Plan Review Details - Permit 16111164
Plan Review Stops For Permit 16111164
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-01-04 Cont ID  
Sent By jgomez Date 2017-01-04 Time 14:20 Rev Time 0.00
Received By jgomez Date 2017-01-04 Time 13:51 Sent To  
Notes
2017-01-04 13:51:39RECEIVED E-MAIL WITH AHRI CERTIFICATES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-03 Cont ID  
Sent By jgomez Date 2017-01-03 Time 19:25 Rev Time 0.00
Received By jgomez Date 2016-12-29 Time 10:08 Sent To  
Notes
2016-12-30 10:08:18RESUB OF REVISION ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-21 Cont ID  
Sent By jgomez Date 2016-12-21 Time 10:57 Rev Time 0.00
Received By jgomez Date 2016-12-19 Time 14:31 Sent To  
Notes
2016-12-19 14:31:16RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-05 Cont ID  
Sent By jgomez Date 2016-12-05 Time 18:43 Rev Time 0.00
Received By jgomez Date 2016-11-29 Time 10:17 Sent To  
Notes
2016-12-05 18:04:42RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS.
 CODE: FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 1- TRANSFER GRILL SIZE SHOWN ON PLAN FOR ALL THE SECOND
 FLOOR BEDROOMS DOESN'T T COMPLY WITH EXCEPTION #2 OF
 SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 (NOTE: ORIGINAL APPROVED PLAN SPECIFIED 10" X 14"
 R.T.G. OVER DOOR WHICH WAS COMPLIANT).
  
 2- ORIGINAL PLAN M1.00 WAS SIGNED AND SEALED BY THE
 ENGINEER OF RECORD. RE-SUBMIT PLAN WITH ENGINEER OF
 RECORD TITLE BLOCK AND SIGNED AND SEALED BY THE
 ENGINEER OR RECORD (WILLIAM F. STUHRKE, PHD, PE).
 CHAPTER 471 FLORIDA STATUTE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
2016-11-30 10:17:16REVISION ROUTED TO JGOMEZ

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-01-04 Cont ID  
Sent By jgomez Date 2017-01-04 Time 14:18 Rev Time 0.00
Received By jgomez Date 2017-01-04 Time 13:51 Sent To  
Notes
2017-01-04 14:20:27MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE COPY OF AHRI CERTIFICATE SPECIFIED ON A/C
 PLAN ON THE EQUIPMENT SCHEDULE AND LEGEND.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-01-04 Cont ID  
Sent By jgomez Date 2017-01-03 Time 19:09 Rev Time 0.00
Received By jgomez Date 2017-01-03 Time 18:48 Sent To  
Notes
2017-01-03 19:06:05RESIDENTIAL (R3) THIRD MECHANICAL REVISION CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE. FLORIDA STATUTE 553.80(2)(B).
  
 ORIGINAL COMMENT:
 1- INFORMATION SHOWN ON SHEET M1.00 DOESN'T MATCH
 INFORMATION SHOWN ON THE AHRI CERTIFICATE # 9962635 AND
 #8205993 SPECIFIED ON THE EQUIPMENT SCHEDULE & LEGEND
 SUBMITTED. REVISE OUTDOOR UNIT MODEL NUMBER, SEER,
 COOLING CAPACITY, ETC. AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 THE AHRI CERTIFICATE NUMBER WAS CHANGED TO 7556872 AND
 7552655 RESPECTIVELY. UNABLE TO FIND THESE NUMBERS ON
 THE AHRI DIRECTORY. PLEASE PROVIDE COPIES OF THE
 REVISED AHRI CERTIFICATES.
 SEC. M1302.1 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-21 Cont ID  
Sent By jgomez Date 2016-12-21 Time 11:04 Rev Time 0.00
Received By jgomez Date 2016-12-21 Time 07:49 Sent To  
Notes
2016-12-21 11:10:53RESIDENTIAL (R3) SECOND MECHANICAL REVISION CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE IF THE PLANS ARE REJECTED 3 OR MORE TIMES AS
 REQUIRED BY F.S. 553.80(2)(B).
  
 1- INFORMATION SHOWN ON SHEET M1.00 DOESN'T MATCH
 INFORMATION SHOWN ON THE AHRI CERTIFICATE # 9962635 AND
 #8205993 SPECIFIED ON THE EQUIPMENT SCHEDULE & LEGEND
 SUBMITTED. REVISE OUTDOOR UNIT MODEL NUMBER, SEER,
 COOLING CAPACITY, ETC. AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-05 Cont ID  
Sent By jgomez Date 2016-12-05 Time 18:21 Rev Time 0.00
Received By jgomez Date 2016-12-05 Time 17:10 Sent To  
Notes
2016-12-05 18:43:04RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- CONDENSER UNIT MANUFACTURER WAS CHANGED FOR A
 COMFORTMAKER UNIT. THE AIR HANDLER UNIT SHOWN ON THE
 EQUIPMENT SCHEDULE IS A GOODMAN UNIT. CLARIFY WHY
 SPECIFYING TWO DIFFERENT MANUFACTURER'S. PROVIDE THE
 AHRI CERTIFICATE FOR THE EQUIPMENT LISTED IN THE
 REVISED EQUIPMENT SCHEDULE. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]