Plan Review Details - Permit 16120265
Plan Review Stops For Permit 16120265
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-14 Cont ID  
Sent By shill Date 2016-12-14 Time 15:00 Rev Time 0.00
Received By shill Date 2016-12-14 Time 14:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-08 Cont ID  
Sent By shill Date 2016-12-08 Time 10:08 Rev Time 0.00
Received By shill Date 2016-12-08 Time 10:08 Sent To  
Notes
2016-12-08 10:18:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE REQUIRED DESIGN PRESSURES FOR THIS JOB, 20MRH,
 EXPOSURE C:
 ZONE 2: -67.8
 ZONE 3: -102.0
  
 THE ASSEMBLY SELECTED, W-51, HAS A DP LIMITATION OF
 -82.5. THE ASSEMBLY SELECTED DOES NOT MEET THE REQUIRED
 DESIGN PRESSURE FOR ZONE 3, FBC R 301.
  
 2. THE PRODUCT APPROVAL IS INCOMPLETE. THE EVALUATION
 REPORT IS MISSING (PAGES APPLICABLE TO ALL ASSEMBLIES,
 PAGES 1 THROUGH 6); FBC 107, PROVIDE.
  
 3. SEE PAGE 6 (NOT INCLUDED IN SUBMITTAL) OF THE
 PRODUCT APPROVAL, LIMITATION 5.7, A QUALIFIED DESIGN
 PROFESSIONAL IS REQUIRED TO DETERMINE ATTACHMENT
 DENSITY FOR ZONE 3.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-14 Cont ID  
Sent By shill Date 2016-12-14 Time 15:00 Rev Time 0.00
Received By shill Date 2016-12-13 Time 15:36 Sent To  
Notes
2016-12-13 15:36:28RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-08 Cont ID  
Sent By shill Date 2016-12-08 Time 10:18 Rev Time 0.00
Received By shill Date 2016-12-07 Time 09:38 Sent To  
Notes
2016-12-08 09:38:26SHILL