Plan Review Details - Permit 16110161
Plan Review Stops For Permit 16110161
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-01-13 Cont ID  
Sent By jgomez Date 2017-01-13 Time 12:06 Rev Time 0.00
Received By jgomez Date 2017-01-13 Time 11:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-01-10 Cont ID  
Sent By jgomez Date 2017-01-09 Time 18:36 Rev Time 0.00
Received By jgomez Date 2017-01-09 Time 15:14 Sent To  
Notes
2017-01-09 15:25:52RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST. .
 CODE: FBC, 5TH EDITION (2014).
  
  
 1- BUILDING IS LOCATED IN EXPOSURE "C" NOT "B".
 ENGINEER OF RECORD TO REVISE EXPOSURE OR PROVIDE
 ENGINEERING ANALYSIS FOR AN "INTERMEDIATE EXPOSURE" AS
 REQUIRED BY THE EXCEPTION ON SEC. R301.2.1.4
 FBC-RESIDENTIAL. NOTE: REVISE DOORS/WINDOWS DESIGN
 PRESSURES ACCORDINGLY. (REPEAT COMMENT).
  
 2- SHEET A-2: WINDOWS SPECIFIED FOR BEDROOM LOCATED
 ADJACENT TO THE GARAGE DON'T FIT ON THE OPENING SIZE
 SPECIFIED ON PLANS. THE WIDTH DIMENSION WAS CHANGED
 FROM 5'-2" TO 62". THIS IS THE SAME DIMENSION. THE
 SPECIFIED WINDOWS AND MULLION DON'T FIT IN THIS
 OPENING. REVISE OPENING WIDTH AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS. (REPEAT COMMENT).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-12 Cont ID  
Sent By jgomez Date 2016-12-09 Time 07:20 Rev Time 0.00
Received By jgomez Date 2016-12-08 Time 18:30 Sent To  
Notes
2016-12-09 07:34:11RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PLANS SUBMITTED ARE REFERENCING THE 2010 FBC. THE
 CURRENT CODE IS THE FBC 5TH EDITION (2014). REVISE
 INFORMATION ON SHEET A-1 AND A-3. CHAPTER 553 F.S.
  
 2- ACCORDING TO SEC. R301.2.1.4 OF FBC 5TH EDITION
 (2014) THIS BUILDING IS LOCATED IN EXPOSURE "C" NOT
 "B". REVISE INFORMATION ON SHEET A-1 AND A3 AS
 REQUIRED.
  
 3- SHEET A-2: WINDOWS SPECIFIED FOR BEDROOM LOCATED
 ADJACENT TO THE GARAGE DON'T FIT ON THE OPENING SIZE
 SPECIFIED ON PLANS. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 4- CLARIFY IF PROPOSED ENTRY DOOR IS "INSWING" OR
 "OUTSWING". SHEET A-2 SHOWS "INSWING" ENTRY DOOR, WHILE
 SHEET S-1 SHOWS "OUTSWING" ENTRY DOOR. NOTE: TYPE OF
 SWING IS IMPORTANT FOR PROPER PRODUCT APPROVAL L
 REVIEW. SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE:
 DESIGNER OF RECORD TO COORDINATE WITH PERSON PREPARING
 THE ENERGY CALCULATIONS TO AVOID CONFLICTS/DELAYS.
 DESIGNER OF RECORD TO PROVIDE ALL THE DETAILS AND
 SPECIFICATIONS REQUIRED BASED ON THE INFORMATION
 SPECIFIED ON THE ENERGY CALCULATIONS SUBMITTED.
  
 5- REVISE ENERGY CALCULATIONS SUBMITTED;
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION. CLARIFY WHY THE PROJECT NAME IS 2416
 S. OLIVE AVE, WHILE THE STREET ADDRESS IS 2417 S. OLIVE
 AVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW THE EXISTING HOUSE COMPLIES WITH THE R-2 INSULATION
 ON THE SLAB ON GRADE EDGE INSULATION SPECIFIED ON ITEM
 #8. SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW THE EXISTING HOUSE COMPLIES WITH THE R-8 CONCRETE
 BLOCK EXTERIOR INSULATION SPECIFIED ON ITEM #9. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW THE EXISTING HOUSE COMPLIES WITH THE R-38 CEILING
 INSULATION SPECIFIED ON ITEM #10. SEC. R405.4.3
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 E) COOLING AND HEATING INFORMATION SHOWN ON ITEMS #12
 AND #13 DON'T MATCH EQUIPMENT SIZING CALCULATIONS
 SUBMITTED. REVISE AS REQUIRED, INCLUDING THE SEER. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 F) REVISE TYPE OF HOT WATER SYSTEM SPECIFIED ON ITEM
 #14. PLANS SUBMITTED DON'T SPECIFY ELECTRIC SYSTEM.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 G) CEILING FANS CREDIT IS TAKEN ON ITEM #15. SPECIFY ON
 PLANS SIZE AND LOCATION OF CEILING FANS AS REQUIRED BY
 SEC. R405.7.6 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 H) OWNER /AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 I) NUMBER OF OCCUPANTS SPECIFIED UNDER "SPACES" ON PAGE
 2 OF 4 DOESN'T MATCH NUMBER OF OCCUPANTS SHOWN ON THE
 EQUIPMENT SIZING CALCULATIONS SUBMITTED. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 J) TYPE OF ROOF SPECIFIED UNDER "ROOF" ON PAGE 2 OF 4
 DOESN'T MATCH TYPE OF ROOF SHOWN ON PLANS. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 K) ACCORDING TO SEC. R806.2 FBC-RESIDENTIAL, THE
 REQUIRED ATTIC VENTILATION RATIO IS 1/150. ATTIC
 INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC
 VENTILATION RATIO. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE EXISTING HOUSE COMPLIES
 WITH THE 1/300 RATIO. SEE SEC. R806.2 FBC-RESIDENTIAL
 FOR THE REQUIREMENTS REQUIRED TO MEET THIS VENT RATIO
 AND PROVIDE THE REQUIRED DOCUMENTATION.
  
 L) REVISE THE WINDOWS/DOORS OVERHANG SEPARATION
 SPECIFIED ON SHEET 3 OF 4 TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 M) DOORS INFORMATION ON PAGE 3 OF 4 SPECIFIES INSULATED
 DOORS. TYPE OF DOORS DON'T MATCH TYPE OF DOORS
 SPECIFIED ON PLANS AND PRODUCT APPROVALS SUBMITTED.
 DOOR WITH GLAZING NEEDS TO BE SPECIFIED ON WINDOWS AREA
 AS REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 N) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT USING
 THE PROGRAM DEFAULT FACTORS.
  
 6-CEILING FANS CREDIT IS TAKEN ON ITEM #15. DESIGNER OF
 RECORD TO SPECIFY ON PLANS SIZE AND LOCATION OF CEILING
 FANS AS REQUIRED BY SEC. 103.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 7- ACCORDING TO SEC. R806.2 FBC-RESIDENTIAL, THE
 REQUIRED ATTIC VENTILATION RATIO IS 1/150. ATTIC
 INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC
 VENTILATION RATIO. DESIGNER OF RECORD TO PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE
 EXISTING HOUSE COMPLIES WITH THE 1/300 RATIO AS
 REQUIRED BY SEC. R806.2 FBC-RESIDENTIAL.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR "INSWING" ENTRY DOOR AS SHOWN
 ON PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-11 Cont ID  
Sent By mvaldes Date 2017-01-11 Time 14:55 Rev Time 0.00
Received By mvaldes Date 2017-01-11 Time 14:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-09 Cont ID  
Sent By mvaldes Date 2016-11-09 Time 16:15 Rev Time 0.00
Received By mvaldes Date 2016-11-09 Time 14:44 Sent To  
Notes
2016-11-09 16:16:25JOB PERMIT NUMBER: 16100893
 JOB ADDRESS: 2417 SOUTH OLIVE AVE
 WEST PALM BEACH FLORIDA 33401
 DATE: NOVEMBER 9, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] PROVIDE A RISER DIAGRAM WITH SERVICE FEEDER WIRE
 SIZE, CONDUIT DETAIL INCLUDING RACEWAY TYPE & SIZE,
 GROUNDING DETAIL WITH ELECTRODE CONDUCTOR SIZE. FBC-
 107.3.5.3
  
 2] SHOW A GFCI OUTDOOR RECEPTACLE OUTLET FOR THE W/H
 IGNITION.
  
 3] GARAGE DOOR MOTOR RECEPTACLE OUTLET REQUIRES GFCI
 PROTECTION PER FBC-R SEC E3902.2.
  
 4] CARBON MONOXIDE ALARM REQUIRED WITHIN 10' OF
 SLEEPING ROOMS DUE TO THE ATTACHED GARAGE PER FBC-R SEC
 315.1
  
 5] CLARIFY SMOKE ALARM LOCATED IN THE KITCHEN TO BE
 LISTED FOR THE USE FOR INSTALLATION NEAR COOKING
 APPLIANCES & EQUIPPED WITH A SILENCING MEANS FEATURE IN
 ACCORDANCE WITH NFPA 29.8.3.4 .
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-11-29 Cont ID  
Sent By tklarge Date 2016-11-29 Time 06:51 Rev Time 0.00
Received By tklarge Date 2016-11-29 Time 06:38 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2017-01-13 Cont ID  
Sent By destabro Date 2017-01-13 Time 11:58 Rev Time 0.00
Received By destabro Date 2017-01-13 Time 11:58 Sent To B
Notes
2017-01-13 12:02:431/13/17 - NO CHANGE TO PLANS REGARDING HISTORIC FABRIC.
 DLE

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2017-01-05 Cont ID  
Sent By fmittner Date 2017-01-05 Time 10:14 Rev Time 0.00
Received By fmittner Date 2017-01-05 Time 10:13 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-11-15 Cont ID  
Sent By fmittner Date 2016-11-15 Time 09:39 Rev Time 0.00
Received By fmittner Date 2016-11-15 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-13 Cont ID  
Sent By jgomez Date 2017-01-13 Time 14:34 Rev Time 0.00
Received By jgomez Date 2017-01-12 Time 11:42 Sent To  
Notes
2017-01-13 11:42:55MET WITH DESIGNER. HE RE-SUBMITTED REVISED PLANS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-11 Cont ID  
Sent By mvaldes Date 2017-01-11 Time 14:55 Rev Time 0.00
Received By mvaldes Date 2016-12-21 Time 13:20 Sent To  
Notes
2016-12-22 13:20:30R24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-12 Cont ID  
Sent By jgomez Date 2016-12-12 Time 11:40 Rev Time 0.00
Received By jgomez Date 2016-11-03 Time 13:18 Sent To  
Notes
2016-11-04 13:19:35R31

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-01-13 Cont ID  
Sent By jgomez Date 2017-01-13 Time 14:34 Rev Time 0.00
Received By jgomez Date 2017-01-13 Time 12:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-01-10 Cont ID  
Sent By jgomez Date 2017-01-10 Time 08:32 Rev Time 0.00
Received By jgomez Date 2017-01-09 Time 18:43 Sent To E
Notes
2017-01-09 19:11:24RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 1- THE LOAD CALCULATIONS ARE CONSIDERING 7 PEOPLE AS
 THE OCCUPANTS IN THIS SINGLE FAMILY RESIDENCE. NUMBER
 OF PEOPLE DOESN'T MATCH NUMBER OF PEOPLE SPECIFIED ON
 THE ENERGY CALCULATIONS. ALSO, CLARIFY WHY THE
 CALCULATIONS ARE CONSIDERING 2 PEOPLE IN THE DINING
 AREA?. THE NUMBER OF PEOPLE MAY AFFECT THE SIZING OF
 THE EQUIPMENT. SEC. R403.6.1 FBC-ENERGY CONSERVATION
 DOESN'T ALLOW ANY FACTORS THAT WILL AFFECT THE SIZING
 OF THE EQUIPMENT. REVISE AS REQUIRED. (REPEAT COMMENT).
  
 2- THE TRANSFER DUCT SIZE SPECIFIED ON THE A/C PLAN FOR
 THE MASTER BEDROOM DOESN'T COMPLY WITH THE BALANCED
 RETURN AIR. SEC. M1602.4. ALL THE SUPPLY AIR INTO THE
 MASTER BEDROOM NEEDS TO BE CONSIDERED, INCLUDING THE
 BATHROOM AS REQUIRED BY EXCEPTION #3 OF SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED. (REPEAT COMMENT).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-12 Cont ID  
Sent By jgomez Date 2016-12-12 Time 11:40 Rev Time 0.00
Received By jgomez Date 2016-12-12 Time 11:40 Sent To  
Notes
2016-12-12 11:47:56RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- THE PERSON WHO PREPARED THE LOAD CALCULATIONS IS THE
 SAME PERSON WHO PREPARED THE ENERGY CALCULATIONS. SEE
 BUILDING REVIEW COMMENTS FOR REQUIRED ENERGY
 CALCULATIONS REVISIONS AND REVISE THE LOAD CALCULATIONS
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- THE LOAD CALCULATIONS ARE CONSIDERING 12 PEOPLE AS
 THE OCCUPANTS IN THIS SINGLE FAMILY RESIDENCE. THE
 NUMBER OF PEOPLE LOOKS A LITTLE BIG HIGH FOR A THREE
 BEDROOM SINGLE FAMILY RESIDENCE. THE HIGH NUMBER OF
 PEOPLE MAY AFFECT THE SIZING OF THE EQUIPMENT. SEC.
 R403.6.1 DOESN'T ALLOW ANY FACTORS THAT WILL AFFECT THE
 SIZING OF THE EQUIPMENT. REVISE AS REQUIRED OR PROVIDE
 DOCUMENTATION SHOWING WHY A HIGHER NUMBER OF PEOPLE
 NEED TO BE CONSIDERED.
  
 3- LOAD CALCULATIONS TO INCLUDE THE EQUIPMENT
 MANUFACTURER'S AND MODEL NUMBER ALONG WITH THE SENSIBLE
 AND TOTAL COOLING CAPACITIES AS REQUIRED BY SEC.
 R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE WITH A/C PLAN SUBMITTED.
  
 4- THE TRANSFER DUCT SIZE SPECIFIED ON THE A/C PLAN FOR
 THE MASTER BEDROOM DOESN'T COMPLY WITH THE BALANCED
 RETURN AIR. SEC. M1602.4. ALL THE SUPPLY AIR INTO THE
 MASTER BEDROOM NEEDS TO BE CONSIDERED, INCLUDING THE
 BATHROOM AS REQUIRED BY EXCEPTION #3 OF SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED.
  
 5- CONDENSER UNIT TIE-DOWN CLIP PRODUCT APPROVAL
 SUBMITTED: PROVIDE CURRENT (2014 CODE) AND LEGIBLE
 PRODUCT APPROVAL.
 FAC 61G20-3.002(33).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-11-29 Cont ID  
Sent By tklarge Date 2016-11-29 Time 06:38 Rev Time 0.00
Received By tklarge Date 2016-11-29 Time 06:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2017-01-13 Cont ID  
Sent By destabro Date 2017-01-13 Time 11:59 Rev Time 0.00
Received By destabro Date 2017-01-13 Time 11:59 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-01-05 Cont ID  
Sent By fmittner Date 2017-01-05 Time 10:14 Rev Time 0.00
Received By fmittner Date 2017-01-05 Time 10:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-11-15 Cont ID  
Sent By fmittner Date 2016-11-15 Time 09:40 Rev Time 0.00
Received By fmittner Date 2016-11-15 Time 09:40 Sent To  
Notes
***NONE***