Plan Review Details - Permit 16100953
Plan Review Stops For Permit 16100953
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-27 Cont ID  
Sent By shill Date 2016-12-27 Time 13:13 Rev Time 0.00
Received By shill Date 2016-12-27 Time 12:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-04 Cont ID  
Sent By shill Date 2016-11-04 Time 10:03 Rev Time 0.00
Received By shill Date 2016-11-04 Time 10:03 Sent To  
Notes
2016-11-04 10:12:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PERMIT VALUE IS TOO LOW. VALUE IS TO INCLUDE ALL
 LABOR, MATERIALS, OVERHEAD, PROFIT, EVEN IF PROVIDED BY
 OTHERS, FBC 109.
  
 2. SEE FIRE COMMENTS. BUSINESS OCCUPANCY IS THE CORRECT
 CLASSIFICATION FOR FLORIDA BUILDING CODE COMPLIANCE, SO
 RATHER THAN CHANGE THE OCCUPANCY CLASSIFICATION PLEASE
 ADD THE CORRECT FIRE OCCUPANCY CLASSIFICATION, FBC
 303.1.2.
  
 3. OCCUPANT LOAD SHOULD BE DETERMINED IN ACCORDANCE
 WITH FBC TABLE 1004.1.2 UNLESS THE SEATING IS FIXED.
 REVISE PLAN TO STATE WHETHER THE SEATING IS FIXED OR
 NOT, AND IF NOT, CALCULATE THE OCCUPANT LOAD AS PER THE
 TABLE.
  
 4. ACCESSIBLE SEATING AND CHECK OUT COUNTER NOT SHOWN,
 REVISE PLAN TO PROVIDE APPLICABLE DETAILS, FBC 5TH
 EDITION ACCESSIBILITY 226, 227, 902, 904.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-20 Cont ID  
Sent By rlecky Date 2016-12-20 Time 13:28 Rev Time 0.00
Received By rlecky Date 2016-12-20 Time 13:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-11-09 Cont ID  
Sent By rlecky Date 2016-11-09 Time 14:08 Rev Time 0.00
Received By rlecky Date 2016-11-09 Time 13:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-12-12 Cont ID  
Sent By pleduc Date 2016-12-12 Time   Rev Time 0.00
Received By pleduc Date 2016-12-09 Time 16:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-11-03 Cont ID  
Sent By pleduc Date 2016-11-03 Time   Rev Time 0.00
Received By pleduc Date 2016-11-03 Time 11:42 Sent To  
Notes
2016-11-03 12:17:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET C - THE OCCUPANCY TYPE IS INDICATED AS B
 BUSINESS. IT APPEARS THAT THE PREVIOUS BUSINESS WAS A
 SALON.
  
 YOU ARE PROPOSING A RESTAURANT FOR LESS THAN 50
 PERSONS. ACCORDING TO THE FLORIDA FIRE PREVENTION CODE,
 NFPA 101, THIS PROPOSED OCCUPANCY IS MERCANTILE AND
 SHALL COMPLY WITH REQUIREMENTS OF CHAPTER 36, NEW
 MERCANTILE OCCUPANCIES.
  
 THIS PERMIT SHALL REFLECT THE APPLICABLE OCCUPANCY
 CHANGE. PLEASE PROVIDE A INDICATING NOTE.
  
  
  
 2) SHEET 1.0A - AN OCCUPANCY LOAD NOTE CALCULATION
 INDICATES A BUSINESS OCCUPANY TOTAL OF 11 PERSON.
  
 FOR NARRATIVE PURPOSES WITH THE PROPOSED 10 SEATS,
 THERE IS ONLY 1 PERSON LEFT TO WORK THE KITCHEN AND NO
 PERSONS AVAILABLE TO STAND AND ORDER. THE PROPOSED
 BUSINESS, IN MOST LIKELIHOOD, WOULD BE IN CONSTANT
 VIOLATION OF THE OCCUPANCY LOAD.
 ACCORDING TO THE MERCANTILE OCCUPANCY FACTOR OF NFPA
 101, CHAPTER 7, 7.3.1.2, ALLOWS FOR 30/SQ FT. AS A
 MIXED USE, THE KITCHEN COULD BE CALCULATED SEPARATELY
 AT 100/SQ. FT. THE REVISED OCCUPANCY LOAD CLACULATION
 MAY PROVIDE A MORE ACCURATE COUNT AND ALLOW FOR MORE IN
 THE KITCHEN AND MORE FOR ORDERING. THERE APPEARS TO
 AMPLE EXITS TO SUPPORT THIS CHANGE.
  
 PLEASE PROVIDE A REVISED LOAD CALCULATION AS
 APPLIICABLE.
  
  
  
 3) SHEET 1.0A - THE PROPOSED BATHROOM DOOR OPENS INTO
 THE EXIT PASSAGE WAY TO THE REAR EXIT.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
  
 PLEASE REVIEW AND PROVIDE CORRECTION PER THE
 REQUIREMENT.
  
  
  
 4) SHEET 1.1A - A PANNI GRILL AND CROCK POT ARE
 INDICATED ON THE KITCHEN EQUIPMENT PLAN.
  
 PER NFPA 101, CHAPTER 36,
  
 36.3.2.3 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING
 EQUIPMENT IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 PLEASE PROVIDE A BRIEF REVIEW INDICATING THE TYPE OF
 MENU THAT IS PROPOSED.
  
 ADDITIONALLY, PLEASE PROVIDE A NOTE INDICATING
 COMPLIANCE WITH THE ABOVE AND NO ADDITIONAL DEVICES
 WILL BE ADDED WITHOUT REVIEW, INSPECTION AND CONSENT OF
 THE FIRE MARSHALS OFFICE.
  
  
  
 5) SHEET 1.1A - A FIRE EXTINGUISHER IS NOT INDICATED
 WITHIN THE KITCHEN AREA.
  
 PER NFPA 101, CHAPTER 36
  
 36.3.5.3 PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED
 IN ALL MERCANTILE OCCUPANCIES IN ACCORDANCE WITH
 9.7.4.1.
  
 9.7.4 MANUAL EXTINGUISHING EQUIPMENT.
 9.7.4.1* WHERE REQUIRED BY THE PROVISIONS OF ANOTHER
 SECTION OF THIS CODE, PORTABLE FIRE EXTINGUISHERS SHALL
 BE SELECTED, INSTALLED, INSPECTED, AND MAINTAINED IN
 ACCORDANCE WITH NFPA 10, STANDARD FOR PORTABLE FIRE
 EXTINGUISHERS.
  
 NFPA 10
  
 6.1.3 PLACEMENT.
 6.1.3.1 FIRE EXTINGUISHERS SHALL BE CONSPICUOUSLY
 LOCATED WHERE THEY ARE READILY ACCESSIBLE AND
 IMMEDIATELY AVAILABLE IN THE EVENT OF FIRE.
 6.1.3.2 FIRE EXTINGUISHERS SHALL BE LOCATED ALONG
 NORMAL PATHS OF TRAVEL, INCLUDING EXITS FROM AREAS.
  
 PLEASE PROVIDE AN ADDITIONAL FIRE EXTINGUSIHER WITHIN
 THE KITCHEN AREA.
  
  
  
 6) SHEET 1.1A - A 2A, 10BC FIRE EXTIGUISHER IS
 INDICATED BY THE ENTRY EXIT DOORWAY.
  
 PER NFPA 10, TABLE 6.3.1.1 INDICATES THE TRAVEL
 DISTANCE TO A 10B FIRE EXTINGUISHERS IS 50 FT.
  
 PLEASE REVIEW THE DIMENSIONS TO THE EXTINGUISHERS TO
 VERIFY PROPER TRAVEL DISTANCE COMPLIANCE. THE
 EXTINGUISHERS MAY NEED TO BE RELOCATED TOWARDS THE
 CENTER OF THE SPACE.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-03 Cont ID  
Sent By ccole Date 2017-01-03 Time 07:29 Rev Time 0.00
Received By ccole Date 2016-12-30 Time 09:57 Sent To  
Notes
2016-12-30 09:57:58SENT TO CCOLE DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-28 Cont ID  
Sent By gjohnson Date 2016-12-28 Time 14:51 Rev Time 0.00
Received By gjohnson Date 2016-12-07 Time 15:54 Sent To  
Notes
2016-12-07 15:56:06B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-17 Cont ID  
Sent By gjohnson Date 2016-11-17 Time 17:31 Rev Time 0.00
Received By gjohnson Date 2016-10-31 Time 13:25 Sent To  
Notes
2016-11-01 13:25:53B16

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-01-03 Cont ID  
Sent By ccole Date 2017-01-03 Time 07:21 Rev Time 0.00
Received By ccole Date 2017-01-03 Time 07:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-13 Cont ID  
Sent By ccole Date 2016-12-13 Time 15:14 Rev Time 0.00
Received By ccole Date 2016-12-13 Time 15:13 Sent To  
Notes
2016-12-13 15:22:262ND REVIEW FBC-2014 MECHANICAL
 PERMIT 316100953
 12/13/16
  
 1) A NEW AC SYSTEM IS SPECIFIED ON THE PLAN: A) CORRECT
 THE NOTE INDICATING "EX AHU". B) PROVIDE THE SEER OF
 THE SYSTEM IN THE SCHEDULE AND THE CORRECT SUPPLY CFMS
 FOR THE 4-TON UNIT.
  
 2) THE 0.7CFM PER SQ. FT. LISTED ON THE O/A CALCULATION
 IS AN EXHAUST RATE, PLEASE CORRECT IF NO EXHAUST IS
 BEING PROVIDED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-03 Cont ID  
Sent By ccole Date 2016-11-03 Time 14:52 Rev Time 0.00
Received By ccole Date 2016-11-03 Time 14:52 Sent To  
Notes
2016-11-03 15:06:551ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING.
 PERMIT #16100953
 11/3/16
  
 1) THE PROPOSED CAFE IS A CHANGE OF OCCUPANCY FROM THE
 PREVIOUS HAIR SALON AS DEFINED IN SECTION 202 FBC-14
 EXISTING BUILDING. COMPLIANCE WITH THE CURRENT ENERGY
 CODE IS REQUIRED PER SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION. SEE SECTION C401.2 FOR COMPLIANCE PATH
 OPTIONS.
  
 2) SHEET 3.1M: PROVIDE THE MAKE AND MODEL OF THE
 EXISTING AC SYSTEM AND THE COOLING AND HEATING
 CAPACITIES.
  
 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 4) KITCHEN EXHAUST IS REQUIRED AT A RATE OF 0.7 CFMS
 PER SQ. FT. IN ACCORDANCE WITH TABLE 403.3 FBC-14
 MECHANICAL- PROVIDE DETAILS ON THE PLAN.
  
 5) IT APPEARS THAT NO AIR IS BEING SUPPLIED TO THE
 CORRIDOR. HOW IS THAT AREA TO BE VENTILATED?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-12-28 Cont ID  
Sent By gjohnson Date 2016-12-28 Time 14:51 Rev Time 0.00
Received By gjohnson Date 2016-12-28 Time 14:51 Sent To  
Notes
2016-12-28 14:19:39!!PLUMBING PROVISO:!!
  
 1. PROVIDE MANUFACTURE SIZING CALCULATIONS FOR GREASE
 INTERCEPTOR ON JOBSITE FOR FIRST ROUGH INSPECTION
 FAILURE TO PROVIDE SIZING CALCULATIONS WILL RESULT IN A
 FAILED INSPECTION AND REINSPECTION FEE.
 PER WPB AMEND TO FBC 107.2.1
  
 2. NEW SANITARY PIPING SHALL CONNECT TO BUILDING DRAIN
 DOWN STEAM OF BATHROOM GROUP. PER FBC PL 912.1

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-17 Cont ID  
Sent By gjohnson Date 2016-11-17 Time 16:53 Rev Time 0.00
Received By gjohnson Date 2016-11-15 Time 15:38 Sent To  
Notes
2016-11-17 17:31:181ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE 1 COMPARTMENT SINK SHALL DRAIN INTO THE GREASE
 INTERCEPTOR.PER FBC PL 1003.1
  
 2. PROVIDE WATER RISER. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 3. LAVATORY IN PUBLIC BATHROOM REQUIRE TEMPERED WATER.
 PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 4. BACKFLOW DEVICE REQUIRED ON ICE MACHINE COFFEE MAKER
 ANY APPLIANCE CONNECTED TO WATER. PER FBC PL 608.16.10
 COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS.
 THE WATER SUPPLY CONNECTION TO COFFEE MACHINES AND
 NONCARBONATED BEVERAGE DISPENSERS SHALL BE PROTECTED
 AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO
 ASSE 1022 OR BY AN AIR GAP.608.3 DEVICES,
 APPURTENANCES, APPLIANCES AND APPARATUS.
 DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS
 INTENDED TO SERVE SOME SPECIAL FUNCTION, SUCH AS
 STERILIZATION, DISTILLATION, PROCESSING, COOLING, OR
 STORAGE OF ICE OR FOODS, AND THAT CONNECT TO THE WATER
 SUPPLY SYSTEM, SHALL BE PROVIDED WITH PROTECTION
 AGAINST BACKFLOW AND CONTAMINATION OF THE WATER SUPPLY
 SYSTEM. WATER PUMPS, FILTERS, SOFTENERS, TANKS AND
 OTHER APPLIANCES AND DEVICES THAT HANDLE OR TREAT
 POTABLE WATER SHALL BE PROTECTED AGAINST CONTAMINATION.
  
 5. ON THE COVER SHEET IN THE SCOPE OF WORK UNDER
 PLUMBING IT CALLS OUT A 35GPM ON SHT.3.0P IT CALLS OUT
 A 25 GPM PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 6. PROVIDE MANUFACTURE SIZING CALCULATION FOR GREASE
 INTERCEPTOR. PERPER WPB AMEND TO FBC 107.2.1
  
 7.SHT. 1.0A ENLARGE ACCESSIBILITY DETAIL IT IS
 DIFFICULT TO READ. WPB AMEND TO FBC 107.2.1.4 QUALITY
 OF BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF
 FLORIDA STATUTES.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2016-11-08 Cont ID  
Sent By ajones Date 2016-11-08 Time 12:26 Rev Time 0.00
Received By ajones Date 2016-11-08 Time 12:26 Sent To  
Notes
***NONE***