2016-12-09 07:34:11 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| CODE: FBC, 5TH EDITION (2014). |
| |
| 1- PLANS SUBMITTED ARE REFERENCING THE 2010 FBC. THE |
| CURRENT CODE IS THE FBC 5TH EDITION (2014). REVISE |
| INFORMATION ON SHEET A-1 AND A-3. CHAPTER 553 F.S. |
| |
| 2- ACCORDING TO SEC. R301.2.1.4 OF FBC 5TH EDITION |
| (2014) THIS BUILDING IS LOCATED IN EXPOSURE "C" NOT |
| "B". REVISE INFORMATION ON SHEET A-1 AND A3 AS |
| REQUIRED. |
| |
| 3- SHEET A-2: WINDOWS SPECIFIED FOR BEDROOM LOCATED |
| ADJACENT TO THE GARAGE DON'T FIT ON THE OPENING SIZE |
| SPECIFIED ON PLANS. REVISE AS REQUIRED. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| 4- CLARIFY IF PROPOSED ENTRY DOOR IS "INSWING" OR |
| "OUTSWING". SHEET A-2 SHOWS "INSWING" ENTRY DOOR, WHILE |
| SHEET S-1 SHOWS "OUTSWING" ENTRY DOOR. NOTE: TYPE OF |
| SWING IS IMPORTANT FOR PROPER PRODUCT APPROVAL L |
| REVIEW. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| NOTE: |
| DESIGNER OF RECORD TO COORDINATE WITH PERSON PREPARING |
| THE ENERGY CALCULATIONS TO AVOID CONFLICTS/DELAYS. |
| DESIGNER OF RECORD TO PROVIDE ALL THE DETAILS AND |
| SPECIFICATIONS REQUIRED BASED ON THE INFORMATION |
| SPECIFIED ON THE ENERGY CALCULATIONS SUBMITTED. |
| |
| 5- REVISE ENERGY CALCULATIONS SUBMITTED; |
| A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM |
| INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE |
| AND JURISDICTION. CLARIFY WHY THE PROJECT NAME IS 2416 |
| S. OLIVE AVE, WHILE THE STREET ADDRESS IS 2417 S. OLIVE |
| AVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH |
| EDITION (2014). |
| |
| B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| HOW THE EXISTING HOUSE COMPLIES WITH THE R-2 INSULATION |
| ON THE SLAB ON GRADE EDGE INSULATION SPECIFIED ON ITEM |
| #8. SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| HOW THE EXISTING HOUSE COMPLIES WITH THE R-8 CONCRETE |
| BLOCK EXTERIOR INSULATION SPECIFIED ON ITEM #9. SEC. |
| R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| HOW THE EXISTING HOUSE COMPLIES WITH THE R-38 CEILING |
| INSULATION SPECIFIED ON ITEM #10. SEC. R405.4.3 |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| E) COOLING AND HEATING INFORMATION SHOWN ON ITEMS #12 |
| AND #13 DON'T MATCH EQUIPMENT SIZING CALCULATIONS |
| SUBMITTED. REVISE AS REQUIRED, INCLUDING THE SEER. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| F) REVISE TYPE OF HOT WATER SYSTEM SPECIFIED ON ITEM |
| #14. PLANS SUBMITTED DON'T SPECIFY ELECTRIC SYSTEM. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| G) CEILING FANS CREDIT IS TAKEN ON ITEM #15. SPECIFY ON |
| PLANS SIZE AND LOCATION OF CEILING FANS AS REQUIRED BY |
| SEC. R405.7.6 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| H) OWNER /AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS |
| REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). |
| |
| I) NUMBER OF OCCUPANTS SPECIFIED UNDER "SPACES" ON PAGE |
| 2 OF 4 DOESN'T MATCH NUMBER OF OCCUPANTS SHOWN ON THE |
| EQUIPMENT SIZING CALCULATIONS SUBMITTED. REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). |
| |
| J) TYPE OF ROOF SPECIFIED UNDER "ROOF" ON PAGE 2 OF 4 |
| DOESN'T MATCH TYPE OF ROOF SHOWN ON PLANS. REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). |
| |
| K) ACCORDING TO SEC. R806.2 FBC-RESIDENTIAL, THE |
| REQUIRED ATTIC VENTILATION RATIO IS 1/150. ATTIC |
| INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC |
| VENTILATION RATIO. PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING HOW THE EXISTING HOUSE COMPLIES |
| WITH THE 1/300 RATIO. SEE SEC. R806.2 FBC-RESIDENTIAL |
| FOR THE REQUIREMENTS REQUIRED TO MEET THIS VENT RATIO |
| AND PROVIDE THE REQUIRED DOCUMENTATION. |
| |
| L) REVISE THE WINDOWS/DOORS OVERHANG SEPARATION |
| SPECIFIED ON SHEET 3 OF 4 TO MATCH PLANS. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| M) DOORS INFORMATION ON PAGE 3 OF 4 SPECIFIES INSULATED |
| DOORS. TYPE OF DOORS DON'T MATCH TYPE OF DOORS |
| SPECIFIED ON PLANS AND PRODUCT APPROVALS SUBMITTED. |
| DOOR WITH GLAZING NEEDS TO BE SPECIFIED ON WINDOWS AREA |
| AS REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). |
| |
| N) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED |
| BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| NOTE: |
| LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL |
| BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT USING |
| THE PROGRAM DEFAULT FACTORS. |
| |
| 6-CEILING FANS CREDIT IS TAKEN ON ITEM #15. DESIGNER OF |
| RECORD TO SPECIFY ON PLANS SIZE AND LOCATION OF CEILING |
| FANS AS REQUIRED BY SEC. 103.2 FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). |
| |
| 7- ACCORDING TO SEC. R806.2 FBC-RESIDENTIAL, THE |
| REQUIRED ATTIC VENTILATION RATIO IS 1/150. ATTIC |
| INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC |
| VENTILATION RATIO. DESIGNER OF RECORD TO PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE |
| EXISTING HOUSE COMPLIES WITH THE 1/300 RATIO AS |
| REQUIRED BY SEC. R806.2 FBC-RESIDENTIAL. |
| |
| 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR "INSWING" ENTRY DOOR AS SHOWN |
| ON PLANS. |
| |