Plan Review Details - Permit 16120061
Plan Review Stops For Permit 16120061
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-02-10 Cont ID  
Sent By rmcdouga Date 2017-02-10 Time 07:56 Rev Time 0.00
Received By rmcdouga Date 2017-02-10 Time 07:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-02-06 Cont ID  
Sent By rmcdouga Date 2017-02-06 Time 17:30 Rev Time 0.00
Received By rmcdouga Date 2017-02-06 Time 17:27 Sent To  
Notes
2017-02-06 17:30:35PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE ARE SOME ISSUES WITH THE ENERGY FORMS R405 -
 2014 THAT WERE SUBMITTED. PLEASE CORRECT. FBC ENERGY
 CONSERVATION RESIDENTIAL PROVISIONS
 B) THE OWNER/AGENT'S SIGNATURE IS REQUIRED ON THE FORM
 PER FBC ENERGY CONSERVATION SECTION R103.1.1.2.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-20 Cont ID  
Sent By rmcdouga Date 2017-01-20 Time 17:03 Rev Time 0.00
Received By rmcdouga Date 2017-01-19 Time 14:27 Sent To  
Notes
2017-01-20 14:35:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE 6 FT HIGH FENCE SHOWN IN DETAIL 4 ON AS-1,
 SPECIFIES A 4 X 4 X 6' PT. POST. THE POSTS FOR THE 6 FT
 FENCE WILL HAVE TO BE 8 FT IN ORDER TO HAVE 2 FT IN THE
 GROUND. PLEASE CORRECT. FBC 107.2.1
  
 2) THERE IS A NOTE THAT SPECIFIES HARDIPLANK SIDING ON
 THE GABLE END ON WALL SECTION 2 ON S1.1. THE REST OF
 THE PLANS INDICATE THAT THE GABLE WILL BE STUCCO WITH
 SIMULATED 6" HORIZONTAL LAPS. PLEASE CLARIFY. FBC
 107.2.1 NOTE: IF HARDI PLANK IS USED, SUBMIT TWO SETS
 OF PRODUCT APPROVALS FOR IT PER FBC 107.3.4.1.
  
 3) THERE ARE SOME ISSUES WITH THE ENERGY FORMS R405 -
 2014 THAT WERE SUBMITTED. PLEASE CORRECT. FBC ENERGY
 CONSERVATION RESIDENTIAL PROVISIONS
 A) THERE WERE TWO ENERGY FORMS SUBMITTED WITH DIFFERNT
 INFORMATION. THE NUMBER OF OCCUPANTS AND THE ATTIC VENT
 RATIO ARE DIFFERENT. PLEASE CLARIFY AND REMOVE THE ONE
 THAT IS NOT SPECIFIC TO THIS PROJECT. FBC 107.2.1
 B) THE OWNER/AGENT'S SIGNATURE IS REQUIRED ON THE FORM
 PER FBC ENERGY CONSERVATION SECTION R103.1.1.2.
 C) THE FORM LISTS A 50 GAL. WATER HEATER AND A 40 GAL.
 WATER HEATER IS SPECIFIED ON PLAN SHEET P-1.0.
 D) THE FORM SPECIFIES A HIP ROOF AND THE PLANS SHOW A
 GABLE ROOF.
 E) THE PERMIT OFFICE IS WEST PALM BEACH AND THE
 JURISDICTION IS 604700. THESE WERE LEFT BLANK ON THE
 FORM.
  
 4) THE PLANS SPECIFY LOMANCO 700 SERIES LOUVERED STATIC
 ROOF VENTS. THE PRODUCT APPROVAL NUMBER ON THE PLANS
 AND THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR
 LOMANCO WHIRLYBIRD WIND TURBINES (NOA NO. 15-0831.08).
 THE PRODUCT APPROVAL FOR THE LOMANCO 700 SERIES VENTS
 IS NOA NO. 16-0510.28. NOTE: IF YOU USE THE WIND
 TURBINES PLEASE BE ADVISED THAT THE TAS 110 (A)
 STANDARD TO WHICH THEY WERE TESTED REQUIRES THAT THE
 TURBINE UNIT BE REMOVED AND REPLACED WITH A STORM CAP
 WHEN TESTING FOR WINDSPEED AND WATER SPRAY ABOVE A 70
 MPH WINDSPEED. FBC TEST PROTOCALS FOR HIGH VELOCITY
 HURRICANE ZONES (TAS) NO. 100(A)-95
  
 5) THE VALUATION HAS BEEN ADJUSTED FROM $130,000.00 TO
 $146,586.71 BASED ON CURRENT ICC VALUATION DATA. FBC
 109.3.
  
 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-30 Cont ID  
Sent By mvaldes Date 2017-01-30 Time 13:38 Rev Time 0.00
Received By mvaldes Date 2017-01-30 Time 11:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-12 Cont ID  
Sent By mvaldes Date 2017-01-12 Time 15:13 Rev Time 0.00
Received By mvaldes Date 2017-01-12 Time 14:30 Sent To  
Notes
2017-01-12 15:15:53JOB PERMIT NUMBER: 16120061
 JOB ADDRESS: 1110 18TH STREET
 WEST PALM BEACH FLORIDA
 DATE: JANUARY 12, 2017
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014,
 (RESIDENTIAL FLORIDA BUILDING CODE) AS WELL AS THE CITY
 OF WEST PALM BEACH AMENDMENTS. SEE BELOW A LIST OF
 ITEMS NOTED.
  
 1] PROVIDE A MAIN DISCONNECT OUTSIDE NEAREST THE POINT
 OF ENTRANCE OF THE SERVICE CONDUCTORS IN ACCORDANCE
 WITH FBC-R SECTION E3601.6.2.
  
 2] PROVIDE A SWITCHED LIGHTING OUTLET FOR EXTERIOR
 EGRESS ILLUMINATION ON THE STORAGE SHED PER FBC-R
 SECTION E3903.3.
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. IF YOU HAVE FURTHER QUESTIONS, PLEASE
 DON'T HESITATE TO CONTACT ME DIRECTLY.
  
 1ST REVIEW
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-10 Cont ID  
Sent By rmcdouga Date 2017-02-10 Time 07:57 Rev Time 0.00
Received By rmcdouga Date 2017-02-09 Time 13:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-06 Cont ID  
Sent By rmcdouga Date 2017-02-06 Time 17:37 Rev Time 0.00
Received By rmcdouga Date 2017-01-26 Time 12:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-25 Cont ID  
Sent By lmarchan Date 2017-01-25 Time 14:47 Rev Time 0.00
Received By lmarchan Date 2016-12-14 Time 10:12 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2017-01-19 Cont ID  
Sent By rmcdouga Date 2017-01-19 Time 18:39 Rev Time 0.00
Received By rmcdouga Date 2017-01-19 Time 18:39 Sent To  
Notes
2017-01-19 18:39:53MU-2016-29588, PAID $9,585.84

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-02-10 Cont ID  
Sent By rmcdouga Date 2017-02-10 Time 07:56 Rev Time 0.00
Received By rmcdouga Date 2017-02-10 Time 07:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-02-06 Cont ID  
Sent By rmcdouga Date 2017-02-06 Time 17:31 Rev Time 0.00
Received By rmcdouga Date 2017-02-06 Time 17:31 Sent To  
Notes
2017-02-06 17:31:56PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS. M1401.3 SIZING. HEATING AND
 COOLING EQUIPMENT AND APPLIANCES SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-20 Cont ID  
Sent By rmcdouga Date 2017-01-20 Time 13:38 Rev Time 0.00
Received By rmcdouga Date 2017-01-20 Time 13:38 Sent To  
Notes
2017-01-20 13:37:56PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS. M1401.3 SIZING. HEATING AND
 COOLING EQUIPMENT AND APPLIANCES SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-01-19 Cont ID  
Sent By rmcdouga Date 2017-01-19 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2017-01-19 Time 17:52 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-01-20 Cont ID  
Sent By rmcdouga Date 2017-01-20 Time 08:25 Rev Time 0.00
Received By rmcdouga Date 2017-01-20 Time 08:25 Sent To  
Notes
2017-01-20 09:10:29OWENS CORNING ASPHALT ROOF SHINGLES FL10674-R12

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2017-02-10 Cont ID  
Sent By rmcdouga Date 2017-02-10 Time 07:56 Rev Time 0.00
Received By rmcdouga Date 2017-02-10 Time 07:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2017-02-06 Cont ID  
Sent By rmcdouga Date 2017-02-06 Time 17:37 Rev Time 0.00
Received By rmcdouga Date 2017-02-06 Time 17:37 Sent To  
Notes
2017-02-06 17:37:24THE FOLLOWING CONSTRUCTION DOCUMENTS ARE REQUIRED TO
 HAVE THE SEAL AND ORIGINAL SIGNATURE OF THE FLORIDA
 LICENSED ENGINEER OR SURVEYOR ON THEM. THE SOIL REPORT,
 THE SURVEY THE TRUSS DRAWINGS AND TRUSS LAYOUT.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE, CHAPTER 472, FLORIDA
 STATUTES OR CHAPTER 481, FLORIDA STATUTES & 61G1
 FLORIDA ADMINISTRATIVE CODE. WHERE SPECIAL CONDITIONS
 EXIST, THE BUILDING OFFICIAL IS AUTHORIZED TO REQUIRE
 ADDITIONAL CONSTRUCTION DOCUMENTS TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-01-20 Cont ID  
Sent By rmcdouga Date 2017-01-20 Time 13:38 Rev Time 0.00
Received By rmcdouga Date 2017-01-20 Time 13:38 Sent To  
Notes
2017-01-20 13:58:25THE FOLLOWING CONSTRUCTION DOCUMENTS ARE REQUIRED TO
 HAVE THE SEAL AND ORIGINAL SIGNATURE OF THE FLORIDA
 LICENSED ENGINEER OR SURVEYOR ON THEM. THE SOIL REPORT,
 THE SURVEY THE TRUSS DRAWINGS AND TRUSS LAYOUT.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE, CHAPTER 472, FLORIDA
 STATUTES OR CHAPTER 481, FLORIDA STATUTES & 61G1
 FLORIDA ADMINISTRATIVE CODE. WHERE SPECIAL CONDITIONS
 EXIST, THE BUILDING OFFICIAL IS AUTHORIZED TO REQUIRE
 ADDITIONAL CONSTRUCTION DOCUMENTS TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-01-05 Cont ID  
Sent By njwira Date 2017-01-05 Time 14:53 Rev Time 0.00
Received By njwira Date 2017-01-05 Time 14:53 Sent To  
Notes
2017-01-05 14:55:331/5/17- PASSED
  
 FRONT SETBACK MEETS CONTEXTUAL SETBACK OF THE
 NEIGHBORHOOD
 REAR SETBACK IS 22.6FT. MEETING THE 10FT. REQUIREMENT
 SIDE SETBACK IS 5FT. MINIMUM 14FT. TOTAL MEETING THE
 5FT. MINIMUM 10FT. TOTAL REQUIREMENT
 ONE PARKING SPACE
 MEETS 40FT. HEIGHT LIMIT
 MEETS ARCHITECTURAL STANDARDS
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-12-30 Cont ID  
Sent By njwira Date 2016-12-30 Time 12:11 Rev Time 0.00
Received By njwira Date 2016-12-30 Time 12:11 Sent To  
Notes
2016-12-30 12:14:2812/30/16- FAILED
  
 SF-11 SINGLE FAMILY LOW DENSITY RESIDENTIAL
 APPROVED LANDSCAPE PLANS REQUIRED
  
 FAILED
 1. CORNER SETBACK IS 9.17FT. WHICH DOESN'T MEET THE
 12FT. REQUIREMENT
 2. FRONT SETBACK IS 6.23FT. WHICH DOESN'T MEET THE
 25FT. REQUIREMENT
 3. SIDE SETBACK DOESN'T MEET THE 5FT. MINIMUM 15FT.
 TOTAL
  
 PASSED
 1. ONE KITCHEN MAKES THIS ONE(1)UNIT
 2. BUILDING HEIGHT IS 14FT. 4 AND 1/2IN.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  