Plan Review Details - Permit 16100914
Plan Review Stops For Permit 16100914 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-11-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-11-18 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-11-18 |
Time |
10:14 |
Sent To |
E |
|
Notes |
2016-11-18 10:18:37 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER ? PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | | | 1. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE | | THEIR PRINTED NAME AND SIGNATURE ON THE PLAN PER FBC | | 107. | | 2. PLANS ARE INELIGIBLE. NO BUILDING REVIEW PERFORMED | | AT THIS TIME. | | | | FBC-107.1 GENERAL - FAC 61G1-16.004 - A TITLE BLOCK | | MUST APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN | | DRAWINGS AND SPECIFICATION IDENTIFICATION SHEETS THAT | | ARE REQUIRED TO BE SIGNED AND SEALED. THE TITLE BLOCK | | MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | (2) FIRM LICENSE NUMBER. | | (3) NAME OR IDENTIFICATION OF PROJECT. | | (4) DATE PREPARED. | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION | | NUMBER OF THE PERSON SEALING THE DOCUMENT. | | (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE | | REVISED. | | | | 61G1-16.001 ARCHITECT?S AND INTERIOR DESIGNER?S SEAL. | | EACH ARCHITECT AND INTERIOR DESIGNER SHALL ACQUIRE A | | SEAL WITH WHICH SHE OR HE SHALL IDENTIFY ALL PLANS, | | SPECIFICATIONS OR REPORTS PREPARED OR ISSUED BY HER OR | | HIM AND FILED FOR PUBLIC RECORD. THE SEAL SHALL BE | | CAPABLE OF LEAVING A PERMANENT INK REPRESENTATION OR | | OTHER FORM OF EMBOSSING OR OPAQUE AND PERMANENT | | IMPRESSION, WHICH ALSO MAY BE COMPUTER GENERATED | | IMPRESSIONS, ON THE SURFACE OF PRINTS OR OTHER | | DUPLICATIONS OF DRAWINGS, AND, AS APPROPRIATE, UPON | | SPECIFICATION PAGES, AND OTHER ARTICLES OF SERVICE. | | WHERE REQUIRED, ELECTRONIC FILES MAY BE SEALED IN | | ACCORDANCE WITH RULE 61G1-16.005, F.A.C. | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | DESIGN. (SEE ALSO SECTION 107.3.5). | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-11-21 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-11-21 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-11-21 |
Time |
14:48 |
Sent To |
P |
|
Notes |
2016-11-21 14:57:36 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING | | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | RECORDS MANAGEMENT. PLANS ARE INLEGIBLE. | | | | 2] THE SCOPE OF WORK, JOB ADDRESS, & APPLICABLE CODE | | SHALL APPEAR ON THE DRAWINGS ALONG WITH THE NAME & | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. FBC | | 107.2.1 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-11-23 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2016-11-23 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2016-10-28 |
Time |
13:43 |
Sent To |
|
|
Notes |
2016-11-01 13:43:21 | GIVEN TO SKENNEDY |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-11-22 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2016-11-22 |
Time |
18:23 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2016-11-22 |
Time |
18:06 |
Sent To |
|
|
Notes |
2016-11-22 18:13:11 | MECHANICAL | | 1ST REVIEW | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | | | (1) THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE | | THEIR PRINTED NAME AND SIGNATURE ON THE PLAN PER FBC | | 107. | | (2) PLANS ARE INELIGABLE. NO MECHANICAL REVIEW DONE AT | | THIS TIME. | | | | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH | | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE | | MEDIUM. THE BUILDING OFFICIAL MAY | | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS | | FOR PLANS AND SPECIFICATIONS, IN | | ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION | | PROGRAM. THIS POLICY MAY INCLUDE SUCH | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | OTHER ITEMS RELATED TO RECORDS | | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH | | THE ARCHIVE REQUIREMENTS OF | | FLORIDA STATUTES. | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-11-22 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-11-22 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-11-22 |
Time |
16:55 |
Sent To |
|
|
Notes |
2016-11-22 16:55:08 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | | | 1. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE | | THEIR PRINTED NAME AND SIGNATURE ON THE PLAN PER FBC | | 107. | | 2. PLANS ARE INELIGIBLE. NO PLUMBING REVIEW PERFORMED | | AT THIS TIME. | | | | FBC-107.1 GENERAL - FAC 61G1-16.004 - A TITLE BLOCK | | MUST APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN | | DRAWINGS AND SPECIFICATION IDENTIFICATION SHEETS THAT | | ARE REQUIRED TO BE SIGNED AND SEALED. THE TITLE BLOCK | | MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | (2) FIRM LICENSE NUMBER. | | (3) NAME OR IDENTIFICATION OF PROJECT. | | (4) DATE PREPARED. | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION | | NUMBER OF THE PERSON SEALING THE DOCUMENT. | | (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE | | REVISED. | | | | 61G1-16.001 ARCHITECT?S AND INTERIOR DESIGNER?S SEAL. | | EACH ARCHITECT AND INTERIOR DESIGNER SHALL ACQUIRE A | | SEAL WITH WHICH SHE OR HE SHALL IDENTIFY ALL PLANS, | | SPECIFICATIONS OR REPORTS PREPARED OR ISSUED BY HER OR | | HIM AND FILED FOR PUBLIC RECORD. THE SEAL SHALL BE | | CAPABLE OF LEAVING A PERMANENT INK REPRESENTATION OR | | OTHER FORM OF EMBOSSING OR OPAQUE AND PERMANENT | | IMPRESSION, WHICH ALSO MAY BE COMPUTER GENERATED | | IMPRESSIONS, ON THE SURFACE OF PRINTS OR OTHER | | DUPLICATIONS OF DRAWINGS, AND, AS APPROPRIATE, UPON | | SPECIFICATION PAGES, AND OTHER ARTICLES OF SERVICE. | | WHERE REQUIRED, ELECTRONIC FILES MAY BE SEALED IN | | ACCORDANCE WITH RULE 61G1-16.005, F.A.C. | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | DESIGN. (SEE ALSO SECTION 107.3.5). | | |
|
|
|