Plan Review Details - Permit 16100919
Plan Review Stops For Permit 16100919
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-01 Cont ID  
Sent By pleduc Date 2016-11-01 Time   Rev Time 0.00
Received By pleduc Date 2016-11-01 Time 09:48 Sent To M
Notes
2016-11-01 09:59:10THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13.
  
 24.2 ACCEPTANCE REQUIREMENTS.
 24.2.1* HYDROSTATIC TESTS.
  
 24.2.1.4 MODIFICATIONS AFFECTING 20 OR FEWER SPRINKLERS
 SHALL NOT REQUIRE TESTING IN EXCESS OF SYSTEM WORKING
 PRESSURE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-22 Cont ID  
Sent By ccole Date 2016-11-22 Time 13:48 Rev Time 0.00
Received By ccole Date 2016-11-21 Time 14:43 Sent To  
Notes
2016-11-21 14:43:55CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-15 Cont ID  
Sent By ccole Date 2016-11-15 Time 15:11 Rev Time 0.00
Received By ccole Date 2016-10-28 Time 09:17 Sent To  
Notes
2016-10-31 09:17:25ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-11-22 Cont ID  
Sent By ccole Date 2016-11-22 Time 13:48 Rev Time 0.00
Received By ccole Date 2016-11-22 Time 13:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-15 Cont ID  
Sent By ccole Date 2016-11-15 Time 15:11 Rev Time 0.00
Received By ccole Date 2016-11-15 Time 15:11 Sent To  
Notes
2016-11-15 15:11:321ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100919
 11/15/16
  
 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1
 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  