Plan Review Details - Permit 16120004
Plan Review Stops For Permit 16120004
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date   Cont ID  
Sent By jwitmer Date 2016-12-13 Time 07:32 Rev Time 0.00
Received By jwitmer Date 2016-12-08 Time 15:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-12-19 Cont ID  
Sent By vperez Date 2016-12-19 Time 07:19 Rev Time 0.00
Received By vperez Date 2016-12-15 Time 15:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-14 Cont ID  
Sent By lmarchan Date 2017-02-14 Time 09:09 Rev Time 0.00
Received By lmarchan Date 2017-01-27 Time 08:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-19 Cont ID  
Sent By vperez Date 2016-12-19 Time 07:19 Rev Time 0.00
Received By vperez Date 2016-12-19 Time 07:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-07 Cont ID  
Sent By lmarchan Date 2016-12-07 Time 10:02 Rev Time 0.00
Received By lmarchan Date 2016-12-02 Time 11:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-12-13 Cont ID  
Sent By ccole Date 2016-12-13 Time 14:43 Rev Time 0.00
Received By ccole Date 2016-12-13 Time 14:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-02-06 Cont ID  
Sent By gjohnson Date 2017-02-06 Time 17:22 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-12-14 Cont ID  
Sent By gjohnson Date 2016-12-14 Time 17:38 Rev Time 0.00
Received By gjohnson Date 2016-12-14 Time 17:38 Sent To  
Notes
2016-12-14 17:50:281ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. P 2.6 AND P2.6 YOUR NOTE FOR THE ROOF RAIN
 WATER CALCULATIONS DOES NOT MATCH THE TABLE IN THE FBC
 PL TABLE 1106.3 SIZE OF HORIZONTAL STORM DRAINGE PIPING
 A) THE RAIN FALL RATE IS 5" NOT 4.5".
 B) THE PIPE SIZE 4.5" DOES-NOT EXIST.
 C) THE SQ FT ON EACH PIPE DOES NOT MATCH THE TABLE.
 PLEASE CLARIFY WPB AMEND TO FBC 107.2.1
  
 2. PLEASE PROVIDE THE SLOPE OF THE PIPE ON THE RISER
 DIAGRAM. PER WPB AMEND TO FBC 107.2.1
 IF THE HORIZONTAL 12" PIPE IS RUN AT 1/8 PER FT IT IS
 UNDER SIZED. PER FBC PL TABLE 1106.3
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-02-14 Cont ID  
Sent By lmarchan Date 2017-02-14 Time 09:09 Rev Time 0.00
Received By lmarchan Date 2017-02-14 Time 09:09 Sent To  
Notes
2017-02-06 17:33:57PLUMBING MECHANICAL AND ELECTRICAL SHEETS OK/GPJ 2/6/17
2016-12-13 07:17:09STRUCTURAL SHEET 152_S1.3B DIGITAL SIGNATURE.
 61G15-23.005 OK 02/09/2017 JW