Plan Review Details - Permit 16110614
Plan Review Stops For Permit 16110614
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-04 Cont ID  
Sent By vperez Date 2017-01-04 Time 08:43 Rev Time 0.00
Received By vperez Date 2017-01-04 Time 08:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-28 Cont ID  
Sent By mvaldes Date 2016-11-28 Time 09:45 Rev Time 0.00
Received By mvaldes Date 2016-11-28 Time 09:45 Sent To  
Notes
2016-11-28 09:49:341ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] LABEL EACH AREA ON THE FLOOR PLAN WITH THE
 OCCUPATION IT PROPERLY SERVES. FBC 107
  
 2] ADD FA DEVICES PER FIRE MARSHALL REQUEST IN
 ACCORDANCE WITH NFPA 101 & NFPA 72

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-12-30 Cont ID  
Sent By pleduc Date 2016-12-30 Time   Rev Time 0.00
Received By pleduc Date 2016-12-30 Time 12:49 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-11-17 Cont ID  
Sent By mvaldes Date 2016-11-28 Time 09:50 Rev Time 0.00
Received By pleduc Date 2016-11-16 Time 16:16 Sent To E
Notes
2016-11-17 14:00:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE APPEARS TO BE LIMITED DETAIL IN EACH OF THE
 SEPARATED OCCUPANCIES INDICATED WALL SECTIONS,
 BATHROOMS, OFFICES, ETC, THAT MAY BE REQUIRED TO HAVE
 ALARM NOTIFICATIONS.
  
 PLEASE PROVIDE FOR GREATER DETAIL IN EACH OF THE AREAS
 AND NOTIFICATIONS DEVICES AS REQUIRED PER NFPA 101,
 CHAPTER 9, BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT, 9.6 FIRE DETECTION, ALARM, AND
 COMMUNICATIONS SYSTEMS AND NFPA 72.
  
 PROVIDE CODE AND NARATIVE JUSTIFICATION IF YOU BELIEVE
 THEY MAY NOT BE REQUIRED.
  
  
  
 2) THERE APPEARS TO BE DIFFERENCT OCCUPANCIES OR SPACES
 THAT MAY BE VACANT.
  
 PLEASE PROVIDE THE OCCUPANCIES CLASSIFICATION OF EACH
 SPACE AND THE DETAILED PROPOSED ALARM DEVICES OF THE
 SPACE AS THERE MAY BE SEPARATE/DIFFERENT REQUIRMENTS
 THAT NEED TO BE MET.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-04 Cont ID  
Sent By vperez Date 2017-01-04 Time 08:44 Rev Time 0.00
Received By vperez Date 2017-01-04 Time 08:44 Sent To  
Notes
2016-12-29 10:01:44RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-28 Cont ID  
Sent By mvaldes Date 2016-11-28 Time 09:50 Rev Time 0.00
Received By mvaldes Date 2016-11-14 Time 13:36 Sent To FIRE
Notes
***NONE***