Plan Review Details - Permit 16110097
Plan Review Stops For Permit 16110097
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2016-12-30 Cont ID  
Sent By shill Date 2016-12-30 Time 12:00 Rev Time 0.00
Received By shill Date 2016-12-30 Time 12:00 Sent To  
Notes
2017-01-31 13:34:33I PASSED THE ADDRESING FAILED STOP AND PUT A NOTE ON
 S.HILL DESK; ISSUED PERMIT RES
2016-12-30 12:02:49PLEASE HAVE THE PROPERTY MANAGER CONTACT MICHAEL ORIO
 REGARDING ADDRESS ASSIGNMENTS.
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET ? WEST PALM BEACH ? FLORIDA 33401
 P: 561.494.1080
 [email protected]
  
 PLEASE NOTIFY [email protected] WHEN THIS HAS BEEN DONE.
 THIS ITEM SHOULD NOT DELAY PERMIT ISSUANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-01-03 Cont ID  
Sent By shill Date 2017-01-03 Time 18:10 Rev Time 0.00
Received By shill Date 2016-12-29 Time 17:59 Sent To  
Notes
2017-01-03 18:10:33PER ARCHITECT, THE MAIL ROOM IS EXISTING AND NO WORK IS
 PROPOSED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-14 Cont ID  
Sent By shill Date 2016-11-14 Time 08:01 Rev Time 0.00
Received By shill Date 2016-11-14 Time 07:41 Sent To  
Notes
2016-11-14 08:01:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. A SEPARATE PERMIT IS REQUIRED FOR EACH SUITE, FBC
 107. INCLUDE THE SUITE NUMBER ON EACH APPLICATION.
  
 2. REVISE PLAN TO INCLUDE OCCUPANT LOAD FOR EACH UNIT,
 FBC 5TH EDITION BUILDING 1004.
  
 3. REVISE PLAN TO INCLUDE SQUARE FOOT AREA FOR EACH
 UNIT, FBC 107.
  
 4. REVISE PLAN TO PROVIDE A ROOM DESIGNATION FOR THE
 UNLABELED AREA WHICH OPENS INTO THE ELEVATOR LOBBY, FBC
 107.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-12 Cont ID  
Sent By mvaldes Date 2017-01-12 Time 17:03 Rev Time 0.00
Received By mvaldes Date 2017-01-12 Time 15:59 Sent To  
Notes
2017-01-12 17:06:03PROVISO 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] APPLY ARC-FLASH HAZARD WARNING LABEL TO ELECTRICAL
 EQUIPMENT LIKELY TO BE WORKED ON WHILE ENERGIZED PER
 NEC 110.16.
  
 2] PULL BOX SHALL BE SIZED IN ACCORDANCE WITH NEC
 314.28.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-09 Cont ID  
Sent By mvaldes Date 2016-11-09 Time 10:23 Rev Time 0.00
Received By mvaldes Date 2016-11-09 Time 08:53 Sent To  
Notes
2016-11-09 10:42:53JOB PERMIT NUMBER: 16110097
 JOB ADDRESS: 400 S AUSTRALIAN AVE
 WEST PALM BEACH FLORIDA
 DATE: NOVEMBER 9, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] CLARIFY IF A NEW ELECTRIC DRINKING FOUNTAIN IS BEING
 INSTALLED? IF SO GFCI PROTECTION WILL BE REQUIRED PER
 NEC 422.52.
  
 2] PLEASE PROPERLY ADJUST CIRCUIT DESIGNATION LABELING
 TO MATCH PANEL "L". FBC-107
  
 3] PLEASE LABEL & IDENTIFY ALL ROOMS ON THE PLAN.
 FBC-107
  
 4] ALL WORK ASSOCIATED WITH LOW VOLTAGE SYSTEM WILL BE
 UNDER A SEPARATE PERMIT. A NOTE WILL SUFFICE.
  
 5] PROVIDE A RISER DIAGRAM TO INCLUDE THE RELOCATION OF
 PANEL "L" SHOW WIRE & CONDUIT SIZES. IF THE EXISTING
 PANEL CABINET WILL BE USED AS A J-BOX ALL PENETRATIONS
 MUST BE SEALED & THE ENCLOSURE SHALL BE MARKED WITH A
 WARNING LABEL IDENTIFYING THE DISCONNECTING MEANS PER
 NEC 312.8(3).
  
 6] ADD A GENERAL ELECTRICAL NOTE STATING THAT AT LEAST
 50 % OF ALL 125 V 15 & 20 AMP RECEPTACLES INSTALLED IN
 PRIVATE OR OPEN OFFICES INCLUDING MODULAR PARTITIONS
 SHALL BE CONTROLLED BY AN AUTOMATIC CONTROL DEVICE PER
 FBC-E SECTION C405.7.1 CONFORMANCE WITH ASHREA 90.1,
 8.4.2.
  
 7] SHOW LIGHTING CONTROLS IN OFFICE AREAS; PLEASE
 REFERENCE FBC-E SECTION C405 FOR LIGHTING REDUCTION,
 AUTOMATIC TIME SWITCHES, OCCUPANCY SENSOR & ETC.
  
 8] THE NEW LOCATION OF PANEL "L" MAY COMPROMISE THE
 FIRE RATING OF THE WALL. PLEASE PROVIDE CALRIFICATION
 IF THE INSTALLATION IS SURFACE MOUNTED OR SHOW
 COMPLIANCE WITH FBC-714 & NEC 300.21.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-12-21 Cont ID  
Sent By scaldero Date 2016-12-21 Time 11:24 Rev Time 0.00
Received By scaldero Date 2016-12-21 Time 11:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-07 Cont ID  
Sent By scaldero Date 2016-11-07 Time 10:23 Rev Time 0.00
Received By scaldero Date 2016-11-07 Time 10:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-30 Cont ID  
Sent By skennedy Date 2017-01-30 Time 13:31 Rev Time 0.00
Received By skennedy Date 2017-01-30 Time 13:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-12 Cont ID  
Sent By mvaldes Date 2017-01-12 Time 17:06 Rev Time 0.00
Received By mvaldes Date 2016-12-15 Time 09:33 Sent To  
Notes
2016-12-16 09:33:39B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-27 Cont ID  
Sent By tklarge Date 2016-11-27 Time 05:33 Rev Time 0.00
Received By tklarge Date 2016-11-02 Time 09:36 Sent To  
Notes
2016-11-04 09:37:06B12

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-01-30 Cont ID  
Sent By skennedy Date 2017-01-30 Time 13:30 Rev Time 0.00
Received By skennedy Date 2017-01-30 Time 13:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-28 Cont ID  
Sent By ccole Date 2016-12-28 Time 09:08 Rev Time 0.00
Received By ccole Date 2016-12-28 Time 09:08 Sent To  
Notes
2016-12-28 09:14:142ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16110097
 12/28/16
  
 1) PROVIDE THE DIMENSIONS OF THE RETURN AIR GRILLS AT
 THE MECHANICAL ROOM- 601.5
  
 2) SHOW THE LOCATION(S) OF THE REQUIRED SMOKE
 DETECTOR(S) IN THE MECHANICAL ROOM- SECTION 606.2.2
  
 3) SHOW THE LOCATION OF THE O/A DUCT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-09 Cont ID  
Sent By ccole Date 2016-11-09 Time 07:56 Rev Time 0.00
Received By ccole Date 2016-11-09 Time 07:54 Sent To  
Notes
2016-11-09 08:08:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110097
 11/9/16
  
 1) SHEET M-1: PLEASE IDENTIFY ALL THE ROOMS AND SPACES
 ON THE PLAN- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 2) M-1: PROVIDE THE MAKES AND MODELS AND COOLING AND
 HEATING CAPACITIES OF THE EXISTING AC SYSTEMS.
  
 3) M-1: CORRECT NOTE #2 INDICATING 1152 SF TO SQUARE
 INCHES.
  
 4) REFER TO SECTION 602.1: PLENUMS SHALL BE LIMITED TO
 ONE FIRE AREA. PROVIDE A DUCTED RETURN TO AC-2 FROM THE
 WEST TENANT SPACE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 15:31 Rev Time 0.00
Received By gjohnson Date 2017-01-12 Time 15:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-27 Cont ID  
Sent By tklarge Date 2016-11-27 Time 05:33 Rev Time 0.00
Received By tklarge Date 2016-11-27 Time 05:06 Sent To  
Notes
2016-11-27 05:27:201) SUBMIT A SANITARY AND WATER RISER FOR BOTH BREAK
 ROOM SINKS. THE PLUMBING SHEET SHOWS THE DISCHARGE LINE
 FROM THE SUMP TANK BUT WHERE ARE THE LINES FROM THE TWO
 SINKS THAT ARE DISCHARGING INTO THE TANK? SHOW THE SIZE
 OF EACH LINE FROM THE FIXTURES INTO THE TANK.WPB AMEND.
 TO FBC SEC. 107.3.5.3.
 2) THE SANITARY CONNNECTION FROM THE SUMP TANK TO THE
 EXISTING BUILDING DRAINAGE SYSTEM SHALL COMPLY WITH
 2014 FBC-PLUMBING SEC.712.3.5.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  