Plan Review Details - Permit 16100950
Plan Review Stops For Permit 16100950
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-02 Cont ID  
Sent By pleduc Date 2016-11-02 Time   Rev Time 0.00
Received By pleduc Date 2016-11-02 Time 15:47 Sent To M
Notes
2016-11-02 15:54:56THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13
  
 24.2 ACCEPTANCE REQUIREMENTS.
 24.2.1* HYDROSTATIC TESTS.
  
 24.2.1.4 MODIFICATIONS AFFECTING 20 OR FEWER SPRINKLERS
 SHALL NOT REQUIRE TESTING IN EXCESS OF SYSTEM WORKING
 PRESSURE.
  
 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS
 RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF
 SYSTEM WORKING PRESSURE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-07 Cont ID  
Sent By ccole Date 2016-11-07 Time 09:00 Rev Time 0.00
Received By ccole Date 2016-10-31 Time 08:47 Sent To  
Notes
2016-11-01 08:48:08ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-11-07 Cont ID  
Sent By ccole Date 2016-11-07 Time 09:00 Rev Time 0.00
Received By ccole Date 2016-11-07 Time 09:00 Sent To  
Notes
2016-11-07 09:03:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100950
 11/7/16
  
 1) THE PLANS SHALL BEAR THE SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  