Plan Review Details - Permit 16110616
Plan Review Stops For Permit 16110616
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-01-05 Cont ID  
Sent By jwitmer Date 2017-01-05 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2017-01-05 Time 09:20 Sent To  
Notes
2017-01-05 09:59:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110616
 ADD: 5001 N. MILITARY TRAIL
 CONT: DAVCO ELECTRICAL
 TEL: 561-732-3434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. JAN. 05/ 2017
 ACTION:PASSED
  
 NOTE! PAPER PLANS SUBMITTED WITH ORIGINAL SEAL &
 SIGNATURE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-12-22 Cont ID  
Sent By jwitmer Date 2016-12-22 Time 08:20 Rev Time 0.00
Received By jwitmer Date 2016-12-22 Time 08:10 Sent To  
Notes
2016-12-22 08:20:10BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110616
 ADD: 5001 N. MILITARY TRAIL
 CONT: DAVCO ELECTRICAL
 TEL: 561-732-3434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. DEC, 22/ 2016
 ACTION: DENIED
  
 1) LIGHT POLE CALCULATIONS BY DAVID B. ROGERS, P. E.
 ARE ORIGINAL SIGNED AND SEALED DOCUMENTS WITH SEALED
 INDEX SHEET. APPROVED.
  
 2) DENIED: POLE FOUNDATION ANALYSIS 3 INDIVIDUAL SHEETS
 WITH STAMPED COPIES OR ELECTRONIC SIGNATURE YOU CAN SEE
 THE INDIVIDUAL PIXELS OF THE COLORED INK, IDENTICAL
 SIGNATURES ON ALL 6 SHEETS OF THE 2 REPORTS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE
 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-28 Cont ID  
Sent By jwitmer Date 2016-11-28 Time 12:36 Rev Time 0.00
Received By jwitmer Date 2016-11-28 Time 12:00 Sent To  
Notes
2016-11-28 12:36:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110616
 ADD: 5001 N. MILITARY TRAIL
 CONT: DAVCO ELECTRICAL
 TEL: 561-732-3434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 28/2016
 ACTION: DENIED
  
 1) 12 FOOT POLE CALCULATIONS PREPARED BY DAVID B.
 ROGERS P. E. ON THE COVER PAGE LIST ALL DOCUMENTS UNDER
 THE ELECTRONIC SIGNATURE. THE ISSUE IS THE PLANS
 INDICATE THEY ARE ELECTRONICALLY SIGNED AND SEALED. THE
 SIGNATURE BLOCK IS TO OPEN UP UPON HOVERING OVER THE
 SIGNATURE FOR VERIFICATION. THIS SIGNATURE DOES NOT
 OPEN.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 2A) THE 25 FOOT CALCULATIONS PREPARED BY CHRIS
 ARLANDSON, P. E. THE SIGNATURE BLOCK IS TO OPEN UP UPON
 HOVERING OVER THE SIGNATURE FOR VERIFICATION. THIS
 SIGNATURE DOES NOT OPEN.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 2B) THE 25 FOOT CALCULATIONS PREPARED BY CHRIS
 ARLANDSON, P. E. ARE MULTIPLE PAGE DOCUMENT AND ONLY
 THE FRONT PAGE SHOWS AN ATEMPT AT AN ELECTRONIC
 SIGNATURE.
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-05 Cont ID  
Sent By mvaldes Date 2016-12-05 Time 12:27 Rev Time 0.00
Received By mvaldes Date 2016-12-05 Time 12:27 Sent To  
Notes
2016-12-05 12:28:46SPOKE TO PROJECT MANAGER AND THE INFORMATION I
 REQUESTED WAS ALREADY PERMITTED UNDER A SEPERATE
 APLLICATION. MV

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-17 Cont ID  
Sent By mvaldes Date 2016-11-17 Time 10:24 Rev Time 0.00
Received By mvaldes Date 2016-11-17 Time 10:09 Sent To  
Notes
2016-11-17 10:25:45JOB PERMIT NUMBER: 16110616
 JOB ADDRESS: 5001 N MILITARY TRAIL
 WEST PALM BEACH FLORIDA (THE BALLPARK OF THE PALM
 BEACHES)
 DATE: NOVEMBER 17, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] CLARIFY ILLUMINATION LEVELS BEING LESS THAN 1'
 CANDLE IN THE FOLLOWING AREAS; WEST APPROACH ROAD, EAST
 APPROACH ROAD, & SOUTH PROPERTY LINE. REFER TO
 FBC-1006.2
  
 2] PROVIDE A VOLTAGE DROP SCHEDULE TO COMPLY WITH FBC-E
 SECTION C405.7.3.2 BRANCH CIRCUIT CONDUCTORS SHALL BE
 SIZED FOR A MAXIMUM VOLTAGE DROP OF 3% DESIGN LOAD.
 PLEASE INCLUDE WIRE & CONDUIT SIZE ON THE SCHEDULE
 CHART.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-05 Cont ID  
Sent By   Date 2017-01-05 Time 10:01 Rev Time 0.00
Received By lmarchan Date 2017-01-04 Time 11:44 Sent To  
Notes
2017-01-04 11:44:38ORIGINAL SIGNED COPIES ROUTED TO JWITMER FOR REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-22 Cont ID  
Sent By   Date 2016-12-22 Time   Rev Time 0.00
Received By lmarchan Date 2016-12-16 Time 14:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-02 Cont ID  
Sent By lmarchan Date 2016-12-02 Time 13:23 Rev Time 0.00
Received By lmarchan Date 2016-11-14 Time 15:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-01-05 Cont ID  
Sent By lmarchan Date 2017-01-05 Time 13:42 Rev Time 0.00
Received By lmarchan Date 2017-01-05 Time 13:42 Sent To  
Notes
2017-01-05 10:00:38BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110616
 ADD: 5001 N. MILITARY TRAIL
 CONT: DAVCO ELECTRICAL
 TEL: 561-732-3434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. JAN. 05/ 2017
 ACTION: DENIED
  
 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) LIGHT POLE CALCULATIONS FOR 12 FOOT POLES BY DAVID
 B. ROGERS, P. E. ARE ORIGINAL SIGNED AND SEALED
 DOCUMENTS WITH SEALED INDEX SHEET AND HAS A STATEMENT
 THE REPORT IS ELECTRONICALLY SEALED.
 THE ELECTRONIC SIGNATURE DOES NOT OPEN FOR VERIFICATION
 OF AUTHENTICITY OF SIGNATURE. 61G15-23.005 PROCEDURES
 FOR SIGNING AND SEALING ELECTRONICALLY TRANSMITTED
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2A) 3RD REVIEW. DENIED: 25 FY. POLE FOUNDATION ANALYSIS
 3 INDIVIDUAL SHEETS. FL ADMIN CODE 61G15-23.002
 ENGINEERS. EFFECTIVE DATE 05/06/2009. (2)(A) EVERY
 SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED UNDER
 THE PROVISIONS OF CHAPTER 471, F.S., SHALL BE SEALED,
 SIGNED AND DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE.
  
 2B) THE ELECTRONIC SIGNATURE OF CHRIS ARLANDSON P. E.
 DOES NOT VALIDATE ITSELF. THE ELECTRONIC SIGNATURE DOES
 NOT OPEN FOR VERIFICATION OF AUTHENTICITY OF SIGNATURE.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
2017-01-04 11:44:581/4/17 ORIGINAL RESUBMITTED SIGNED COPIES ROUTED TO
 JWITMER FOR REVIEW
2016-12-16 14:22:2012/16/16 RECEIVED SIGNED AND SEALED DRAWINGS, IN
 LIBRARY. LEM

Review Stop Z ZONING
Rev No 1 Status P Date 2016-11-30 Cont ID  
Sent By ajones Date 2016-11-30 Time 14:26 Rev Time 0.00
Received By ajones Date 2016-11-30 Time 14:26 Sent To  
Notes
***NONE***