Plan Review Details - Permit 16111165
Plan Review Stops For Permit 16111165
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-20 Cont ID  
Sent By rmcdouga Date 2016-12-20 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2016-12-19 Time 14:32 Sent To  
Notes
2016-12-19 14:32:49RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-01 Cont ID  
Sent By rmcdouga Date 2016-12-01 Time 08:26 Rev Time 0.00
Received By rmcdouga Date 2016-11-29 Time 10:21 Sent To  
Notes
2016-11-30 10:22:14REVISION ROUTED TO RMCDOUGAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-20 Cont ID  
Sent By rmcdouga Date 2016-12-20 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2016-12-20 Time 07:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-01 Cont ID  
Sent By rmcdouga Date 2016-12-01 Time 08:26 Rev Time 0.00
Received By rmcdouga Date 2016-12-01 Time 08:26 Sent To  
Notes
2016-12-01 09:30:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE REVISION IS TO CHANGE THE HEATING AND COOLING
 EQUIPMENT FROM TRANE TO RHEEM. THE EQUIPMENT SCHEDULE
 CHANGED THE CONDENSER TO A RHEEM 13PJL60A01, HOWEVER
 THE COIL WAS NOT CHANGED FROM THE TRANE
 GAM2A0C60S51++TDR. THE AHRI REFERENCE NUMBER 5720554 IS
 NOT CORRECT. PER FBC ENERGY CONSERVATION R101.4.7 AND
 R403.6 MATCHED SYSTEMS ARE REQUIRED.
  
  