Plan Review Details - Permit 16100893
Plan Review Stops For Permit 16100893 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2017-12-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-12-08 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-12-08 |
Time |
10:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2017-09-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-09-15 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-09-14 |
Time |
16:46 |
Sent To |
|
|
Notes |
2017-09-15 09:24:59 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 3RD REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | THE FOLLOWING COMMENTS FROM 1ST REVIEW HAVE NOT BEEN | | ADDRESSED | | | | 1. VALUE. | | 2. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS. | | | | NEW COMMENT - 3RD REVIEW | | | | 3. ENERGY PERFORMANCE LEVEL FORM TO BE SIGNED BY | | BUILDER. | | 4. ENERGY SUBMITTAL FORM 405 TO BE SIGNED BY | | OWNER/AGENT. | | | | THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF | | WORK. | | THE PERMIT VALUATION AND PERMIT FEE MUST BE | | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED | | CONTRACTOR WOULD PROVIDE. | | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE | | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT | | RENTAL TO VERIFY VALUE. | | | | CITY OF WPB CHPT. 1 - VALUE | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | DATA OF NATIONAL CONSTRUCTION | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | BUILDING OFFICIAL. | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED AND MARK VOID. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2017-02-16 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-02-16 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-02-16 |
Time |
13:58 |
Sent To |
|
|
Notes |
2017-02-16 14:21:48 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 2ND REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. VALUE APPEARS LOW FOR PROOSED SCOPE OF WORK. | | | | THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF | | WORK. | | THE PERMIT VALUATION AND PERMIT FEE MUST BE | | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED | | CONTRACTOR WOULD PROVIDE. | | PLEASE INCREASE THE VALUATION ACCORDINGLY. | | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE | | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT | | RENTAL TO VERIFY VALUE. | | | | CITY OF WPB CHPT. 1 - VALUE | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | DATA OF NATIONAL CONSTRUCTION | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | BUILDING OFFICIAL. | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-12-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-12-09 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-12-09 |
Time |
12:17 |
Sent To |
|
|
Notes |
2016-12-09 13:14:52 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 1ST REVIEW | | RESULTS: DENIED | | | | 1. VALUE APPEARS LOW. | | 2. PROVIDE ENERGY SUBMITTAL. | | 3. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS. | | 4. SPECIFY INSULATION R VALUE FOR NEW ROOFS. | | | | VALUATION ? BASED ON THE MARSHALL-SWIFT VALUATION | | SERVICE YOUR STATED VALUE APPEARS LOW. | | THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF | | WORK. | | THE PERMIT VALUATION AND PERMIT FEE MUST BE | | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED | | CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE VALUATION | | ACCORDINGLY. | | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE | | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT | | RENTAL TO VERIFY VALUE. | | | | CITY OF WPB CHPT. 1 | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | DATA OF NATIONAL CONSTRUCTION | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | BUILDING OFFICIAL. | | | | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY | | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW, AND | | DOOR SUBMITTALS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED AND MARK VOID. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2017-08-29 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-08-29 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-08-29 |
Time |
11:31 |
Sent To |
|
|
Notes |
2017-08-29 11:31:34 | REVIEWED PER COMMENTS ONLY. JP |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2017-02-08 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2017-02-08 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2017-02-08 |
Time |
10:19 |
Sent To |
|
|
Notes |
2017-02-08 10:23:28 | 2ND ELECTRICAL REVIEW | | | | PRIOR COMMENT REGARDING FIRE ALARM SYSTEM NOT ADDRESSED | | PER FIRE COMMENTS. | | | | NEW COMMENTS. | | | | PER NEW ELECTRICAL SERVICE SHOWN, MAIN 1 OF 6, 2 OF 6 | | ETC MUST BE LABELED ON RISER DIAGRAM. AN AIC | | CALCULATION WAS NOT SUBMITTED. FBC 107.3.5 | | | | V. PEREZ | | *6717 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-11-03 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-11-03 |
Time |
17:25 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-11-03 |
Time |
14:43 |
Sent To |
|
|
Notes |
2016-11-03 18:05:54 | JOB PERMIT NUMBER: 16100893 | | JOB ADDRESS: 522 43RD ST | | WEST PALM BEACH FLORIDA | | DATE: NOVEMBER 3, 2016 | | ELECTRICAL PLAN REVIEW COMMENTS | | | | - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC | | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA | | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH | | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. | | | | 1] THE APPLICABLE CODES IN EFFECT ARE NEC 2011, NFPA 72 | | (2010), NFPA 101 (2012). PLEASE CORRECT NOTE 1 | | ACCORDINGLY. | | | | 2] SHOW CIRCUIT DESIGNATION # ON THE FLOOR PLAN TO | | MATCH PANEL SCHEDULE. FBC-107 | | | | 3] SHOW ALL PANELBOARDS LOCATION ON THE FLOOR PLAN TO | | VERIFY WORK SPACE CLEARANCES. NEC 110.26 | | | | 4] AT LEAST 1 WALL SWITCHED CONTROLLED LIGHTING OUTLET | | SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE | | EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE | | LEVEL ACCESS PER NEC 210.70(A)(2). | | | | 5] ADD GFI SYMBOL TO RECEPTACLE BY THE RANGE IN THE | | KITCHEN COUNTER-TOP (RED-LINED ON PLANS), ALSO ADD GFI | | "WP/WR" SYMBOL TO RECEPTACLE OUTLETS INSTALLED | | OUTDOORS. NEC 210.8(A)(6), 210.8(A)(3) &, 406.9(B). | | | | 6] ALL AREAS SPECIFIED IN NEC 210.52 SHALL HAVE AFCI | | PROTECTION PER NEC 210.12(A). CORRECT ELECTRICAL NOTE | | 22. | | | | 7] ADD GENERAL ELECTRICAL NOTE FOR TAMPER RESISTANT | | RECEPTACLES IN ACCORDANCE WITH NEC 406.12. | | | | 8] ALL MEANS OF EGRESS STAIRWAYS IN COMMON AREAS WILL | | REQUIRE EXIT LIGHTS & EMERGENCY LIGHTS THROUGH-OUT THE | | EXIT DISCHARGE. EXTERIOR ILLUMINATION IS REQUIRED TO | | ILLUMINATE EGRESS PATH UNTIL PUBLIC WAY IS SAFELY | | REACHED. FBC 1011 & 1006 (SHOW COMPLIANCE). | | | | 9] EXIT & EMERGENCY LIGHTS SHALL BE FED AHEAD OF LOCAL | | LIGHTING AREA SERVED. NEC 700.12(F)(4) | | | | 10] FIRE MARSHALL SHALL DETERMINE IF A FIRE ALARM IS | | REQUIRED OR IF SINGLE STATION SMOKE ALARMS WILL SUFFICE | | ENOUGH FIRE PROTECTION. | | | | 11] EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL | | OVERCURRENT DEVICES, AS CONFIGURED ACCESSIBILITY IS | | LIMITED. PLEASE SEE NEC 240.24(B) | | | | 12] PROVIDE AIC CALCULATIONS TO VERIFY SHORT-CIRCUIT | | RATINGS OF ELECTRICAL EQUIPMENT. NEC 110.10 & 110.9 | | | | 13] CLARIFY RISER DIAGRAM FEEDER LAYOUT, EACH UNIT THAT | | WILL BE INDIVIDUALLY METERED SHALL HAVE ITS DEDICATED | | PANEL BOARD WITH ALL ASSOCIATED LOADS TERMINATING | | ACCORDINGLY. ELIMINATE PANELS "C1", "C2", "C3" TO | | COMPLY WITH NEC REQUIREMENTS & SHOW PANEL SCHEDULES | | WITH MATCHING FLOOR PLAN CIRCUITS. ADJUST RISER-DIAGRAM | | DETAIL TO REFLECT ALL CONDUIT & WIRE SIZES. FBC | | 107.3.5.3 | | | | - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER | | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES | | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER | | QUESTIONS, PLEASE DON?T HESITATE TO CONTACT ME | | DIRECTLY. | | | | 1ST REVIEW FBC 2014 5TH ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2017-11-09 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-11-09 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-11-09 |
Time |
10:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2017-08-14 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-08-14 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-08-14 |
Time |
10:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2017-02-09 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-02-09 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-02-09 |
Time |
10:37 |
Sent To |
|
|
Notes |
2017-02-09 10:44:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PREVIOUS COMMENTS WERE NOT ADDRESSED. | | | | PREVIOUS COMMENYS: | | | | 1) PLEASE PROVIDE THE OCCUPANCY CLASSFICATION PER THE | | FLORIDA FIRE PREVENTION CODE. | | | | ONE UNIT, # 5, HAS 6 BEDROOMS, A GAME ROOM, COMMON | | WASHER/DRYER ROOM AND APPEARS TO HAVE A POSSIBLE USE | | BEYOND A SINGLE FAMILY RESIDENCE. | | | | ADDITIONAL COMMENT: WILL THIS BUILDING BE USED AS A | | RECOVERY TYPE RESIDENCE ? IF SO, HOW MANY RESIDENTS ARE | | PROPOSED ? IT IS IMPERATIVE FOR THE LIFE SAFETY REVIEW | | TO HAVE DEFINITIVE OCCUPANCY CLASSIFICATION. | | | | | | | | | | 2) AS SUBMITTED THE CONSTRUCTION SHALL COMPLY WITH THE | | FLORIDA FIRE PREVENTION CODE, NFPA 101, CHAPTER 30, NEW | | APARTMENT BUILDINGS AND ALL APPLICABLE CODES. | | | | UNLESS OTHERWISE INDICATED SEPARATLY BY THE CORRECTION | | OF # 1 ABOVE, PLEASE PROVIDE AN APPLICABLE NOTE, | | | | ADDITIONAL COMMENT: IF IT WILL NOT BE A RECOVERY | | RESIDENCE AND IT IS NOT CONSIDERED A NEW APARTMENT, YOU | | MUST INDICATE AND ENSURE COMPLIANCE WITH EXISTING | | APARTMENT OCCUPANCCIES. | | | | | | | | 3) A FIRE SPRINKLER SYSTEM IS NOT INDICATED. PER NFPA | | 101, CHAPTER 30: | | | | 30.3.5 EXTINGUISHMENT REQUIREMENTS. | | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY | | AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM | | INSTALLED IN ACCORDANCE WITH 30.3.5.2. | | 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS | | INSTALLED, EITHER FOR TOTAL OR PARTIAL BUILDING | | COVERAGE, THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE | | WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 AND | | 30.3.5.4. IN BUILDINGS FOUR OR FEWER STORIES ABOVE | | GRADE PLANE, SYSTEMS IN ACCORDANCE WITH NFPA 13R, | | STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN | | LOW-RISE RESIDENTIAL OCCUPANCIES, SHALL BE PERMITTED. | | | | PLEASE PROVIDE FIRE SPRINKLER DRAWINGS OR A NARRATIVE | | IN COMPLIANCE WITH FS 61G - PER FLORIDA ADMINISTRATIVE | | CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING | | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE | | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS | | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD | | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM | | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP | | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED | | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. | | | | ADDITIONAL COMMENT: BASED ON THE OCCUPANCY | | CLASSIFICATION AND OCCUPANCY USE A FIRE SPRINKLER | | SYSTEM MAY STILL BE REQUIRED. PLEASE PROVIDE SPECIFIC | | INFORMATION AND ANSWERS. | | | | | | | | | | 4) A FIRE ALARM SYSTEM IN NOT INDICATED. PER NFPA 101, | | CHAPTER 30 & CHAPTER 9. | | | | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY | | AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM | | INSTALLED IN ACCORDANCE WITH 30.3.5.2. | | | | 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. | | 9.6.1* GENERAL. | | 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY | | WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS | | CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER | | SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE | | FLORIDA BUILDING CODE. | | | | | | ADDITIONAL COMMENT: BASED ON THE OCCUPANCY | | CLASSIFICATION AND OCCUPANCY USE A FIRE ALARM SYSTEM | | MAY STILL BE REQUIRED. IF IT IS A EXISTING APARTMENT | | OCCUPANCY CLASSIFICATION UNDER NFPA 101, CHAPTER 31, A | | FIRE ALARM IS NOT REQUIRED. PLEASE PROVIDE SPECIFIC | | INFORMATION AND ANSWERS. | | | | | | | | | | 5) PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED | | FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE | | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY | | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE | | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME | | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED | | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES | | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED | | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED | | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. | | A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE | | MARKED WITH THE LETTER "R". | | B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS | | SHALL BE MARKED WITH THE LETTER "F". | | C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF | | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". | | | | ADDITIONAL COMMENT: COMMENT NOT ADDRESSED. | | | | | | | | 6) THE PROPOSED LAUNDRY ROOM SHALL BE PROTECTED BY 1 - | | HOUR SEPARATION AND FIRE SPRINKLERS | | | | PER NFPA 101, CHAPTER 30, | | | | 30.3.2 PROTECTION FROM HAZARDS. | | 30.3.2.1 HAZARDOUS AREAS. ANY HAZARDOUS AREA SHALL BE | | PROTECTED IN ACCORDANCE WITH SECTION 8.7. | | 30.3.2.1.1 THE AREAS DESCRIBED IN TABLE 30.3.2.1.1 | | SHALL BE PROTECTED AS INDICATED. | | | | TABLE 30.3.2.1.1 LAUNDRIES 1 HOUR AND SPRINKLERS >100 | | FT2 (>9.3 M2) OUTSIDE OF DWELLING UNITS | | | | ADDITIONAL COMMENT: THE SAME CODE IS APPLICABLE TO | | EXISTING APARTMENTS. COMMENT NOT ADDRESSED. SECTION 8.7 | | HAS SPECIFIC LANGUAGE THAT NEEDS TO BE USED IN THE | | DESIGN OF THE LAUNDRY ROOM, NO WINDOWS, | | 8.7 SPECIAL HAZARD PROTECTION. | | 8.7.1 GENERAL. | | 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF | | HAZARD GREATER THAN THAT NORMAL TO THE GENERAL | | OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE | | PROVIDED BY ONE OF THE FOLLOWING MEANS: | | (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT | | WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN | | ACCORDANCE WITH SECTION 8.3. | | (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING | | SYSTEMS IN ACCORDANCE WITH SECTION 9.7 | | (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD | | IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11 | | THROUGH 43 | | | | 8.3 FIRE BARRIERS. | | 8.3.1 GENERAL. | | 8.3.1.1 FIRE BARRIERS USED TO PROVIDE ENCLOSURE, | | SUBDIVISION, OR PROTECTION UNDER THIS CODE SHALL BE | | CLASSIFIED IN ACCORDANCE WITH ONE OF THE FOLLOWING FIRE | | RESISTANCE RATINGS: | | (1) 3-HOUR FIRE RESISTANCE RATING | | (2) 2-HOUR FIRE RESISTANCE RATING | | (3) 1-HOUR FIRE RESISTANCE RATING | | (4)* ?-HOUR FIRE RESISTANCE RATING | | 8.3.1.2* FIRE BARRIERS SHALL COMPLY WITH ONE OF THE | | FOLLOWING: | | (1) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL | | TO OUTSIDE WALL OR FROM ONE FIRE BARRIER TO ANOTHER, OR | | A COMBINATION THEREOF, INCLUDING CONTINUITY THROUGH ALL | | CONCEALED SPACES, SUCH AS THOSE FOUND ABOVE A CEILING, | | INCLUDING INTERSTITIAL SPACES. | | (2) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL | | TO OUTSIDE WALL OR FROM ONE FIRE BARRIER TO ANOTHER, | | AND FROM THE FLOOR TO THE BOTTOM OF THE INTERSTITIAL | | SPACE, PROVIDED THAT THE CONSTRUCTION ASSEMBLY FORMING | | THE BOTTOM OF THE INTERSTITIAL SPACE HAS A FIRE | | RESISTANCE RATING NOT LESS THAN THAT OF THE FIRE | | BARRIER. | | | | THE DOORS, O & P, TO THE LAUNDRY ARE NOTED TO HOLLOW | | CORE, THERE ARE WINDOWS, AN EXIT STAIRWAY AND A WOOD | | WALL ABOVE THE LAUNDRY. ON THE OTHER SIDE THERE IS A | | WINDOW WITHIN 10 FT OF THE LAUNDRY THAT IS UNPROTECTED. | | | | PLEASE REVIEW, CLARIFY AND/OR CORRECT. | | | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | COMMENT REMAINS | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | COMMENT REMAINS | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2016-11-07 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-11-07 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-11-04 |
Time |
15:38 |
Sent To |
|
|
Notes |
2016-11-04 16:52:54 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) PLEASE PROVIDE THE OCCUPANCY CLASSFICATION PER THE | | FLORIDA FIRE PREVENTION CODE. | | | | ONE UNIT, # 5, HAS 6 BEDROOMS, A GAME ROOM, COMMON | | WASHER/DRYER ROOM AND APPEARS TO HAVE A POSSIBLE USE | | BEYOND A SINGLE FAMILY RESIDENCE. | | | | | | 2) AS SUBMITTED THE CONSTRUCTION SHALL COMPLY WITH THE | | FLORIDA FIRE PREVENTION CODE, NFPA 101, CHAPTER 30, NEW | | APARTMENT BUILDINGS AND ALL APPLICABLE CODES. | | | | UNLESS OTHERWISE INDICATED SEPARATLY BY THE CORRECTION | | OF # 1 ABOVE, PLEASE PROVIDE AN APPLICABLE NOTE, | | | | | | 3) A FIRE SPRINKLER SYSTEM IS NOT INDICATED. PER NFPA | | 101, CHAPTER 30: | | | | 30.3.5 EXTINGUISHMENT REQUIREMENTS. | | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY | | AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM | | INSTALLED IN ACCORDANCE WITH 30.3.5.2. | | 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS | | INSTALLED, EITHER FOR TOTAL OR PARTIAL BUILDING | | COVERAGE, THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE | | WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 AND | | 30.3.5.4. IN BUILDINGS FOUR OR FEWER STORIES ABOVE | | GRADE PLANE, SYSTEMS IN ACCORDANCE WITH NFPA 13R, | | STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN | | LOW-RISE RESIDENTIAL OCCUPANCIES, SHALL BE PERMITTED. | | | | PLEASE PROVIDE FIRE SPRINKLER DRAWINGS OR A NARRATIVE | | IN COMPLIANCE WITH FS 61G - PER FLORIDA ADMINISTRATIVE | | CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING | | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE | | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS | | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD | | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM | | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP | | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED | | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. | | | | | | | | 4) A FIRE ALARM SYSTEM IN NOT INDICATED. PER NFPA 101, | | CHAPTER 30 & CHAPTER 9. | | | | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY | | AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM | | INSTALLED IN ACCORDANCE WITH 30.3.5.2. | | | | 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. | | 9.6.1* GENERAL. | | 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY | | WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS | | CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER | | SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE | | FLORIDA BUILDING CODE. | | | | | | | | 5) PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED | | FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE | | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY | | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE | | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME | | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED | | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES | | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED | | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED | | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. | | A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE | | MARKED WITH THE LETTER "R". | | B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS | | SHALL BE MARKED WITH THE LETTER "F". | | C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF | | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". | | | | | | | | 6) THE PROPOSED LAUNDRY ROOM SHALL BE PROTECTED BY 1 - | | HOUR SEPARATION AND FIRE SPRINKLERS | | | | PER NFPA 101, CHAPTER 30, | | | | 30.3.2 PROTECTION FROM HAZARDS. | | 30.3.2.1 HAZARDOUS AREAS. ANY HAZARDOUS AREA SHALL BE | | PROTECTED IN ACCORDANCE WITH SECTION 8.7. | | 30.3.2.1.1 THE AREAS DESCRIBED IN TABLE 30.3.2.1.1 | | SHALL BE PROTECTED AS INDICATED. | | | | TABLE 30.3.2.1.1 LAUNDRIES 1 HOUR AND SPRINKLERS >100 | | FT2 (>9.3 M2) OUTSIDE OF DWELLING UNITS | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2017-12-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-12-08 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-11-07 |
Time |
15:57 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2017-09-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-09-15 |
Time |
09:18 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-08-04 |
Time |
15:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2017-02-15 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2017-02-15 |
Time |
18:17 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2017-02-01 |
Time |
10:30 |
Sent To |
|
|
Notes |
2017-02-15 18:15:37 | ROUTED TO GEORGE JOHNSON 2/15/2017 - JORGE V. | 2017-02-02 10:31:25 | B29 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-01-10 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-01-10 |
Time |
13:03 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-01-05 |
Time |
10:10 |
Sent To |
|
|
Notes |
2017-01-06 10:11:04 | RESUB ROUTED TO CTHROOP |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-12-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-12-09 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-10-28 |
Time |
10:16 |
Sent To |
|
|
Notes |
2016-12-08 18:04:22 | ROUTED TO CHRIS THROOP 12/8/2016 - JORGE V. | 2016-10-31 10:16:35 | R20 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2016-12-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-12-09 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-12-09 |
Time |
12:18 |
Sent To |
|
|
Notes |
2016-12-09 13:05:32 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 1ST REVIEW | | RESULTS: DENIED | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2017-11-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-11-29 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-11-29 |
Time |
15:39 |
Sent To |
|
|
Notes |
2017-11-29 16:16:06 | 4TH REVIEW FBC-2014 MECHANICAL | | PERMIT #16100893 | | 11/29/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE GENERAL CONTRACTOR ALEJANDRO RODRIGUEZ IS NOT A | | LICENSED AC OR MECHANICAL CONTRACTOR AND THEREFORE | | CANNOT DESIGN THE PLANS FOR THE PROPOSED PROJECT. | | PLEASE SEE SECTION 105.3.1.2 FBC-14 BUILDING WHICH | | PERMITS THE INSTALLING AC CONTRACTOR TO DESIGN THE | | PLANS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2017-09-07 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-09-07 |
Time |
12:37 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-09-06 |
Time |
11:29 |
Sent To |
|
|
Notes |
2017-09-07 12:50:07 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16100893 | | 9/7/16 | | | | PLAN REVIEW RESULTS: DENIED. | | | | COMMENTS FROM THE 2ND REVIEW STILL EXIST. I HAVE | | REPRINTED THEM BELOW THE 3RD REVIEW COMMENTS. PLEASE | | COMPLY WITH BOTH THE 2ND AND 3RD REVIEW COMMENTS. | | | | 1) M.1 & M.2: THE LAUNDRY ROOM (SYSTEM 7) IS NOT SHOWN | | ON THE PLANS OR INCLUDED IN THE SCHEDULE- SEE AC AND | | ENERGY CALCULATIONS. | | | | 2) THE ENERGY CALCULATION FORM R405-2014 MUST BE SIGNED | | BY THE OWNER/AGENT. | | | | 3) THE WIND LOAD DESIGN CRITERIA AND ENGINEERING FOR | | THE EXTERIOR CONDENSER AHOWN ON M.2 CANNOT BE PREPARED | | BY AN AC CONTRACTOR. PROVIDE ENGINEERED DESIGN BY A FL. | | LICENSED P.E., OR SUBMIT A FL. PRODUCT APPROVAL FOR TIE | | DOWN CLIPS WITH APPROVAL STAMP BY THE DESIGN | | PROFESSIONAL OF RECORD. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | 2ND REVIEW | | | | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL: 107.2 CONSTRUCTION DOCUMENTS: 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | FLORIDA ENERGY CODE FBC 2014 | | | | (1) SYSTEM #5 ON THE APPROVED PLANS DOES NOT MATCH THE | | HEAT LOAD CALCULATIONS DESIGN REQUIREMENTS. CHECK HEAT | | LOAD CALCULATIONS AND MAKE ALL REQUIRED CORRECTIONS. | | (2) FORM R405-2014 MUST BE COMPLETLY FILLED OUT WITH | | ALL OF THE REQUIRED INFORMATION AND SIGNATURES. SEE | | HIGHLIGHTED AREAS. ONE OF THE ENERGY CALCULATIONS IS | | MISSING PAGE 1 OF 7. | | (3) A CMC LICENSE CANNOT DESIGN CONDENSER TIE DOWNS. | | CONDENSER TIE DOWNS MUST BE ENGINEERED. PROVIDE | | ENGINEERED CONDENSER TIE DOWN DETAIL OR PROVIDE | | ENGINEER STAMPED PLANS. (SEE PROVISIONAL ON PLANS) | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2017-02-15 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2017-02-15 |
Time |
18:14 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2017-02-15 |
Time |
16:52 |
Sent To |
|
|
Notes |
2017-02-15 18:09:42 | 2ND REVIEW | | | | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | FLORIDA ENERGY CODE FBC 2014 | | | | (1) SYSTEM #5 ON THE APPROVED PLANS DOES NOT MATCH THE | | HEAT LOAD CALCULATIONS DESIGN REQUIREMENTS. CHECK HEAT | | LOAD CALCULATIONS AND MAKE ALL REQUIRED CORRECTIONS. | | (2) FORM R405-2014 MUST BE COMPLETLY FILLED OUT WITH | | ALL OF THE REQUIRED INFORMATION AND SIGNATURES. SEE | | HIGHLIGHTED AREAS. ONE OF THE ENERGY CALCULATIONS IS | | MISSING PAGE 1 OF 7. | | (3) A CMC LICENSE CANNOT DESIGN CONDENSER TIE DOWNS. | | CONDENSER TIE DOWNS MUST BE ENGINEERED. PROVIDE | | ENGINEERED CONDENSER TIE DOWN DETAIL OR PROVIDE | | ENGINEER STAMPED PLANS. (SEE PROVISIONAL ON PLANS) | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-12-08 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2016-12-08 |
Time |
18:02 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2016-12-08 |
Time |
17:34 |
Sent To |
|
|
Notes |
2016-12-08 17:58:20 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | (1) PROVIDE PROPER VENTILATION FOR LIVING AREAS IN | | LIVING UNITS #1, #2, #3. | | | | FLORIDA ENERGY CODE FBC 2014 | | | | (2) PROVIDE HEAT LOAD CALCULATIONS AS PER R403.6.1 (SEE | | BELOW) | | | | R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED | | IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT | | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR | | OTHER APPROVED HEATING AND COOLING CALCULATION | | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE | | DIRECTIONAL ORIENTATION OF THE BUILDING. THE | | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR | | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH | | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN | | CONDITIONS DESCRIBED IN | | SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER | | SAFETY FACTORS, PROVISIONS FOR FUTURE EXPANSION OR | | OTHER FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM | | SIZING CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY | | LOCAL INTERMITTENT MECHANICAL VENTILATION SUCH AS | | STANDARD KITCHEN AND BATHROOM EXHAUST SYSTEMS. | | | | (3) PROVIDE FORM R405-2014 ENERGY CALCULATIONS. (SEE | | BELOW) | | | | FLORIDA ENERGY CODE - SECTION R202 RENOVATED BUILDINGS | | - A RESIDENTIAL OR NONRESIDENTIAL BUILDING UNDERGOING | | ALTERATION THAT VARIES INSULATION, HVAC SYSTEMS, WATER | | HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS, | | PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30 | | PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE. | | | | C101.4.4 CHANGE IN OCCUPANCY OR USE. | | SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD | | RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL | | OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE | | THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE | | C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1) | | OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY | | WITH SECTION C405.5. | | | | R101.4.3 ADDITIONS, ALTERATIONS, RENOVATIONS OR | | REPAIRS. | | ADDITIONS, ALTERATIONS, RENOVATIONS OR REPAIRS TO AN | | EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF | | SHALL CONFORM TO THE PROVISIONS OF THIS CODE AS THEY | | RELATE TO NEW CONSTRUCTION WITHOUT REQUIRING THE | | UNALTERED PORTION(S) OF THE EXISTING BUILDING OR | | BUILDING SYSTEM TO COMPLY WITH THIS CODE. ADDITIONS, | | ALTERATIONS, RENOVATIONS OR REPAIRS SHALL NOT CREATE AN | | UNSAFE OR HAZARDOUS CONDITION OR OVERLOAD EXISTING | | BUILDING SYSTEMS. AN ADDITION SHALL BE DEEMED TO COMPLY | | WITH THIS CODE IF THE ADDITION ALONE COMPLIES OR IF THE | | EXISTING BUILDING AND ADDITION COMPLY WITH THIS CODE AS | | A SINGLE BUILDING. | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2017-11-30 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-11-30 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-11-30 |
Time |
10:15 |
Sent To |
|
|
Notes |
2017-11-30 10:25:37 | 4TH REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | PREVIOUS COMMENT NOT COMPLIED. 4TH REQUEST | | | | 8. THE VALUATION OF THE JOB APPEARS TO BE A LITTLE LOW | | PLEASE PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR | | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO | | MEET THE | | APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL | | BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING | | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE | | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | BUILDING OFFICIAL. PER WPB AMEND TO FBC 109.3 | | | | NEW COMMENTS: | | | | 1. SHT. S-01 AND S-2 IN THE TITLE BLOCK IT STATES THIS | | IS A REMODEL OF 1 STORY RESIDENCE THERE IS 2 BUILDING 1 | | IS 2 STORY'S PLEASE CLARIFY. PER WPB AMEND TO FBC | | 107.2.1 | | | | 2. THE BRANCH DRAIN FOR THE WASHING MACHINE IN THE 2 | | STORY BUILDING SHALL BE 3". PER FBC PL 406.2 AND THE | | INSTILLATION GUIDE FOR STUDOR VENTS | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2017-08-29 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-08-29 |
Time |
18:23 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-08-29 |
Time |
12:01 |
Sent To |
|
|
Notes |
2017-08-29 18:24:50 | 3RD REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | PREVIOUS COMMENT NOT COMPLIED. 3RD REQUEST | | | | 8. THE VALUATION OF THE JOB APPEARS TO BE A LITTLE LOW | | PLEASE PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR | | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO | | MEET THE | | APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL | | BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING | | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE | | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | BUILDING OFFICIAL. PER WPB AMEND TO FBC 109.3 | | | | PREVIOUS COMMENTS 2ND REQUEST NOT COMPLIED | | | | 1. VALVES FOR THE STACKABLE WASHING MACHINES SHALL BE | | ACCESSIBLE. PER FBC PL 606.3 | | | | 2.SHT. S2 #7 UNDER PLUMBING NOTES AIR CHAMBERS ARE NOT | | APPROVED A WATER-HAMMER ARRESTOR SHALL BE INSTALLED | | WHERE QUICK-CLOSING VALVES ARE UTILIZED. PER FBC PL | | 604.9 | | | | 3.THE UPSTAIRS BATHROOM WITH A TUB IS NOT SHOWN ON THE | | RISER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2017-02-16 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-02-16 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-02-16 |
Time |
09:08 |
Sent To |
|
|
Notes |
2017-02-16 09:10:55 | 2ND REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | PREVIOUS COMMENT NOT COMPLIED. | | | | 8. THE VALUATION OF THE JOB APPEARS TO BE A LITTLE LOW | | PLEASE PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR | | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO | | MEET THE | | APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL | | BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING | | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE | | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | BUILDING OFFICIAL. PER WPB AMEND TO FBC 109.3 | | | | NEW COMMENTS: | | | | 1. VALVES FOR THE STACKABLE WASHING MACHINES SHALL BE | | ACCESSIBLE. PER FBC PL 606.3 | | | | 2.SHT. S2 #7 UNDER PLUMBING NOTES AIR CHAMBERS ARE NOT | | APPROVED A WATER-HAMMER ARRESTOR SHALL BE INSTALLED | | WHERE QUICK-CLOSING VALVES ARE UTILIZED. PER FBC PL | | 604.9 | | | | 3.THE UPSTAIRS BATHROOM WITH A TUB IS NOT SHOWN ON THE | | RISER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-11-16 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-11-16 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-11-15 |
Time |
15:38 |
Sent To |
|
|
Notes |
2016-11-16 15:50:04 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. COVER SHEET IN THE SCOPE OF WORK PLEASE LIST UNDER | | PLUMBING ALL NEW WORK BEING DONE THE BATHROOM ADDITIONS | | AND LAUNDRY ADDITIONS. PER WPB AMEND TO FBC 107.2.1 | | | | 2. SHT. S2 WASHING MACHINE DETAIL SHOWS A 3" STANDPIPE | | THE RISER SHOWS A 2" STAND PIPE PLEASE CLARIFY. PER WPB | | AMEND TO FBC 107.2.1 | | | | 3. SHT S1 BAR SINK NOT SHOWN ON FLOOR PLAN PLEASE | | PROVIDE. PER WPB AMEND TO FBC 107.2.1 | | | | 4. SHT S1 SHOW BATH #3 WITH A TUB ON THE RISER DIAGRAM | | BATH #3 IS SHOWN WITH A SHOWER PLEASE CLARIFY. PER WPB | | AMEND TO FBC 107.2.1 | | | | 5. PROVIDE A RISER DIAGRAM FOR HOT AND COLD WATER. PER | | WPB AMEND TO FBC 107.3.5.1.3(13) | | | | 6. WASHING MACHINES AND DRYERS SHALL COMPLY WITH FBC | | ACC 214 | | | | 7. THE WASHING MACHINE IN THE TWO STORY DWELLING NEEDS | | TO BE SHOWN ON RISER DIAGRAM. PER WPB AMEND TO FBC | | 107.2.1 | | | | 8. THE VALUATION OF THE JOB APPEARS TO BE A LITTLE LOW | | PLEASE PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR | | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO | | MEET THE | | APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL | | BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING | | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE | | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | BUILDING OFFICIAL. PER WPB AMEND TO FBC 109.3 | | | | 9. PLEASE INDICATE ON THE PLAN THE WATER HEATERS TO BE | | EXITING TO REMAIN IN SAME LOCATION O R NEW. PER WPB | | AMEND TO FBC 107.2.1 | | | | 10. THE LOCATION OF FIXTURE AND APPLIANCES IN LAUNDRY | | ROOM DON'T MATCH FROM S1 AND E1 PLEASE CLARIFY. PER WPB | | AMEND TO FBC 107.2.1 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2017-01-10 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-01-10 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-01-10 |
Time |
13:03 |
Sent To |
|
|
Notes |
2017-01-10 13:04:49 | PRODUCT APPROVALS FOR ROOFING SUBMITTED, REVIEWED AND | | APPROVED. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2016-12-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-12-09 |
Time |
13:05 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-12-09 |
Time |
12:18 |
Sent To |
|
|
Notes |
2016-12-09 13:07:05 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 1ST REVIEW | | RESULTS: DENIED | | | | 1. PROVIDE PRODUCT APPROVALS FOR NEW ROOF SYSTEM. | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY | | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING | | SUBMITTALS. | | | 2016-12-06 08:48:54 | ROOFING |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
AW |
Date |
2017-11-27 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
2017-11-27 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-08-11 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
2017-08-11 |
Time |
|
Sent To |
|
|
Notes |
2017-08-11 12:55:59 | *************************ZONING | | REVIEW**************************************** | | | | REPEAT COMMENT | | | | ******ZONING FAILED************* | | | | THE REAR SETBACK REQUIRED BY CODE FOR ADDITION IS 15 | | FEET OR 10% OF LOT DEPTH, WHICHEVER IS LESS. A MINIMUM | | OF 10.5 FEET IS REQUIRED FOR ADDITION. | | | | PLEASE LET ME KNOW WHAT QUESTIONS YOU MAY HAVE. | | | | ALANA WOOTEN | | ASSOCIATE PLANNER | | PLANNING AND ZONING DIVISION | | 561-822-1449 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2017-02-15 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2017-02-15 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
awooten |
Date |
2017-02-15 |
Time |
|
Sent To |
|
|
Notes |
2017-02-15 14:58:48 | ******ZONING FAILED************* | | | | THE REAR SETBACK REQUIRED BY CODE FOR ADDITION IS 15 | | FEET OR 10% OF LOT DEPTH, WHICHEVER IS LESS. A MINIMUM | | OF 10.5 FEET IS REQUIRED FOR ADDITION. | | | | PLEASE LET ME KNOW WHAT QUESTIONS YOU MAY HAVE. | | | | ALANA WOOTEN | | ASSOCIATE PLANNER | | PLANNING AND ZONING DIVISION | | 561-822-1449 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2016-12-08 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2016-12-08 |
Time |
16:33 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2016-12-08 |
Time |
16:33 |
Sent To |
|
|
Notes |
2016-12-08 16:39:33 | 12/8/16- FAILED | | THE REAR SETBACK REAR SETBACK IS 15 FEET OR 10% PERCENT | | OF THE LOT DEPTH WHICHEVER IS LESS. A MINIMUM OF 10.5 | | FEET IS REQUIRED. | | ANGELLA VANN, AICP | | 561-822-1441 | | [email protected] | | |
|
|
|