Plan Review Details - Permit 16120133
Plan Review Stops For Permit 16120133
Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-03-01 Cont ID  
Sent By pleduc Date 2017-03-01 Time   Rev Time 0.00
Received By pleduc Date 2017-03-01 Time 16:19 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-02-23 Cont ID  
Sent By pleduc Date 2017-02-23 Time   Rev Time 0.00
Received By pleduc Date 2017-02-23 Time 11:51 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-01-03 Cont ID  
Sent By pleduc Date 2017-01-03 Time   Rev Time 0.00
Received By pleduc Date 2016-12-30 Time 16:11 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-12-20 Cont ID  
Sent By J.Walker Date 2016-12-20 Time   Rev Time 0.15
Received By   Date 2016-12-19 Time   Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-03-02 Cont ID  
Sent By ccole Date 2017-03-02 Time 10:05 Rev Time 0.00
Received By ccole Date 2017-02-27 Time 11:35 Sent To  
Notes
2017-02-28 11:36:06RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-24 Cont ID  
Sent By ccole Date 2017-02-24 Time 12:25 Rev Time 0.00
Received By ccole Date 2017-02-09 Time 11:51 Sent To  
Notes
2017-02-10 11:51:48RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-03 Cont ID  
Sent By ccole Date 2017-01-03 Time 09:54 Rev Time 0.00
Received By ccole Date 2016-12-30 Time 10:40 Sent To  
Notes
2016-12-30 10:41:07RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-27 Cont ID  
Sent By ccole Date 2016-12-27 Time 12:08 Rev Time 0.00
Received By ccole Date 2016-12-05 Time 10:32 Sent To  
Notes
2016-12-06 10:33:02ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-03-02 Cont ID  
Sent By ccole Date 2017-03-02 Time 10:05 Rev Time 0.00
Received By ccole Date 2017-03-02 Time 09:36 Sent To  
Notes
2017-03-02 10:32:34MECHANICAL PROVISO:
  
 GUARDS SHALL BE PROVIDED WHERE ANY FANS OR EQUIPMENT
 ARE LOCATED WITHIN 10' OF ROOF EDGES- SECTION 304.11

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-02-24 Cont ID  
Sent By ccole Date 2017-02-24 Time 12:15 Rev Time 0.00
Received By ccole Date 2017-02-24 Time 12:15 Sent To  
Notes
2017-02-24 12:19:083RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16120133
 2/24/17
  
 1) PLEASE REMOVE THE FIRE SUPPRESSION PLANS AND THE M-1
 PLAN FROM THE PLAN SETS. THIS PERMIT APPLICATION IS
 SOLEY FOR THE KITCHEN EXHAUST HOOD. A SEPARATE PERMIT
 IS REQUIRED FOR THE FIRE SUPPRESSION SYSTEM, AND THE
 REVISED M-1 PLAN SHEET MUST BE SUBMITTED AS A REVISION
 OT MASTER PERMIT #16040451.
  
 2) THE SUBMITTED KITCHEN EXHAUST PLANS APPEAR TO COPIES
 FROM AN ORIGINAL SET AND MUCH OF THE PRINT IS
 ILLEGIBLE. I HAVE SPOKEN WITH LORI FROM HOOD DEPOT AND
 THEY ARE READY TO RESUBMIT CLEAR, CORRECTED, SIGNED AND
 SEALED PLANS ADDRESSING THE PREVIOUS REVIEW COMMENT ON
 1/03/2017.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-01-03 Cont ID  
Sent By ccole Date 2017-01-03 Time 09:34 Rev Time 0.00
Received By ccole Date 2017-01-03 Time 09:34 Sent To  
Notes
2017-01-03 09:41:042ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16120133
 1/3/17
  
 1) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS. PLEASE
 PROVIDE AN AC LOAD CALCULATION THAT INCLUDES THE
 ADDITIONAL HEAT GAIN FROM THE MAKEUP AIR, AND THAT
 INDICATES THE ADDITIONAL LOAD DOES NOT EXCEED THE
 CAPACITY OF THE EXISTING OR PROPOSED AC SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-27 Cont ID  
Sent By ccole Date 2016-12-27 Time 12:09 Rev Time 0.00
Received By ccole Date 2016-12-27 Time 12:09 Sent To  
Notes
2016-12-27 12:25:021ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16120133
 12/27/16
  
 1) THE 1" CLEARANCE FOR THE HOOD TO THE COMBUSTIBLE
 CEILING AND WALLS IS NOT PERMITTED PER TABLE 308.6
 FBC-14 MECHANICAL, AND NFPA-96 SECTION 4.2.3.2, TABLE
 A.3.3.37, AND FIGURE A.4.2(H). PLEASE CORRECT THE
 PLANS.
  
 2) INDICATE COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE.
  
 3) IT APPEARS THAT GURADS WILL BE REQUIRED AT THE ROOF
 EDGE THAT IS SHOWN IN CLOSE PROXIMITY TO THE EXHAUST
 FAN ON SHEET 4- SEE SECTION 304.11.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  