Plan Review Stops For Permit 16110718 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-11-23 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-11-23 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-11-23 |
Time |
12:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-11-23 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-11-23 |
Time |
09:24 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-11-23 |
Time |
08:23 |
Sent To |
|
|
Notes |
2016-11-23 09:24:47 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] PLEASE LABEL WIRE-WAY "LINE GUTTER" & SHOW DIMESION | | SIZES, LABEL EACH DISCONNECT WITH UNIT & ADDRESS | | NUMBERS IT SERVES PER NEC 225.37 (IDENTIFICATION) | | | | 2] PROVIDE GROUNDING ELECTRODE CONDUCTOR SIZE ON THE | | RISER DIAGRAM. NEC 250.66 | | | | 3] ALONG WITH THE TOTAL BUILDING CALCULATION PROVIDE | | PANEL SCHEDULES FOR NEW PANELS WITH INDIVIDUAL LOAD | | CLACS PER EACH. FBC 107.3.5.3 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-11-23 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-11-23 |
Time |
09:24 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-11-15 |
Time |
14:13 |
Sent To |
|
|
Notes |
2016-11-16 14:13:27 | ROUTED TO ELECTRICAL INBOX |
|
|
|