Plan Review Details - Permit 16111051
Plan Review Stops For Permit 16111051
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-12-19 Cont ID  
Sent By tklarge Date 2016-12-19 Time 09:11 Rev Time 0.00
Received By tklarge Date 2016-12-19 Time 09:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-12-10 Cont ID  
Sent By tklarge Date 2016-12-10 Time 08:58 Rev Time 0.00
Received By tklarge Date 2016-12-10 Time 08:37 Sent To  
Notes
2016-12-10 08:57:461) INDICATE THE DELIVERY PRESSURE AND THE PRESSURE DROP
 ON THIS SYSTEM. THE SIZING DOCUMENTS SUBMITTED FOR THE
 TRACPIPE SHOW THAT A 3/4" LINE IS UNDERSIZED TO SUPPLY
 THE BTU LOAD FOR BOTH TANKLESS WATER HEATERS AT 1/2 LB.
 SUPPLY PRESSURE WITH A PRESSURE DROP OF 0.5" W.C.FOR
 BOTH AN 80 FEET AND 10 FEET RUN.
 2) IF THIS IS A 2 LB. SYSTEM, SHOW THE LOCATION OF THE
 PRESSURE REGULATORS ON THE PLAN. PLEASE SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY REFLECTS THE ENTIRE GAS
 SYSTEM, PIPE SIZES, TOTAL LENGTH FROM THE POINT OF
 DELIVERY TO THE FURTHEST OUTLET, ETC.
 SEE THE PREVIOUS GAS REVIEW COMMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-11-26 Cont ID  
Sent By tklarge Date 2016-11-26 Time 03:56 Rev Time 0.00
Received By tklarge Date 2016-11-26 Time 03:38 Sent To  
Notes
2016-11-26 03:53:481. SUBMIT AN ISOMETRIC DRAWING FOR ALL CHANGES BEING
 MADE TO THE EXISTING GAS PIPING SYSTEM AND THAT CLEARLY
 SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014
 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES
 SEC. G2413.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 7. INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT, SUBMIT A
 GAS RISER SHOWING ALL GAS APPLIANCES ON THE SYSTEM, THE
 BTU LOAD OF EACH APPLIANCE AND THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF EACH SECTION.
  
 8 SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE
 WATER HEATERS SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS FOR THE MINIMUM REQUIRED
 DISTANCE FROM OPERABLE WINDOWS AND DOORS..
  
 9 SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE
 THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC
 SEC.402.3, FBCR SEC. G 2413.3.
  
 10 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. FGC SECS. 401.4, 401.8, 402.1,402.2,
 402.3 , FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-19 Cont ID  
Sent By tklarge Date 2016-12-19 Time 09:11 Rev Time 0.00
Received By tklarge Date 2016-12-19 Time 09:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-10 Cont ID  
Sent By tklarge Date 2016-12-10 Time 08:58 Rev Time 0.00
Received By tklarge Date 2016-11-23 Time 12:46 Sent To G
Notes
***NONE***