Plan Review Details - Permit 16111107
Plan Review Stops For Permit 16111107
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-27 Cont ID  
Sent By ccole Date 2016-12-27 Time 09:53 Rev Time 0.00
Received By ccole Date 2016-12-21 Time 13:00 Sent To  
Notes
2016-12-22 13:01:04RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-29 Cont ID  
Sent By ccole Date 2016-11-29 Time 07:45 Rev Time 0.00
Received By ccole Date 2016-11-28 Time 13:25 Sent To  
Notes
2016-11-28 13:25:16CCOLE'S DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-27 Cont ID  
Sent By ccole Date 2016-12-27 Time 09:53 Rev Time 0.00
Received By ccole Date 2016-12-27 Time 09:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-29 Cont ID  
Sent By ccole Date 2016-11-29 Time 07:45 Rev Time 0.00
Received By ccole Date 2016-11-29 Time 07:45 Sent To  
Notes
2016-11-29 07:55:511ST REVIEW FBC-2014 RESIDENTIAL
 REVISION #16111107
 MASTER #15100627
 11/29/16
  
 1) IDENTIFY ALL ROOMS AND SPACES ON THE LAYOUT PLAN-
 SECTION 107.1 WPB AMENDMENTS TO THE FBC.
  
 2) INDICATE THE TYPE AND SIZE OF DRYER EXHAUST DUCT,
 SHOW THE DUCT RUN AND TERMINATION LOCATION- M1502.
  
 3) SHOW THE 2ND FLOOR BATH EXHAUST DUCT RUNS AND
 TERMINATION LOCATIONS- M1501.1
  
 4) THE 10X10 RETURN GRILLS ARE UNDERSIZED FOR 225 & 250
 CFMS- SECTION M1602.4. 50 SQ. INCHES PER 100 CFM
 REQUIRED-
  
 5) PROVIDE CONDENSER ANCHORING DETAILS- M1305.1.4.1 &
 M1401.4
  
 6) SUBMIT SPECS FOR THE RANGE HOOD- M1503
  
 7) SUBMIT A SUB-PERMIT APPLICATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  