Plan Review Details - Permit 16111129
Plan Review Stops For Permit 16111129
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-12-30 Cont ID  
Sent By shill Date 2016-12-30 Time 15:56 Rev Time 0.00
Received By shill Date 2016-12-30 Time 13:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2017-01-03 Cont ID  
Sent By rlecky Date 2017-01-03 Time 13:52 Rev Time 0.00
Received By rlecky Date 2017-01-03 Time 13:52 Sent To  
Notes
2017-01-03 13:54:07SCOPE OF WORK WITHIN DOCUMENTS DOES NOT INCLUDE
 ELECTRIC. RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-05 Cont ID  
Sent By pleduc Date 2017-01-05 Time   Rev Time 0.00
Received By pleduc Date 2017-01-05 Time 11:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-24 Cont ID  
Sent By ccole Date 2017-01-24 Time 09:02 Rev Time 0.00
Received By ccole Date 2017-01-18 Time 09:14 Sent To  
Notes
2017-01-19 09:14:29RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-19 Cont ID  
Sent By lmarchan Date 2017-01-19 Time 09:12 Rev Time 0.00
Received By lmarchan Date 2016-11-28 Time 17:11 Sent To  
Notes
2016-12-29 09:06:3512/29 - B11
2016-11-28 17:11:30GENERATOR BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-01-24 Cont ID  
Sent By ccole Date 2017-01-24 Time 09:02 Rev Time 0.00
Received By ccole Date 2017-01-24 Time 09:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-29 Cont ID  
Sent By ccole Date 2016-12-29 Time 06:53 Rev Time 0.00
Received By ccole Date 2016-12-29 Time 06:53 Sent To  
Notes
2016-12-29 07:02:301ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16111129
 12/28/16
  
 1) THE 3.5.02 PLAN SHEET HAS DETAILS AND PRINT THAT IS
 ILLEGFIBLE. PLEASE PROVIDE AN ENLARGED SHEET.
  
 2) REFER TO TABLE 1509.6.5 FBC-14 BUILDING AND PROVIDE
 A DRAWING THAT INDICATES THE CLEARANCE DISTANCE
 MEASUREMENTS FROM THE ROOF SURFACE TO THE UNDERSIDE OF
 THE DOC UNITS.
  
 3) SHOW THE PIPING LAYOUT AND INDICATE HOW THE PIPING
 WILL MBE SUPPORTED ON THE ROOF.
  
 4) INDICATE COMPLIANCE WITH SECTION 501.3.1 (2) FOR
 EXHAUST OUTLET CLEARSANCES TO AIR INTAKES
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2017-01-23 Cont ID  
Sent By tklarge Date 2017-01-23 Time 07:39 Rev Time 0.00
Received By tklarge Date 2017-01-23 Time 06:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-30 Cont ID  
Sent By tklarge Date 2016-11-30 Time 05:35 Rev Time 0.00
Received By tklarge Date 2016-11-30 Time 05:33 Sent To  
Notes
2016-11-30 05:34:551) SUBMIT MANUFACTURER'S SPECIFICATIONS / INSTALL
 DOCUMENTS FOR THE EQUIPMENT TO BE INSTALLED. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) INDICATE IF THE LOCATION OF THE EXHAUST PIPES FROM
 THE GENERATORS WILL BE RELOCATED. IF SO, THE LOCATION
 SHALL COMPLY WITH THE FMC SEC. 501.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2017-01-10 Cont ID  
Sent By aaponte Date 2017-01-10 Time 15:53 Rev Time 0.00
Received By aaponte Date 2017-01-10 Time 15:53 Sent To  
Notes
***NONE***