Plan Review Details - Permit 16110014
Plan Review Stops For Permit 16110014
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-03 Cont ID  
Sent By pleduc Date 2016-11-03 Time   Rev Time 0.00
Received By pleduc Date 2016-11-03 Time 10:59 Sent To M
Notes
2016-11-03 11:08:32THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13.
  
 24.2 ACCEPTANCE REQUIREMENTS.
 24.2.1* HYDROSTATIC TESTS.
  
 24.2.1.4 MODIFICATIONS AFFECTING 20 OR FEWER SPRINKLERS
 SHALL NOT REQUIRE TESTING IN EXCESS OF SYSTEM WORKING
 PRESSURE.
  
 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS
 RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF
 SYSTEM WORKING PRESSURE.
  
  
  
 2) PLEASE ENSURE THAT FIRE PUMP TEST PRESSURES ARE
 CALCULATED FOR WORKING PRESSURE.
  
 24.2.1.2 PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO
 SYSTEM WORKING PRESSURES IN EXCESS OF 150 PSI (10.4
 BAR) SHALL BE TESTED AS DESCRIBED IN 24.2.1.1, AT A
 PRESSURE OF 50 PSI (3.5 BAR) IN EXCESS OF SYSTEM
 WORKING PRESSURE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-16 Cont ID  
Sent By ccole Date 2016-11-16 Time 12:07 Rev Time 0.00
Received By ccole Date 2016-11-01 Time 14:28 Sent To  
Notes
2016-11-01 14:28:44ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-11-16 Cont ID  
Sent By ccole Date 2016-11-16 Time 12:07 Rev Time 0.00
Received By ccole Date 2016-11-16 Time 12:07 Sent To  
Notes
***NONE***