Plan Review Details - Permit 16110285
Plan Review Stops For Permit 16110285
Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2017-04-20 Time 10:07 Sent To  
Notes
2017-04-21 10:07:39RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-09 Cont ID  
Sent By lmarchan Date 2016-11-09 Time 08:33 Rev Time 0.00
Received By lmarchan Date 2016-11-07 Time 09:46 Sent To  
Notes
2016-11-08 09:47:05REVISION ROUTED TO JVALIDO

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-04-24 Cont ID  
Sent By hmoser Date 2017-04-24 Time 14:32 Rev Time 0.00
Received By hmoser Date 2017-04-24 Time 14:20 Sent To  
Notes
2017-04-24 14:59:58 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-08 Cont ID  
Sent By jvalido Date 2016-11-08 Time 14:17 Rev Time 0.00
Received By jvalido Date 2016-11-08 Time 13:22 Sent To  
Notes
2016-11-08 14:15:43CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 AS PER DAIKIN SPECIFICATIONS THE RATED CFM OUTPUT AT .1
 FRICTION LOST FOR DV24PVCC14 IS 700 CFM. MAXIMUM OUTPUT
 AT .1 FRICTION LOST IS 770 CFM. AS PER YOUR SUBMITTED
 PLANS THE FIRST FLOOR TOTAL SUPPLY OUTLET CFM OUTPUT IS
 500 CFM. AS PER YOUR SUBMITTED PLANS THE SECOND FLOOR
 TOTAL SUPPLY OUTLET CFM OUTPUT IS 575 CFM.
  
 (1) PROVIDE PROPER SUPPLY AIR OUTLET CFM DISTRIBUTION
 BALANCE AS PER RATED CFM MANUFACTURER SPECIFICATIONS.
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  