Plan Review Details - Permit 16110987
Plan Review Stops For Permit 16110987
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-01-06 Cont ID  
Sent By cthroop Date 2017-01-06 Time 11:17 Rev Time 0.00
Received By cthroop Date 2017-01-06 Time 11:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-01-05 Cont ID  
Sent By cthroop Date 2017-01-05 Time 10:24 Rev Time 0.00
Received By cthroop Date 2017-01-05 Time 10:24 Sent To  
Notes
2017-01-05 11:10:32BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THIS IS A REPAIR TO AN EXISTING BUILDING, (STORAGE
 STRUCTURE). CHANGE GOVERNING CODES TO 2014 FBC EXISTING
 BUILDING.
 2. WORK COMPLETED WITHOUT PERMIT AS INDICATED ON PLANS.
 4X FEE WILL APPLY.
 3. ENGINEER OF RECORD (EOR) TO PRODUCE CERTIFICATION
 LETTER FOR COMPLETED WORK. INCLUDE CERTIFICATION OF
 WOOD CONNECTORS PREVIOUSLY REVIEWED AND APPROVED BY
 EOR.
 4. CHANGE SCOPE OF WORK TO ACCURATLEY DESCRIBE EXTENT
 OF WORK COMPLETED WITHOUT PERMIT. IF WINDOWS AND DOORS
 WERE INSTALLED PROVIDE PRODUCT APPROVALS FOR EACH.
 5. FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
 6. A PERMIT FOR THE STORAGE STRUCTURE DOES NOT RELIEVE
 OWNER FROM THE EXISTING 4X FEE IMPOSED FOR WORK
 PERFORMED ON MAIN HOUSE AND GARAGE. REF: CASE #
 CE16050796.
 7. THE STATED VALUE APPEARS LOW.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE VALUATION
 ACCORDINGLY.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-08 Cont ID  
Sent By cthroop Date 2016-12-08 Time 08:06 Rev Time 0.00
Received By cthroop Date 2016-12-08 Time 08:06 Sent To  
Notes
2016-12-08 08:28:15BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. PROVIDE SITE PLAN WITH ALL STRUCTURES ON PROPERTY
 WITH SETBACKS.
 2. PROVIDE DETAIL FOR WATER-RESISTIVE BARRIER PER FBC
 1403.2. INCLUDE ALL FLASHINGS.
 3. VALUE APPEARS LOW.
  
 FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE
 SETBACKS AND BUILDING SEPARATION.
  
 1403.2 WEATHER PROTECTION.
 EXTERIOR WALLS SHALL PROVIDE THE BUILDING WITH A
 WEATHER-RESISTANT EXTERIOR WALL ENVELOPE. THE EXTERIOR
 WALL ENVELOPE SHALL INCLUDE FLASHING, AS DESCRIBED IN
 SECTION 1405.4. THE EXTERIOR WALL ENVELOPE SHALL BE
 DESIGNED AND CONSTRUCTED IN SUCH A MANNER AS TO PREVENT
 THE ACCUMULATION OF WATER WITHIN THE WALL ASSEMBLY BY
 PROVIDING A WATER-RESISTIVE BARRIER BEHIND THE EXTERIOR
 VENEER, AS DESCRIBED IN SECTION 1404.2, AND A MEANS FOR
 DRAINING WATER THAT ENTERS THE ASSEMBLY TO THE
 EXTERIOR. PROTECTION AGAINST CONDENSATION IN THE
 EXTERIOR WALL ASSEMBLY SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 1405.3.
  
 THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF
 WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2017-01-04 Cont ID  
Sent By mvaldes Date 2017-01-04 Time 17:08 Rev Time 0.00
Received By mvaldes Date 2017-01-04 Time 16:53 Sent To B
Notes
2017-01-04 17:09:14NO ELECTRICAL WORK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-07 Cont ID  
Sent By mvaldes Date 2016-12-07 Time 14:08 Rev Time 0.00
Received By mvaldes Date 2016-12-07 Time 13:41 Sent To B
Notes
2016-12-07 14:08:321ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE A SITE SPECIFIC ELECTRICAL FLOOR PLAN WITH
 ALL POWER & LIGHTING OUTLETS SHOWN FOR THE PROPOSED
 PLAYROOM. FBC 107
  
 2] COMPLY WITH RECEPTACLE SPACING REQUIREMENTS PER
 FBC-R SECTIONS E3901.2.1 & E3902.2.2.
  
 3] ADD A GENERAL ELECTRICAL NOTE FOR AFCI PROTECTION IN
 ACCORDANCE WITH FBC-R SECTIONS E3902.2.2 & E3902.13.
  
 4] SMOKE ALARMS REQUIRED PER FBC-R 314 & 315, IF
 EXISTING PLEASE MAKE A NOTE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-05 Cont ID  
Sent By cthroop Date 2017-01-05 Time 10:24 Rev Time 0.00
Received By cthroop Date 2016-12-21 Time 13:25 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-08 Cont ID  
Sent By cthroop Date 2016-12-08 Time 08:06 Rev Time 0.00
Received By cthroop Date 2016-12-02 Time 15:24 Sent To  
Notes
2016-12-05 15:24:48ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2016-12-30 Cont ID  
Sent By cthroop Date 2017-01-05 Time 10:24 Rev Time 0.00
Received By njwira Date 2016-12-21 Time 17:25 Sent To E
Notes
2016-12-30 15:45:4012/30/16- PASSED
  
 STRUCTURE IS A LEGAL NON-CONFORMITY
 STORAGE HAS NO KITCHEN OR LIVING SPACE PERMITTED
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-12-07 Cont ID  
Sent By njwira Date 2016-12-07 Time 10:17 Rev Time 0.00
Received By njwira Date 2016-12-06 Time 13:46 Sent To E
Notes
2016-12-07 10:19:3412/7/16- FAILED
  
 SF-7 SINGLE FAMILY LOW DENSITY RESIDENTIAL
  
 FAILED
 1. NEED INTERIOR DRAWINGS SHOWING WHAT ROOMS AND WHERE
 ARE THE ROOMS IN THE GARAGE APPEARS THERE IS A
 RESIDENCE CURRENTLY THERE.
 2. 94-304(2) PLEASE PROVIDE TWO(2) COPIES OF A SURVEY
 SHOWING THAT SETBACKS ARE MET.
  
 PASSED
 1. BUILDING HEIGHT IS 8FT. 3IN. MEETING 25FT. LIMIT
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  