Plan Review Details - Permit 16110138
Plan Review Stops For Permit 16110138
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-16 Cont ID  
Sent By cthroop Date 2016-12-16 Time 15:17 Rev Time 0.00
Received By cthroop Date 2016-12-16 Time 15:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-01 Cont ID  
Sent By ccole Date 2016-12-01 Time 11:17 Rev Time 0.00
Received By cthroop Date 2016-12-01 Time 11:17 Sent To  
Notes
2016-12-01 11:21:22BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. PROVIDE COVER SHEET AND PLAN INDEX.
 2. PROVIDE LIST OF GOVERNING CODES.
 3. PROVIDE STRUCTURAL DETAILS FOR SERVICE LADDERS AND
 PLATFORMS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-15 Cont ID  
Sent By vperez Date 2016-12-15 Time 11:45 Rev Time 0.00
Received By vperez Date 2016-12-15 Time 11:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-08 Cont ID  
Sent By vperez Date 2016-11-08 Time 14:10 Rev Time 0.00
Received By vperez Date 2016-11-08 Time 14:10 Sent To FIRE
Notes
2016-11-08 14:12:44PLEASE SHOW ON THE PLANS THE SIZE OF EXISTING BRANCH
 CIRCUIT FEEDING COOLING TOWERS AND PANEL DESIGNATION
 WHERE POWER ORIGINATES. NOTE ON PLANS ABOUT REDUCTION
 OF LOADS OK.
  
 ADDRESS MECHANICAL COMMENTS FOR AN ELECTRICAL APPROVAL
  
 VAL PEREZ
 *6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-12-12 Cont ID  
Sent By pleduc Date 2016-12-12 Time   Rev Time 0.00
Received By pleduc Date 2016-12-09 Time 16:55 Sent To  
Notes
2016-12-12 10:54:13THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) PLEASE PROVIDE DETAILED INFOMATION INDICATING
 COMPLIANCE WITH NFPA 780 - LIGHTNING PROTECTION
 SYSTEMS.
  
 NFPA 214 , WATER-COOLING TOWERS
 5.7* LIGHTNING PROTECTION. LIGHTNING PROTECTION, WHERE
 PROVIDED, SHALL BE INSTALLED IN ACCORDANCE WITH THE
 PROVISIONS OF NFPA 780.
  
  
  
 2) PLEASE PROVIDE DETAILED INFORMATION INDICATING
 COMPLIANCE WITH NFPA 214 - WATER-COOLING TOWERS
  
 INCLUDING, BUT NO LIMITED TO:
  
 CHAPTER 4 LOCATION OF WATER-COOLING TOWERS
 4.1 CONSTRUCTION MATERIALS OF WATER-COOLING TOWERS.
 4.1.1 WHERE THE COOLING TOWER'S STRUCTURE, FAN,
 DISTRIBUTION SYSTEM, LOUVERS, AND FILL AND DRIFT
 ELIMINATOR MATERIALS ARE ALL OF NONCOMBUSTIBLE
 MATERIALS, A FIRE PROTECTION SYSTEM SHALL NOT BE
 REQUIRED.
 4.1.2 IF ANY OF THE CONSTRUCTION MATERIALS ARE
 COMBUSTIBLE AND THE FACTORS IN SECTION 4.2 NECESSITATE
 IT, FIRE PROTECTION SHALL BE PROVIDED IN ACCORDANCE
 WITH CHAPTER 5, AND TOWERS SHALL BE LOCATED IN
 ACCORDANCE WITH CHAPTER 4.
 4.2* FIRE RISK ANALYSIS. A FIRE RISK ANALYSIS SHALL BE
 CONDUCTED. THE FOLLOWING ARE SOME OF THE FACTORS THAT
 SHALL BE CONSIDERED IN DETERMINING THE EXTENT AND
 METHOD OF FIRE PROTECTION REQUIRED FOR INDUCED-DRAFT
 AND NATURAL-DRAFT WATER-COOLING TOWERS:
 (1) IMPORTANCE TO CONTINUITY OF OPERATION
 (2)*SIZE AND CONSTRUCTION OF TOWER
 (3) TYPE OF TOWER
 (4) LOCATION OF TOWER
 (5) WATER SUPPLY
 (6) VALUE OF TOWER
 (7) CLIMATE
 (8)*WATER DELIVERY TIME
 (9) ENVIRONMENT
 (10) ROOFTOP TOWERS
 (11) LIMITED ACCESS
 (12) MATERIALS OF CONSTRUCTION (SEE SECTION 4.1)
 4.3 COMBUSTIBLE EXTERIOR SURFACES. WATER-COOLING TOWERS
 WITH COMBUSTIBLE EXTERIOR SURFACES, INCLUDING THE DECK,
 DISTRIBUTION BASINS, AND SO FORTH, SHALL BE LOCATED AT
 LEAST 100 FT (30.5 M) FROM THE FOLLOWING HAZARDS:
 (1) STRUCTURES OR PROCESSES THAT EMIT SPARKS OR FLYING
 BRANDS UNDER ORDINARY CIRCUMSTANCES, SUCH AS CHIMNEYS,
 INCINERATORS, FLARE STACKS, OR COB BURNERS
 (2) MATERIALS OR PROCESSES OF SEVERE FIRE HAZARD, SUCH
 AS PETROLEUM PROCESSING AND STORAGE TANKS, EXPLOSIVES
 MANUFACTURING OR STORAGE, AND PETROLEUM PRODUCT
 PIPELINES AND PUMPING STATIONS
 4.4 COMBUSTIBLE SURFACES WITH FIXED PROTECTION. TOWERS
 WITH COMBUSTIBLE EXTERIOR SURFACES THAT ARE PROVIDED
 WITH FIXED EXPOSURE PROTECTION IN ACCORDANCE WITH
 5.2.10 SHALL BE PERMITTED TO BE LOCATED CLOSER THAN 100
 FT (30.5 M) FROM THE HAZARDS
 LISTED IN SECTION 4.3.
 4.5 NONCOMBUSTIBLE EXTERIOR SURFACES. TOWERS WITH
 NONCOMBUSTIBLE EXTERIOR SURFACES SHALL BE LOCATED 40 FT
 (12 M) OR MORE FROM THE HAZARDS LISTED IN SECTION 4.3.
 4.6 NONCOMBUSTIBLE SURFACES WITH FIXED PROTECTION.
 TOWERS WITH NONCOMBUSTIBLE EXTERIOR SURFACES THAT ARE
 PROVIDED WITH FIXED INTERIOR FIRE PROTECTION INSTALLED
 IN ACCORDANCE WITH CHAPTER 5 SHALL BE PERMITTED TO BE
 LOCATED CLOSER THAN 40 FT (12 M) FROM THE HAZARDS
 LISTED IN SECTION 4.3.
 4.7 COMBUSTIBLE TOWERS ON BUILDING ROOFS. COMBUSTIBLE
 WATER-COOLING TOWERS LOCATED ON BUILDING ROOFS OR OTHER
 LOCATIONS TO WHICH ACCESS FOR MANUAL FIRE FIGHTING IS
 RESTRICTED OR DIFFICULT SHALL BE PROVIDED WITH A
 PROTECTION SYSTEM IN ACCORDANCE WITH CHAPTER 5.
  
  
  
 3) PROVIDE MANUFACTURES SPECIFICATION / PRODUCT SHEETS,
 INDICATING COMPLIANCE WITH THE NONCOMBUSTIBLE MATERIALS
 NOTED ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-11-16 Cont ID  
Sent By pleduc Date 2016-11-16 Time   Rev Time 0.00
Received By pleduc Date 2016-11-16 Time 12:53 Sent To B
Notes
2016-11-16 13:12:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INNSUFFICIENT DETAIL PROVIDING FOR THE
 COMPLIANCE OF THE REQUIRMENTS OF NFPA FIRE CODES.
  
  
  
 2) PLEASE PROVIDE DETAILED INFOMATION INDICATING
 COMPLIANCE WITH NFPA 780 - LIGHTNING PROTECTION
 SYSTEMS.
  
  
  
 3) PLEASE PROVIDE DETAILED INFORMATION INDICATING
 COMPLIANCE WITH NFPA 214 - WATER-COOLING TOWERS
  
 INCLUDING, BUT NO LIMITED TO:
  
 CHAPTER 4 LOCATION OF WATER-COOLING TOWERS
 4.1 CONSTRUCTION MATERIALS OF WATER-COOLING TOWERS.
 4.1.1 WHERE THE COOLING TOWER?S STRUCTURE, FAN,
 DISTRIBUTION SYSTEM, LOUVERS, AND FILL AND DRIFT
 ELIMINATOR MATERIALS ARE ALL OF NONCOMBUSTIBLE
 MATERIALS, A FIRE PROTECTION SYSTEM SHALL NOT BE
 REQUIRED.
 4.1.2 IF ANY OF THE CONSTRUCTION MATERIALS ARE
 COMBUSTIBLE AND THE FACTORS IN SECTION 4.2 NECESSITATE
 IT, FIRE PROTECTION SHALL BE PROVIDED IN ACCORDANCE
 WITH CHAPTER 5, AND TOWERS SHALL BE LOCATED IN
 ACCORDANCE WITH CHAPTER 4.
 4.2* FIRE RISK ANALYSIS. A FIRE RISK ANALYSIS SHALL BE
 CONDUCTED. THE FOLLOWING ARE SOME OF THE FACTORS THAT
 SHALL BE CONSIDERED IN DETERMINING THE EXTENT AND
 METHOD OF FIRE PROTECTION REQUIRED FOR INDUCED-DRAFT
 AND NATURAL-DRAFT WATER-COOLING TOWERS:
 (1) IMPORTANCE TO CONTINUITY OF OPERATION
 (2)*SIZE AND CONSTRUCTION OF TOWER
 (3) TYPE OF TOWER
 (4) LOCATION OF TOWER
 (5) WATER SUPPLY
 (6) VALUE OF TOWER
 (7) CLIMATE
 (8)*WATER DELIVERY TIME
 (9) ENVIRONMENT
 (10) ROOFTOP TOWERS
 (11) LIMITED ACCESS
 (12) MATERIALS OF CONSTRUCTION (SEE SECTION 4.1)
 4.3 COMBUSTIBLE EXTERIOR SURFACES. WATER-COOLING TOWERS
 WITH COMBUSTIBLE EXTERIOR SURFACES, INCLUDING THE DECK,
 DISTRIBUTION BASINS, AND SO FORTH, SHALL BE LOCATED AT
 LEAST 100 FT (30.5 M) FROM THE FOLLOWING HAZARDS:
 (1) STRUCTURES OR PROCESSES THAT EMIT SPARKS OR FLYING
 BRANDS UNDER ORDINARY CIRCUMSTANCES, SUCH AS CHIMNEYS,
 INCINERATORS, FLARE STACKS, OR COB BURNERS
 (2) MATERIALS OR PROCESSES OF SEVERE FIRE HAZARD, SUCH
 AS PETROLEUM PROCESSING AND STORAGE TANKS, EXPLOSIVES
 MANUFACTURING OR STORAGE, AND PETROLEUM PRODUCT
 PIPELINES AND PUMPING STATIONS
 4.4 COMBUSTIBLE SURFACES WITH FIXED PROTECTION. TOWERS
 WITH COMBUSTIBLE EXTERIOR SURFACES THAT ARE PROVIDED
 WITH FIXED EXPOSURE PROTECTION IN ACCORDANCE WITH
 5.2.10 SHALL BE PERMITTED TO BE LOCATED CLOSER THAN 100
 FT (30.5 M) FROM THE HAZARDS
 LISTED IN SECTION 4.3.
 4.5 NONCOMBUSTIBLE EXTERIOR SURFACES. TOWERS WITH
 NONCOMBUSTIBLE EXTERIOR SURFACES SHALL BE LOCATED 40 FT
 (12 M) OR MORE FROM THE HAZARDS LISTED IN SECTION 4.3.
 4.6 NONCOMBUSTIBLE SURFACES WITH FIXED PROTECTION.
 TOWERS WITH NONCOMBUSTIBLE EXTERIOR SURFACES THAT ARE
 PROVIDED WITH FIXED INTERIOR FIRE PROTECTION INSTALLED
 IN ACCORDANCE WITH CHAPTER 5 SHALL BE PERMITTED TO BE
 LOCATED CLOSER THAN 40 FT (12 M) FROM THE HAZARDS
 LISTED IN SECTION 4.3.
 4.7 COMBUSTIBLE TOWERS ON BUILDING ROOFS. COMBUSTIBLE
 WATER-COOLING TOWERS LOCATED ON BUILDING ROOFS OR OTHER
 LOCATIONS TO WHICH ACCESS FOR MANUAL FIRE FIGHTING IS
 RESTRICTED OR DIFFICULT SHALL BE PROVIDED WITH A
 PROTECTION SYSTEM IN ACCORDANCE WITH CHAPTER 5.
  
  
  
 4) PROVIDE MANUFACTURES SPECIFICATION / PRODUCTS SHEETS
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-16 Cont ID  
Sent By cthroop Date 2016-12-16 Time 15:17 Rev Time 0.00
Received By cthroop Date 2016-12-07 Time 14:11 Sent To  
Notes
2016-12-07 14:11:21B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-01 Cont ID  
Sent By cthroop Date 2016-12-01 Time 11:17 Rev Time 0.00
Received By cthroop Date 2016-11-03 Time 11:17 Sent To  
Notes
2016-11-07 11:17:43SENT TO CHRIS COLE DESK 11/7/16.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-16 Cont ID  
Sent By ccole Date 2016-12-16 Time 14:10 Rev Time 0.00
Received By ccole Date 2016-12-16 Time 14:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-08 Cont ID  
Sent By ccole Date 2016-11-08 Time 10:13 Rev Time 0.00
Received By ccole Date 2016-11-08 Time 06:52 Sent To  
Notes
2016-11-08 10:50:101ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110138
 11/8/16
  
 1) PLEASE PROVIDE A COVER SHEET AND PLAN INDEX FOR THE
 PROPOSED PROJECT- SECTION 107.1 WPB AMENDMENTS TO THE
 FBC.
  
 2) DESIGN CRITERIA: PROVIDE A LIST OF CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT- SECTION
 107.1.
  
 3) SYSTEM COMMISSIONING IS REQUIRED FOR THE NEW COOLING
 TOWERS AND OUTSIDE AIR UNITS IN COMPLIANCE WITH SECTION
 C408.2 FBC-14 ENERGY CONSERVATION. PLEASE PROVIDE ON
 THE PLAN OR IN DOCUMENT FORM AN OUTLINE OF THE
 COMMISSIONING PLAN AND PROCEDURES AS INDICATED IN
 SECTION C408.2.1.
  
 4) INDICATE THE TYPE AND THICKNESS OF WATER PIPING
 INSULATION, AND SUBMIT SPECS FOR BOTH THE PVC PIPING
 AND THE INSULATION.
  
 5) PROVIDE A BACKFLOW PREVENTER FOR THE 1" MAKE UP
 WATER PIPE- SECTION 608.1 FBC-14 PLUMBING.
  
 6) CLARIFY IF THE NEW MARLEY COOLING TOWERS HAVE FM
 APPROVAL- SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 7) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF
 SERVICE PLATFORMS AND LADDERS- SECTION 306.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  