2016-11-01 14:49:10 | REVISION ROUTED TO HMOSER |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2017-05-10 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2017-05-10 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-05-10 |
Time |
13:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-11-03 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2016-11-03 |
Time |
17:02 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-11-03 |
Time |
16:58 |
Sent To |
|
|
Notes |
2016-11-03 17:04:46 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16110011 | | 11/3/16 | | | | 1) THE CORRIDOR CANNOT BE USED TO CONVEY RETURN AIR- | | SECTION 601.2. PROVIDE A DUCTED RETURN FROM THE STORAGE | | ROOM. | | | | 2) THE FLEX DUCT RETURNING 150 CFMS OF RETURN AIR FROM | | THE BAR AREA APPEARS TO BE MISLABELED AS 12" INSTEAD OF | | 8". | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|
|
|