Plan Review Details - Permit 16110230
Plan Review Stops For Permit 16110230
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-07 Cont ID  
Sent By ccole Date 2016-12-07 Time 12:26 Rev Time 0.00
Received By ccole Date 2016-12-05 Time 10:31 Sent To  
Notes
2016-12-06 10:31:11RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-14 Cont ID  
Sent By ccole Date 2016-11-14 Time 11:30 Rev Time 0.00
Received By ccole Date 2016-11-04 Time 13:09 Sent To  
Notes
2016-11-07 13:09:35ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-07 Cont ID  
Sent By ccole Date 2016-12-07 Time 12:26 Rev Time 0.00
Received By ccole Date 2016-12-07 Time 12:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-14 Cont ID  
Sent By ccole Date 2016-11-14 Time 10:57 Rev Time 0.00
Received By ccole Date 2016-11-14 Time 10:57 Sent To  
Notes
2016-11-14 11:29:141ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110230
 11/14/16
  
 1) THE 18X18" RETURN GRILL IS UNDERSIZED PER SECTION
 601.5- 600 SQ. INCHES REQUIRED.
  
 2) REFER TO SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION: THE MECHANICAL CLOSET SHALL BE CONSIDERED
 A "PLENUM CHAMBER" AND MUST BE CONSTRUCTED IN
 ACCORDANCE WITH SECTION 602.1. PLEASE VERIFY
 COMPLIANCE.
  
 3) THE BMP CLIP SUBMITTAL HAS A COPIED ENGINEER'S
 SIGNATURE AND SEAL WHICH IS NOT ACCEPTABLE PER SECTION
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE. PROVIDE SITE
 SPECIFIC WIND LOAD ENGINEERING DESIGNED BY A FL.
 LICENSED ENGINEER- SEE SECTION 301.15 FBC-14
 MECHANICAL, AND SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  