Plan Review Details - Permit 16120124
Plan Review Stops For Permit 16120124
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-06-22 Cont ID  
Sent By jwitmer Date 2017-06-22 Time 15:27 Rev Time 0.00
Received By jwitmer Date 2017-06-22 Time 15:27 Sent To  
Notes
2017-06-22 15:27:36EXPLORITORY OPENING UP IN PREPARATION FOR REPAIRS FOR
 NON-FUNCTIONING SPLASH PAD.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-21 Cont ID  
Sent By jwitmer Date 2017-06-21 Time 10:33 Rev Time 0.00
Received By jwitmer Date 2017-06-21 Time 09:12 Sent To  
Notes
2017-06-21 10:33:40BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120124
 ADD: 723 39TH ST.
 CONT: WEST CONSTRUCTION INC./ MARTHA A. MORGAN
 TEL: 561-248-3868
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JUNE 21, 2017
 ACTION: DENIED
  
 1) SEMI-COMPLIED, OWNER OR OWNERS AGENT WILL ALSO NEEDS
 TO SIGN THE PERMIT APPLICATION UNDER THE HEADING
 SIGNATURE OWNER.
  
 2) COMPLIED.
  
 3) 2ND REQUEST. THE ENGINEERS SIGNATURE OF BRADLEY J.
 CASH P. E. IS A STAMP OF A SIGNATURE NOT A TRUE INK
 SIGNATURE OF THE P. E.
 FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE
 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 4) COMPLIED. FULL SIZE SHEETS.
  
 5-6) COMPLIED.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-24 Cont ID  
Sent By jwitmer Date 2017-01-24 Time 13:26 Rev Time 0.00
Received By jwitmer Date 2017-01-24 Time 12:02 Sent To  
Notes
2017-01-24 13:26:15BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120124
 ADD: 723 39TH ST.
 CONT: WEST CONSTRUCTION INC./ MARTHA A. MORGAN
 TEL: 561-248-3868
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 24, 2017
 ACTION: DENIED
  
 1) CONTRACTOR (QUALIFIER) NEEDS TO SIGN THE PERMIT
 APPLICATION UNDER THE HEADING SIGNATURE OF CONTRACTOR
  
 2) THE ADDRESS PROVIDED ON THE APPLICATION 723 39TH ST.
 APPEARS TO BE AN OFFICE BUILDING, PERHAPS THE
 ADMINISTRATIVE OFFICES FOR THE BOYS & GIRLS CLUB
 ATHLETIC CENTER ADDRESSED AS 4017 PINEWOOD AVE. THE
 ORIGINAL BOYS & GIRLS CLUB ATHLETIC CENTER PERMIT
 03060499 HAD A FEW PLANS INDICATING THE LOCATION OF THE
 NORTHWOOD CENTER SPLASH PAD, SHEET C-3. THE ACTUAL
 PERMIT FOR THE NORTHWOOD CENTER SPLASH PAD PERMIT
 03060502 WAS NEVER ISSUED AND VOIDED. THE PLAN
 DOCUMENTS WERE ADDRESSED UNDER 4105 PINEWOOD AVE. THE
 FOUNTAIN PLAZA IS NOT ON ANY PRIVATE PROPERTY BUT IN
 THE RIGHT OF WAY. PLEASE UPDATE THE ADDRESS TO ONE THAT
 IS ADJACENT TO THE RIGHT OF WAY WHERE THE PROJECT IS
 LOCATED.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED UNDER THIS PERMIT.
  
 3) THE DOCUMENTS SUBMITTED F1OF 4 WERE CREATED
 ORIGINALLY BY JOHN BROWN P. E. 30698 DATED 09/06/05.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE
 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 4) THE SUBMITTED PLANS F1 OF 4 HAVE BEEN REDUCED IN
 SIZE AND NOT TO THE MINIMUM 1/8 INCH SCALE. PLANS ARE
 SO SMALL THEY ARE ILLEGIBLE. 107.2.1.4 QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR
 OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT.
  
 5) THE PERMIT APPLICATION INDICATES THE SCOPE OF WORK
 TO BE MAINTENANCE AND REHABILITATION. PLEASE DOCUMENT
 WHAT WORK IS GOING TO OCCUR UNDER THIS PERMIT. SHEET F2
 OF 4 HAS A LEGEND FOR RETURN PIPES AND SUPPLY PIPES.
 ARE PIPES TO BE REPLACED, IS CONCRETE DECK TO BE
 REMOVED AND OR PAVERS? THERE ARE NO SHEETS INDICATING
 THERE IS TO BE ANY STRUCTURAL WORK OCCURRING UNDER THIS
 PERMIT? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) ONE SINGLE SHEET WITH GENERAL NOTES. THERE IS NO
 TITLE BLOCK ON THIS SHEET, NO ONE HAS TAKEN
 RESPONSIBILITY OF OWNERSHIP FOR THIS DOCUMENT. 107.3.4
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2017-06-22 Cont ID  
Sent By jwitmer Date 2017-06-22 Time 15:27 Rev Time 0.00
Received By jwitmer Date 2017-06-22 Time 15:27 Sent To  
Notes
2017-06-22 15:28:23EXPLORITORY OPENING UP IN PREPARATION FOR REPAIRS FOR
 NON-FUNCTIONING SPLASH PAD.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-06-16 Cont ID  
Sent By jleahy Date 2017-06-16 Time 07:13 Rev Time 0.00
Received By jleahy Date 2017-06-16 Time 07:13 Sent To  
Notes
2017-06-16 07:23:09CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 NEED CUT SHEETS FOR THE PUMPS, LIGHT FIXTURES,
 CONTROLERS AND ENCLOSURE SHOWING A LISTINGS FOR ALL.
  
 WHERE DOES THE POWER COME FROM? PLEASE SHOW WHERE POWER
 WILL BE OBTAINED FROM.
  
 PANEL SCHEDULE. SHOWING ALL EQUIPMENTS AND BRANCH
 CIRCUIT AND BREAKER SIZES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-30 Cont ID  
Sent By mvaldes Date 2017-01-30 Time 10:42 Rev Time 0.00
Received By mvaldes Date 2017-01-30 Time 10:38 Sent To  
Notes
2017-01-30 11:04:381ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] WPB AMENDMENTS TO 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 2] WPB AMENDMENTS TO FBC 107.2.1.4 QUALITY OF BUILDING
 PLANS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THIS POLICY MAY INCLUDE SUCH THINGS
 AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER
 ITEMS RELATED TO RECORDS MANAGEMENT.
  
 3] PLANS REQUIRE SIGN & SEAL FORM ENGINEER PER FS 471.
  
 4] GENERAL NOTES SHALL BE SUBMITTED IN 2 COPIES. FBC
 107
  
 5] EQUIPOTENTIAL BONDING SHALL BE IN ACCORDANCE WITH
 NEC 680.26(B)(1)-(7).
  
 6] CLEARLY DESCRIBE IN DETAIL THE SCOPE OF THE WORK.
 FBC 107
  
 7] PROVIDE MANUFACTURE SPECS OF POOL ELECTRICAL
 EQUIPMENT. FBC 107

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-13 Cont ID  
Sent By J.Walker Date 2017-06-13 Time   Rev Time 0.00
Received By   Date 2017-06-12 Time   Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-23 Cont ID  
Sent By J.Walker Date 2017-01-23 Time   Rev Time 0.15
Received By   Date 2017-01-20 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-06-21 Cont ID  
Sent By jwitmer Date 2017-06-21 Time 10:33 Rev Time 0.00
Received By jwitmer Date 2017-06-08 Time 09:45 Sent To  
Notes
2017-06-09 09:45:11B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-30 Cont ID  
Sent By mvaldes Date 2017-01-30 Time 11:05 Rev Time 0.00
Received By mvaldes Date 2017-01-13 Time 13:39 Sent To  
Notes
2017-01-17 13:39:44B02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-01-25 Cont ID  
Sent By ccole Date 2017-01-25 Time 11:31 Rev Time 0.00
Received By ccole Date 2017-01-25 Time 11:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2017-06-22 Cont ID  
Sent By jwitmer Date 2017-06-22 Time 15:27 Rev Time 0.00
Received By jwitmer Date 2017-06-22 Time 15:27 Sent To  
Notes
2017-06-22 15:28:47EXPLORITORY OPENING UP IN PREPARATION FOR REPAIRS FOR
 NON-FUNCTIONING SPLASH PAD.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-16 Cont ID  
Sent By gjohnson Date 2017-06-16 Time 14:27 Rev Time 0.00
Received By gjohnson Date 2017-06-16 Time 14:27 Sent To  
Notes
2017-06-16 14:39:571ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1.THE SCOPE OF WORK IS UNCLEAR PLEASE CONTACT ME TO
 CLARIFY SCOPE OF WORK.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-27 Cont ID  
Sent By gjohnson Date 2017-01-27 Time 10:53 Rev Time 0.00
Received By gjohnson Date 2017-01-26 Time 09:01 Sent To  
Notes
2017-01-27 12:23:061ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEAS PROVIDE A COPY OF THE APPLICATION FOR
 OPERATION PERMIT FROM DEPT OF HEALTH . PER FLORIDA
 ADMINISTRATIVE RULE 64E-9
  
 2. SHT. F2 SHOWS 2" SUMP PUMP DRAIN, 2"BACKWASH AND 3"
 OVERFLOW DRAIN DRAINING TO THE STORM DRAIN SHT FF3 P4
 PUMP SHOWS WASTE TO STORMSEWER THIS IS PROHIBITED. PER
 WPB ORD, SEC. 90-203.(A)
 SHALL GET APPROVAL FROM ENGINEERING DEPT. CONTACT MANNY
 GONZALEZ 494- 1085
  
 3. PROVIDE RATE OF FILTRATION FOR THE SAND FILTER TO
 COMPLY WITH FBC 4541.6.5.5.1
  
 4. THE LAST TO SHEETS SPLASH PAD PIPING AND WET DECK
 ARE MISSING TEXT PART OF IT IS CUT OFF PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 5. PROVIDE DETAIL OF AUTOMATIC FILL VALVE MUST SHOW AIR
 GAP OR HAVE A BACK FLOW. PER WPB AMEND TO FBC 107.2.1
  
 6. PLEASE INDICATE WHICH FILTRATION SYSTEM YOU ARE
 COMPILING WITH THE PLAN IS UNCLEAR AND TO SMALL TO READ
 SHALL COMPLY WITH FBC 454.1.9.8.6.1 OR 454.1.9.8.6.3
 IF YOUR USING 454.1.9.8.6.1 YOU ALSO SHALL COMPLY WITH
 454.1.9.8.6.8
  
 7. PLEASE INDICATE ON PLAN IF THE PAD WILL BE USED AT
 NIGHT IF SO IT SHALL COMPLY WITH FBC 454.1.9.8.4
  
 8. PLEASE PROVIDE THE TURN OVER RATE POF THE SYSTEM.
 PER WPB AMEND TO FBC 107.2.1
  
 9. SHT F2 ITEM 19 IS MISSING ON EQUIPMENT SCHEDULE
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 10. SHOW COMPLIANCE WITH FBC 4554.1.9.8.6.8 TO
 COMPLETELY DRAIN THE TANK WILL THE PAC FAB VACUUM
 FITTING BE USED FOR THIS CLARIFY . PER WPB AMEND TO FBC
 107.2.1
  
 11. PLEASE PROVIDE A SITE PLAN SHOWING THE RESTROOM AND
 DISTANCE THAT WILL SERVE SPLASH PAD SHOW FENCING AND
 THE SHOWER. PER WPB AMEND TO FBC 107.2.1
  
 12. THE DESCRIPTION OF WORK ON THE APPLICATION STATES
 MAINTENANCE AND REHABILITATION NORTHWOOD REC CENTER
 SPLASH PAD ON THE SATELLITE VIEW IT DOES NOT APPEAR TO
 HAVE AN EXISTING SPLASH PAD PLEASE CLARIFY IS THIS NEW
 OR EXISTING IF NEW THE APPLICATION WILL NEED TO BE
 CHANGED. PER WPB AMEND TO FBC 107.2.1
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-06-14 Cont ID  
Sent By llouie Date 2017-06-14 Time   Rev Time 0.00
Received By llouie Date 2017-06-14 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-01-23 Cont ID  
Sent By llouie Date 2017-01-23 Time   Rev Time  
Received By llouie Date 2017-01-23 Time   Sent To  
Notes
2017-01-23 15:56:55** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE AN UPDATED SURVEY OF THE PROPERTY.
  
 2.) THE PARTIAL SITE PLAN SHOW A 4 FT. HIGH FENCE AT
 THE FRONT OF THE PROPOSED WATER FEATURE. IS THIS FENCE
 EXISTING OR PROPOSED? PROVIDE A DETAIL IF THE FENCE IS
 PROPOSED.
  
 * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.
  