Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-13 Cont ID  
Sent By cthroop Date 2016-12-13 Time 08:52 Rev Time 0.00
Received By cthroop Date 2016-12-13 Time 08:52 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-18 Cont ID  
Sent By cthroop Date 2016-11-18 Time 10:39 Rev Time 0.00
Received By cthroop Date 2016-11-18 Time 10:38 Sent To E
Notes
2016-11-18 10:43:03BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
  
 1. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE PLAN PER FBC
 107.
  
 2. FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-12 Cont ID  
Sent By mvaldes Date 2016-12-12 Time 15:47 Rev Time 0.00
Received By mvaldes Date 2016-12-12 Time 15:34 Sent To B
Notes
2016-12-12 15:47:51ROUTED TO CT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-28 Cont ID  
Sent By mvaldes Date 2016-11-28 Time 09:27 Rev Time 0.00
Received By mvaldes Date 2016-11-28 Time 08:59 Sent To P
Notes
2016-11-28 09:14:581ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
  
 1] A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS
 SHALL BE PROVIDED TO SERVE ALL WALL AND FLOOR
 RECEPTACLE OUTLETS LOCATED IN THE KITCHEN. NEC
 210.52(B)(1) A NOTE WILL SUFFICE.
  
 2] SHOW GFCI PROTECTED RECEPTACLE OUTLETS & COMPLY WITH
 COUNTER TOP SPACING REQUIREMENTS ON THE KITCHEN LAYOUT
 FLOOR PLAN, INCLUDE ALL KITCHEN APPLIANCES OUTLET
 LOCATION (RANGE,DISHWASHER,MICROWAVE, & ETC) ASWELL PER
 NEC 210.8(A)(6) & 210.52(C)
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-13 Cont ID  
Sent By gjohnson Date 2016-12-13 Time 16:47 Rev Time 0.00
Received By gjohnson Date 2016-12-02 Time 13:36 Sent To  
Notes
2016-12-05 13:38:25RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-05 Cont ID  
Sent By lmarchan Date 2016-12-05 Time 13:35 Rev Time 0.00
Received By lmarchan Date 2016-11-16 Time 09:31 Sent To  
Notes
2016-11-17 09:31:56BLDG MISC 1

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-12-13 Cont ID  
Sent By gjohnson Date 2016-12-13 Time 16:32 Rev Time 0.00
Received By gjohnson Date 2016-12-13 Time 16:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-11-29 Cont ID  
Sent By gjohnson Date 2016-11-29 Time 06:26 Rev Time 0.00
Received By gjohnson Date 2016-11-29 Time 06:26 Sent To  
Notes
2016-11-29 06:31:071ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE EXISTING LAYOUT. PER WPB AMEND TO FBC
 107.2.1
  
 2. PROVIDE SCOPE OF WORK FOR PLUMBING. PER WPB AMEND TO
 FBC 107.2.1
  
 3. COMPLY WITH COMMENTS FROM BUILDING AND ELECTRICAL.
 PER WPB AMEND TO FBC 107.2.1