARATE
 PERMIT.
  
 2. ALL SIGNAGE SHALL BE SUBMITTED UNDER SEPARATE PERMIT
 AND SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 94-408(F) OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-01-13 Cont ID  
Sent By jroach Date 2017-01-13 Time 11:39 Rev Time 0.00
Received By jroach Date 2017-01-13 Time 11:39 Sent To  
Notes
2017-01-13 15:54:44ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.13.2017
 PERMIT NO.: 16121343, 16120344, 16120345
 ADDRESS: 1301 SUMMIT BOULEVARD
 CONTRACTOR/CONTACT: ALLEN GAST
 TELEPHONE NO.: 561.281.1001
 SCOPE OF REVIEW: NEW ENTRY.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO THE PALM BEACH ZOO'S LEASE AGREEMENT
 WITH THE CITY OF WEST PALM BEACH, INDIVIDUAL STRUCTURES
 OR IMPROVEMENTS IN EXCESS OF $5,000 ARE TO BE SUBMITTED
 TO THE CITY COMMISSION FOR PRIOR APPROVAL AS SUCH
 IMPROVEMENTS WOULD OCCUR ON CITY-OWNED PROPERTY.
  
 2. BEFORE COMMENCING THE IMPROVEMENTS, THE ZOO SHALL
 PROVIDE THE CITY'S RISK MANAGER WITH CERTIFICATES OF
 INSURANCE EVIDENCING THAT ANY CONTRACTOR(S) PERFORMING
 THE IMPROVEMENTS CARRIES COMMERCIAL GENERAL LIABILITY
 INSURANCE (INCLUDING, WITHOUT LIMITATION, CONTRACTOR?S
 LIABILITY COVERAGE), WRITTEN ON AN OCCURRENCE BASIS
 WITH A MINIMUM COMBINED SINGLE LIMIT OF $2,000,000,
 ALONG WITH WORKERS COMPENSATION INSURANCE AS REQUIRED
 BY LAW, AND INCLUDING THE CITY OF WEST PALM BEACH AS AN
 ADDITIONAL INSURED.
  
 3. ALL LANDSCAPING SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT APPLICATION.
  
 4. ALL IRRIGATION SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT APPLICATION.
  
 5. PLANS REFERENCE A NEW MONUMENT SIGN. ALL SIGNAGE
 SHALL BE SUBMITTED UNDER SEPARATE PERMIT AND SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTION 94-408(F) OF
 THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS. OF
 CONCERN IS THE MAXIMUM NUMBER OF FREESTANDING SIGNS,
 MAXIMUM SIZE OF ALL SIGNS, AND THE MAXIMUM HEIGHT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved