Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-03 Cont ID  
Sent By hmoser Date 2016-11-03 Time 17:02 Rev Time 0.00
Received By ccole Date 2016-11-03 Time 16:58 Sent To  
Notes
2016-11-03 17:04:461ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110011
 11/3/16
  
 1) THE CORRIDOR CANNOT BE USED TO CONVEY RETURN AIR-
 SECTION 601.2. PROVIDE A DUCTED RETURN FROM THE STORAGE
 ROOM.
  
 2) THE FLEX DUCT RETURNING 150 CFMS OF RETURN AIR FROM
 THE BAR AREA APPEARS TO BE MISLABELED AS 12" INSTEAD OF
 8".
  