Plan Review Details - Permit 16120196
Plan Review Stops For Permit 16120196
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-01-27 Cont ID  
Sent By jwitmer Date 2017-01-27 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2017-01-27 Time 16:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-09 Cont ID  
Sent By jwitmer Date 2016-12-09 Time 07:43 Rev Time 0.00
Received By jwitmer Date 2016-12-09 Time 07:01 Sent To  
Notes
2016-12-09 07:35:14BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120196
 ADD: 1911 N. FLAGLER DR. SUITE # ??????
 CONT: CHANDLER
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 09/ 2016
 ACTION: DENIED
  
 1) THE LOCATION OF THE JOBSITE IS NOT IDENTIFIED BY
 SUITE NUMBER. 2014 FLORIDA BUILDING CODE W 2014 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK.
  
 2) SHEET A1.1 OFFICES NOT IDENTIFIED. THE OFFICE JUST
 BEHIND THE WATER FOUNTAIN DOES NOT COMPLY WITH 2014
 FBC-ACCESS. CODE, SECTION 404.2.4. MANEUVERING
 CLEARANCES. THE MINIMUM MANEUVERING CLEARANCES REQUIRED
 ON THE LATCH SIDE OF THE DOOR IS 18 INCHES, ALSO SEE
 FIGURE 404.2.4.1(A).
  
 3) NEITHER SHEET A1.1 A2.1 NOR E1.2 SHOWS EXIT LIGHTS,
 OR DECTIONAL SIGNAGE LIGHTING. 2014 FBC-B 1011.1 EXIT
 SIGNS WHERE REQUIRED.
  
 4A) THE PLANS DO NOT INDICATE WHERE COMPLIANCE WITH
 SECTION 1011.4 FBC-B & 703.2 OF THE ACCESSIBILITY CODE
 CAN BE FOUND. 703.2 RAISED CHARACTERS.
 RAISED CHARACTERS SHALL COMPLY WITH 703.2 AND SHALL BE
 DUPLICATED IN BRAILLE COMPLYING WITH 703.3. RAISED
 CHARACTERS SHALL BE INSTALLED IN ACCORDANCE WITH 703.4.
  
 4B) 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND.
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST
 TACTILE CHARACTER AND 60 INCHES (1525 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-01 Cont ID  
Sent By mvaldes Date 2017-02-01 Time 15:53 Rev Time 0.00
Received By mvaldes Date 2017-02-01 Time 15:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-14 Cont ID  
Sent By mvaldes Date 2016-12-14 Time 10:36 Rev Time 0.00
Received By mvaldes Date 2016-12-14 Time 09:28 Sent To  
Notes
2016-12-14 10:46:31JOB PERMIT NUMBER: 16120196
 JOB ADDRESS: 1911 N FLAGLER DRIVE
 WEST PALM BEACH FLORIDA 33407
 DATE: DECEMBER 14, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] SHOW EXITS SIGNS ON THE ELECTRICAL LIGHTING PLAN.
 FBC-1011.
  
 2] PROVIDE AN OCCUPANCY SENSOR IN OFFICE SUITE 102.
 FBC-E SECTION C405.2.2.2.
  
 3] PROVIDE A MOUNTING DETAIL FOR THE CEILING GRID LIGHT
 FIXTURES IN ACCORDANCE WITH NEC 410.36(B). SHOW
 SUPPORTING DETAIL IN COMPLIANCE WITH ACOUSTICAL SYSTEM
 PROVISIONS ASTM 635C & 636C.
  
 4] PROVIDE PULL BOX SIZE TO MEET MINIMUM REQUIREMENTS
 OF NEC 314.28.
  
 5] ADD A NOTE FOR SOURCE OF SUPPLY MARKING ON PANEL "B"
 PER NEC 408.4(B).
  
 6] ADD A NOTE THAT LOW VOLTAGE SHALL BE UNDER A
 SEPARATE PERMIT.
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-01-23 Cont ID  
Sent By pleduc Date 2017-01-23 Time   Rev Time 0.00
Received By pleduc Date 2017-01-23 Time 09:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-12-13 Cont ID  
Sent By pleduc Date 2016-12-13 Time   Rev Time 0.00
Received By pleduc Date 2016-12-13 Time 10:09 Sent To  
Notes
2016-12-13 10:15:22THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET A 1.1 - EXISTING EXIT LIGHTS SHALL BE VERIFIED
 ON FIRE INSPECTION.
  
 PLEASE ENSURE PROPER ILLUMINATION AND FUNCTION.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-01 Cont ID  
Sent By mvaldes Date 2017-02-01 Time 15:54 Rev Time 0.00
Received By mvaldes Date 2017-01-18 Time 14:03 Sent To  
Notes
2017-01-19 14:04:07B12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-30 Cont ID  
Sent By gjohnson Date 2016-12-30 Time 11:24 Rev Time 0.00
Received By gjohnson Date 2016-12-06 Time 08:49 Sent To  
Notes
2016-12-07 08:49:37B04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-12-09 Cont ID  
Sent By jwitmer Date 2016-12-09 Time 07:22 Rev Time 0.00
Received By jwitmer Date 2016-12-09 Time 07:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-01-25 Cont ID  
Sent By ccole Date 2017-01-25 Time 14:46 Rev Time 0.00
Received By ccole Date 2017-01-25 Time 14:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-12-16 Cont ID  
Sent By ccole Date 2016-12-16 Time 10:46 Rev Time 0.00
Received By ccole Date 2016-12-16 Time 10:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-02-01 Cont ID  
Sent By gjohnson Date 2017-02-01 Time 14:54 Rev Time 0.00
Received By gjohnson Date 2017-02-01 Time 13:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-12-30 Cont ID  
Sent By gjohnson Date 2016-12-30 Time 11:24 Rev Time 0.00
Received By gjohnson Date 2016-12-30 Time 11:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-12-15 Cont ID  
Sent By njwira Date 2016-12-15 Time 15:08 Rev Time 0.00
Received By njwira Date 2016-12-15 Time 15:08 Sent To  
Notes
2016-12-15 15:09:2112/15/16- PASSED
  
 ALL MODIFICATIONS ARE INTERIOR
 OFFICE USE PERMITTED IN THIS ZONE
 NO LANDSCAPING PERMIT REQUIRED
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  