Plan Review Details - Permit 16100893
Plan Review Stops For Permit 16100893
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-12-08 Cont ID  
Sent By cthroop Date 2017-12-08 Time 15:26 Rev Time 0.00
Received By cthroop Date 2017-12-08 Time 10:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-09-15 Cont ID  
Sent By cthroop Date 2017-09-15 Time 09:19 Rev Time 0.00
Received By cthroop Date 2017-09-14 Time 16:46 Sent To  
Notes
2017-09-15 09:24:59BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THE FOLLOWING COMMENTS FROM 1ST REVIEW HAVE NOT BEEN
 ADDRESSED
  
 1. VALUE.
 2. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS.
  
 NEW COMMENT - 3RD REVIEW
  
 3. ENERGY PERFORMANCE LEVEL FORM TO BE SIGNED BY
 BUILDER.
 4. ENERGY SUBMITTAL FORM 405 TO BE SIGNED BY
 OWNER/AGENT.
  
 THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF
 WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-02-16 Cont ID  
Sent By cthroop Date 2017-02-16 Time 13:58 Rev Time 0.00
Received By cthroop Date 2017-02-16 Time 13:58 Sent To  
Notes
2017-02-16 14:21:48BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE APPEARS LOW FOR PROOSED SCOPE OF WORK.
  
 THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF
 WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 PLEASE INCREASE THE VALUATION ACCORDINGLY.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 - VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-09 Cont ID  
Sent By cthroop Date 2016-12-09 Time 13:07 Rev Time 0.00
Received By cthroop Date 2016-12-09 Time 12:17 Sent To  
Notes
2016-12-09 13:14:52BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. VALUE APPEARS LOW.
 2. PROVIDE ENERGY SUBMITTAL.
 3. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS.
 4. SPECIFY INSULATION R VALUE FOR NEW ROOFS.
  
 VALUATION ? BASED ON THE MARSHALL-SWIFT VALUATION
 SERVICE YOUR STATED VALUE APPEARS LOW.
 THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF
 WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE VALUATION
 ACCORDINGLY.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW, AND
 DOOR SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-08-29 Cont ID  
Sent By jpearson Date 2017-08-29 Time 11:31 Rev Time 0.00
Received By jpearson Date 2017-08-29 Time 11:31 Sent To  
Notes
2017-08-29 11:31:34REVIEWED PER COMMENTS ONLY. JP

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-02-08 Cont ID  
Sent By vperez Date 2017-02-08 Time 10:19 Rev Time 0.00
Received By vperez Date 2017-02-08 Time 10:19 Sent To  
Notes
2017-02-08 10:23:282ND ELECTRICAL REVIEW
  
 PRIOR COMMENT REGARDING FIRE ALARM SYSTEM NOT ADDRESSED
 PER FIRE COMMENTS.
  
 NEW COMMENTS.
  
 PER NEW ELECTRICAL SERVICE SHOWN, MAIN 1 OF 6, 2 OF 6
 ETC MUST BE LABELED ON RISER DIAGRAM. AN AIC
 CALCULATION WAS NOT SUBMITTED. FBC 107.3.5
  
 V. PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-03 Cont ID  
Sent By mvaldes Date 2016-11-03 Time 17:25 Rev Time 0.00
Received By mvaldes Date 2016-11-03 Time 14:43 Sent To  
Notes
2016-11-03 18:05:54JOB PERMIT NUMBER: 16100893
 JOB ADDRESS: 522 43RD ST
 WEST PALM BEACH FLORIDA
 DATE: NOVEMBER 3, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] THE APPLICABLE CODES IN EFFECT ARE NEC 2011, NFPA 72
 (2010), NFPA 101 (2012). PLEASE CORRECT NOTE 1
 ACCORDINGLY.
  
 2] SHOW CIRCUIT DESIGNATION # ON THE FLOOR PLAN TO
 MATCH PANEL SCHEDULE. FBC-107
  
 3] SHOW ALL PANELBOARDS LOCATION ON THE FLOOR PLAN TO
 VERIFY WORK SPACE CLEARANCES. NEC 110.26
  
 4] AT LEAST 1 WALL SWITCHED CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE
 EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE
 LEVEL ACCESS PER NEC 210.70(A)(2).
  
 5] ADD GFI SYMBOL TO RECEPTACLE BY THE RANGE IN THE
 KITCHEN COUNTER-TOP (RED-LINED ON PLANS), ALSO ADD GFI
 "WP/WR" SYMBOL TO RECEPTACLE OUTLETS INSTALLED
 OUTDOORS. NEC 210.8(A)(6), 210.8(A)(3) &, 406.9(B).
  
 6] ALL AREAS SPECIFIED IN NEC 210.52 SHALL HAVE AFCI
 PROTECTION PER NEC 210.12(A). CORRECT ELECTRICAL NOTE
 22.
  
 7] ADD GENERAL ELECTRICAL NOTE FOR TAMPER RESISTANT
 RECEPTACLES IN ACCORDANCE WITH NEC 406.12.
  
 8] ALL MEANS OF EGRESS STAIRWAYS IN COMMON AREAS WILL
 REQUIRE EXIT LIGHTS & EMERGENCY LIGHTS THROUGH-OUT THE
 EXIT DISCHARGE. EXTERIOR ILLUMINATION IS REQUIRED TO
 ILLUMINATE EGRESS PATH UNTIL PUBLIC WAY IS SAFELY
 REACHED. FBC 1011 & 1006 (SHOW COMPLIANCE).
  
 9] EXIT & EMERGENCY LIGHTS SHALL BE FED AHEAD OF LOCAL
 LIGHTING AREA SERVED. NEC 700.12(F)(4)
  
 10] FIRE MARSHALL SHALL DETERMINE IF A FIRE ALARM IS
 REQUIRED OR IF SINGLE STATION SMOKE ALARMS WILL SUFFICE
 ENOUGH FIRE PROTECTION.
  
 11] EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL
 OVERCURRENT DEVICES, AS CONFIGURED ACCESSIBILITY IS
 LIMITED. PLEASE SEE NEC 240.24(B)
  
 12] PROVIDE AIC CALCULATIONS TO VERIFY SHORT-CIRCUIT
 RATINGS OF ELECTRICAL EQUIPMENT. NEC 110.10 & 110.9
  
 13] CLARIFY RISER DIAGRAM FEEDER LAYOUT, EACH UNIT THAT
 WILL BE INDIVIDUALLY METERED SHALL HAVE ITS DEDICATED
 PANEL BOARD WITH ALL ASSOCIATED LOADS TERMINATING
 ACCORDINGLY. ELIMINATE PANELS "C1", "C2", "C3" TO
 COMPLY WITH NEC REQUIREMENTS & SHOW PANEL SCHEDULES
 WITH MATCHING FLOOR PLAN CIRCUITS. ADJUST RISER-DIAGRAM
 DETAIL TO REFLECT ALL CONDUIT & WIRE SIZES. FBC
 107.3.5.3
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON?T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-11-09 Cont ID  
Sent By pleduc Date 2017-11-09 Time   Rev Time 0.00
Received By pleduc Date 2017-11-09 Time 10:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-08-14 Cont ID  
Sent By pleduc Date 2017-08-14 Time   Rev Time 0.00
Received By pleduc Date 2017-08-14 Time 10:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-02-09 Cont ID  
Sent By pleduc Date 2017-02-09 Time   Rev Time 0.00
Received By pleduc Date 2017-02-09 Time 10:37 Sent To  
Notes
2017-02-09 10:44:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PREVIOUS COMMENTS WERE NOT ADDRESSED.
  
 PREVIOUS COMMENYS:
  
 1) PLEASE PROVIDE THE OCCUPANCY CLASSFICATION PER THE
 FLORIDA FIRE PREVENTION CODE.
  
 ONE UNIT, # 5, HAS 6 BEDROOMS, A GAME ROOM, COMMON
 WASHER/DRYER ROOM AND APPEARS TO HAVE A POSSIBLE USE
 BEYOND A SINGLE FAMILY RESIDENCE.
  
 ADDITIONAL COMMENT: WILL THIS BUILDING BE USED AS A
 RECOVERY TYPE RESIDENCE ? IF SO, HOW MANY RESIDENTS ARE
 PROPOSED ? IT IS IMPERATIVE FOR THE LIFE SAFETY REVIEW
 TO HAVE DEFINITIVE OCCUPANCY CLASSIFICATION.
  
  
  
  
 2) AS SUBMITTED THE CONSTRUCTION SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE, NFPA 101, CHAPTER 30, NEW
 APARTMENT BUILDINGS AND ALL APPLICABLE CODES.
  
 UNLESS OTHERWISE INDICATED SEPARATLY BY THE CORRECTION
 OF # 1 ABOVE, PLEASE PROVIDE AN APPLICABLE NOTE,
  
 ADDITIONAL COMMENT: IF IT WILL NOT BE A RECOVERY
 RESIDENCE AND IT IS NOT CONSIDERED A NEW APARTMENT, YOU
 MUST INDICATE AND ENSURE COMPLIANCE WITH EXISTING
 APARTMENT OCCUPANCCIES.
  
  
  
 3) A FIRE SPRINKLER SYSTEM IS NOT INDICATED. PER NFPA
 101, CHAPTER 30:
  
 30.3.5 EXTINGUISHMENT REQUIREMENTS.
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH 30.3.5.2.
 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR TOTAL OR PARTIAL BUILDING
 COVERAGE, THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE
 WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 AND
 30.3.5.4. IN BUILDINGS FOUR OR FEWER STORIES ABOVE
 GRADE PLANE, SYSTEMS IN ACCORDANCE WITH NFPA 13R,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN
 LOW-RISE RESIDENTIAL OCCUPANCIES, SHALL BE PERMITTED.
  
 PLEASE PROVIDE FIRE SPRINKLER DRAWINGS OR A NARRATIVE
 IN COMPLIANCE WITH FS 61G - PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 ADDITIONAL COMMENT: BASED ON THE OCCUPANCY
 CLASSIFICATION AND OCCUPANCY USE A FIRE SPRINKLER
 SYSTEM MAY STILL BE REQUIRED. PLEASE PROVIDE SPECIFIC
 INFORMATION AND ANSWERS.
  
  
  
  
 4) A FIRE ALARM SYSTEM IN NOT INDICATED. PER NFPA 101,
 CHAPTER 30 & CHAPTER 9.
  
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH 30.3.5.2.
  
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS
 CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER
 SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE
 FLORIDA BUILDING CODE.
  
  
 ADDITIONAL COMMENT: BASED ON THE OCCUPANCY
 CLASSIFICATION AND OCCUPANCY USE A FIRE ALARM SYSTEM
 MAY STILL BE REQUIRED. IF IT IS A EXISTING APARTMENT
 OCCUPANCY CLASSIFICATION UNDER NFPA 101, CHAPTER 31, A
 FIRE ALARM IS NOT REQUIRED. PLEASE PROVIDE SPECIFIC
 INFORMATION AND ANSWERS.
  
  
  
  
 5) PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED
 FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 ADDITIONAL COMMENT: COMMENT NOT ADDRESSED.
  
  
  
 6) THE PROPOSED LAUNDRY ROOM SHALL BE PROTECTED BY 1 -
 HOUR SEPARATION AND FIRE SPRINKLERS
  
 PER NFPA 101, CHAPTER 30,
  
 30.3.2 PROTECTION FROM HAZARDS.
 30.3.2.1 HAZARDOUS AREAS. ANY HAZARDOUS AREA SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 8.7.
 30.3.2.1.1 THE AREAS DESCRIBED IN TABLE 30.3.2.1.1
 SHALL BE PROTECTED AS INDICATED.
  
 TABLE 30.3.2.1.1 LAUNDRIES 1 HOUR AND SPRINKLERS >100
 FT2 (>9.3 M2) OUTSIDE OF DWELLING UNITS
  
 ADDITIONAL COMMENT: THE SAME CODE IS APPLICABLE TO
 EXISTING APARTMENTS. COMMENT NOT ADDRESSED. SECTION 8.7
 HAS SPECIFIC LANGUAGE THAT NEEDS TO BE USED IN THE
 DESIGN OF THE LAUNDRY ROOM, NO WINDOWS,
 8.7 SPECIAL HAZARD PROTECTION.
 8.7.1 GENERAL.
 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF
 HAZARD GREATER THAN THAT NORMAL TO THE GENERAL
 OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE
 PROVIDED BY ONE OF THE FOLLOWING MEANS:
 (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT
 WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 8.3.
 (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING
 SYSTEMS IN ACCORDANCE WITH SECTION 9.7
 (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD
 IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11
 THROUGH 43
  
 8.3 FIRE BARRIERS.
 8.3.1 GENERAL.
 8.3.1.1 FIRE BARRIERS USED TO PROVIDE ENCLOSURE,
 SUBDIVISION, OR PROTECTION UNDER THIS CODE SHALL BE
 CLASSIFIED IN ACCORDANCE WITH ONE OF THE FOLLOWING FIRE
 RESISTANCE RATINGS:
 (1) 3-HOUR FIRE RESISTANCE RATING
 (2) 2-HOUR FIRE RESISTANCE RATING
 (3) 1-HOUR FIRE RESISTANCE RATING
 (4)* ?-HOUR FIRE RESISTANCE RATING
 8.3.1.2* FIRE BARRIERS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 (1) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL
 TO OUTSIDE WALL OR FROM ONE FIRE BARRIER TO ANOTHER, OR
 A COMBINATION THEREOF, INCLUDING CONTINUITY THROUGH ALL
 CONCEALED SPACES, SUCH AS THOSE FOUND ABOVE A CEILING,
 INCLUDING INTERSTITIAL SPACES.
 (2) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL
 TO OUTSIDE WALL OR FROM ONE FIRE BARRIER TO ANOTHER,
 AND FROM THE FLOOR TO THE BOTTOM OF THE INTERSTITIAL
 SPACE, PROVIDED THAT THE CONSTRUCTION ASSEMBLY FORMING
 THE BOTTOM OF THE INTERSTITIAL SPACE HAS A FIRE
 RESISTANCE RATING NOT LESS THAN THAT OF THE FIRE
 BARRIER.
  
 THE DOORS, O & P, TO THE LAUNDRY ARE NOTED TO HOLLOW
 CORE, THERE ARE WINDOWS, AN EXIT STAIRWAY AND A WOOD
 WALL ABOVE THE LAUNDRY. ON THE OTHER SIDE THERE IS A
 WINDOW WITHIN 10 FT OF THE LAUNDRY THAT IS UNPROTECTED.
  
 PLEASE REVIEW, CLARIFY AND/OR CORRECT.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 COMMENT REMAINS
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 COMMENT REMAINS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-11-07 Cont ID  
Sent By pleduc Date 2016-11-07 Time   Rev Time 0.00
Received By pleduc Date 2016-11-04 Time 15:38 Sent To  
Notes
2016-11-04 16:52:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) PLEASE PROVIDE THE OCCUPANCY CLASSFICATION PER THE
 FLORIDA FIRE PREVENTION CODE.
  
 ONE UNIT, # 5, HAS 6 BEDROOMS, A GAME ROOM, COMMON
 WASHER/DRYER ROOM AND APPEARS TO HAVE A POSSIBLE USE
 BEYOND A SINGLE FAMILY RESIDENCE.
  
  
 2) AS SUBMITTED THE CONSTRUCTION SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE, NFPA 101, CHAPTER 30, NEW
 APARTMENT BUILDINGS AND ALL APPLICABLE CODES.
  
 UNLESS OTHERWISE INDICATED SEPARATLY BY THE CORRECTION
 OF # 1 ABOVE, PLEASE PROVIDE AN APPLICABLE NOTE,
  
  
 3) A FIRE SPRINKLER SYSTEM IS NOT INDICATED. PER NFPA
 101, CHAPTER 30:
  
 30.3.5 EXTINGUISHMENT REQUIREMENTS.
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH 30.3.5.2.
 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR TOTAL OR PARTIAL BUILDING
 COVERAGE, THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE
 WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 AND
 30.3.5.4. IN BUILDINGS FOUR OR FEWER STORIES ABOVE
 GRADE PLANE, SYSTEMS IN ACCORDANCE WITH NFPA 13R,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN
 LOW-RISE RESIDENTIAL OCCUPANCIES, SHALL BE PERMITTED.
  
 PLEASE PROVIDE FIRE SPRINKLER DRAWINGS OR A NARRATIVE
 IN COMPLIANCE WITH FS 61G - PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
  
  
 4) A FIRE ALARM SYSTEM IN NOT INDICATED. PER NFPA 101,
 CHAPTER 30 & CHAPTER 9.
  
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH 30.3.5.2.
  
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS
 CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER
 SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE
 FLORIDA BUILDING CODE.
  
  
  
 5) PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED
 FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
  
 6) THE PROPOSED LAUNDRY ROOM SHALL BE PROTECTED BY 1 -
 HOUR SEPARATION AND FIRE SPRINKLERS
  
 PER NFPA 101, CHAPTER 30,
  
 30.3.2 PROTECTION FROM HAZARDS.
 30.3.2.1 HAZARDOUS AREAS. ANY HAZARDOUS AREA SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 8.7.
 30.3.2.1.1 THE AREAS DESCRIBED IN TABLE 30.3.2.1.1
 SHALL BE PROTECTED AS INDICATED.
  
 TABLE 30.3.2.1.1 LAUNDRIES 1 HOUR AND SPRINKLERS >100
 FT2 (>9.3 M2) OUTSIDE OF DWELLING UNITS
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-12-08 Cont ID  
Sent By cthroop Date 2017-12-08 Time 15:26 Rev Time 0.00
Received By cthroop Date 2017-11-07 Time 15:57 Sent To I
Notes
2017-11-08 15:57:53B29

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-09-15 Cont ID  
Sent By cthroop Date 2017-09-15 Time 09:18 Rev Time 0.00
Received By cthroop Date 2017-08-04 Time 15:07 Sent To  
Notes
2017-08-07 15:07:32B29

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-15 Cont ID  
Sent By jvalido Date 2017-02-15 Time 18:17 Rev Time 0.00
Received By jvalido Date 2017-02-01 Time 10:30 Sent To  
Notes
2017-02-15 18:15:37ROUTED TO GEORGE JOHNSON 2/15/2017 - JORGE V.
2017-02-02 10:31:25B29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-10 Cont ID  
Sent By cthroop Date 2017-01-10 Time 13:03 Rev Time 0.00
Received By cthroop Date 2017-01-05 Time 10:10 Sent To  
Notes
2017-01-06 10:11:04RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-09 Cont ID  
Sent By cthroop Date 2016-12-09 Time 13:07 Rev Time 0.00
Received By cthroop Date 2016-10-28 Time 10:16 Sent To  
Notes
2016-12-08 18:04:22ROUTED TO CHRIS THROOP 12/8/2016 - JORGE V.
2016-10-31 10:16:35R20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-12-09 Cont ID  
Sent By cthroop Date 2016-12-09 Time 13:04 Rev Time 0.00
Received By cthroop Date 2016-12-09 Time 12:18 Sent To  
Notes
2016-12-09 13:05:32BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-11-29 Cont ID  
Sent By ccole Date 2017-11-29 Time 16:04 Rev Time 0.00
Received By ccole Date 2017-11-29 Time 15:39 Sent To  
Notes
2017-11-29 16:16:064TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16100893
 11/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GENERAL CONTRACTOR ALEJANDRO RODRIGUEZ IS NOT A
 LICENSED AC OR MECHANICAL CONTRACTOR AND THEREFORE
 CANNOT DESIGN THE PLANS FOR THE PROPOSED PROJECT.
 PLEASE SEE SECTION 105.3.1.2 FBC-14 BUILDING WHICH
 PERMITS THE INSTALLING AC CONTRACTOR TO DESIGN THE
 PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-09-07 Cont ID  
Sent By ccole Date 2017-09-07 Time 12:37 Rev Time 0.00
Received By ccole Date 2017-09-06 Time 11:29 Sent To  
Notes
2017-09-07 12:50:073RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16100893
 9/7/16
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 2ND REVIEW STILL EXIST. I HAVE
 REPRINTED THEM BELOW THE 3RD REVIEW COMMENTS. PLEASE
 COMPLY WITH BOTH THE 2ND AND 3RD REVIEW COMMENTS.
  
 1) M.1 & M.2: THE LAUNDRY ROOM (SYSTEM 7) IS NOT SHOWN
 ON THE PLANS OR INCLUDED IN THE SCHEDULE- SEE AC AND
 ENERGY CALCULATIONS.
  
 2) THE ENERGY CALCULATION FORM R405-2014 MUST BE SIGNED
 BY THE OWNER/AGENT.
  
 3) THE WIND LOAD DESIGN CRITERIA AND ENGINEERING FOR
 THE EXTERIOR CONDENSER AHOWN ON M.2 CANNOT BE PREPARED
 BY AN AC CONTRACTOR. PROVIDE ENGINEERED DESIGN BY A FL.
 LICENSED P.E., OR SUBMIT A FL. PRODUCT APPROVAL FOR TIE
 DOWN CLIPS WITH APPROVAL STAMP BY THE DESIGN
 PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 2ND REVIEW
  
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL: 107.2 CONSTRUCTION DOCUMENTS: 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 FLORIDA ENERGY CODE FBC 2014
  
 (1) SYSTEM #5 ON THE APPROVED PLANS DOES NOT MATCH THE
 HEAT LOAD CALCULATIONS DESIGN REQUIREMENTS. CHECK HEAT
 LOAD CALCULATIONS AND MAKE ALL REQUIRED CORRECTIONS.
 (2) FORM R405-2014 MUST BE COMPLETLY FILLED OUT WITH
 ALL OF THE REQUIRED INFORMATION AND SIGNATURES. SEE
 HIGHLIGHTED AREAS. ONE OF THE ENERGY CALCULATIONS IS
 MISSING PAGE 1 OF 7.
 (3) A CMC LICENSE CANNOT DESIGN CONDENSER TIE DOWNS.
 CONDENSER TIE DOWNS MUST BE ENGINEERED. PROVIDE
 ENGINEERED CONDENSER TIE DOWN DETAIL OR PROVIDE
 ENGINEER STAMPED PLANS. (SEE PROVISIONAL ON PLANS)
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-02-15 Cont ID  
Sent By jvalido Date 2017-02-15 Time 18:14 Rev Time 0.00
Received By jvalido Date 2017-02-15 Time 16:52 Sent To  
Notes
2017-02-15 18:09:422ND REVIEW
  
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 FLORIDA ENERGY CODE FBC 2014
  
 (1) SYSTEM #5 ON THE APPROVED PLANS DOES NOT MATCH THE
 HEAT LOAD CALCULATIONS DESIGN REQUIREMENTS. CHECK HEAT
 LOAD CALCULATIONS AND MAKE ALL REQUIRED CORRECTIONS.
 (2) FORM R405-2014 MUST BE COMPLETLY FILLED OUT WITH
 ALL OF THE REQUIRED INFORMATION AND SIGNATURES. SEE
 HIGHLIGHTED AREAS. ONE OF THE ENERGY CALCULATIONS IS
 MISSING PAGE 1 OF 7.
 (3) A CMC LICENSE CANNOT DESIGN CONDENSER TIE DOWNS.
 CONDENSER TIE DOWNS MUST BE ENGINEERED. PROVIDE
 ENGINEERED CONDENSER TIE DOWN DETAIL OR PROVIDE
 ENGINEER STAMPED PLANS. (SEE PROVISIONAL ON PLANS)
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-08 Cont ID  
Sent By jvalido Date 2016-12-08 Time 18:02 Rev Time 0.00
Received By jvalido Date 2016-12-08 Time 17:34 Sent To  
Notes
2016-12-08 17:58:20CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE PROPER VENTILATION FOR LIVING AREAS IN
 LIVING UNITS #1, #2, #3.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (2) PROVIDE HEAT LOAD CALCULATIONS AS PER R403.6.1 (SEE
 BELOW)
  
 R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED
 IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN
 SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER
 SAFETY FACTORS, PROVISIONS FOR FUTURE EXPANSION OR
 OTHER FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM
 SIZING CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY
 LOCAL INTERMITTENT MECHANICAL VENTILATION SUCH AS
 STANDARD KITCHEN AND BATHROOM EXHAUST SYSTEMS.
  
 (3) PROVIDE FORM R405-2014 ENERGY CALCULATIONS. (SEE
 BELOW)
  
 FLORIDA ENERGY CODE - SECTION R202 RENOVATED BUILDINGS
 - A RESIDENTIAL OR NONRESIDENTIAL BUILDING UNDERGOING
 ALTERATION THAT VARIES INSULATION, HVAC SYSTEMS, WATER
 HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS,
 PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30
 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE.
  
 C101.4.4 CHANGE IN OCCUPANCY OR USE.
 SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD
 RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL
 OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE
 THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE
 C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1)
 OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY
 WITH SECTION C405.5.
  
 R101.4.3 ADDITIONS, ALTERATIONS, RENOVATIONS OR
 REPAIRS.
 ADDITIONS, ALTERATIONS, RENOVATIONS OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL CONFORM TO THE PROVISIONS OF THIS CODE AS THEY
 RELATE TO NEW CONSTRUCTION WITHOUT REQUIRING THE
 UNALTERED PORTION(S) OF THE EXISTING BUILDING OR
 BUILDING SYSTEM TO COMPLY WITH THIS CODE. ADDITIONS,
 ALTERATIONS, RENOVATIONS OR REPAIRS SHALL NOT CREATE AN
 UNSAFE OR HAZARDOUS CONDITION OR OVERLOAD EXISTING
 BUILDING SYSTEMS. AN ADDITION SHALL BE DEEMED TO COMPLY
 WITH THIS CODE IF THE ADDITION ALONE COMPLIES OR IF THE
 EXISTING BUILDING AND ADDITION COMPLY WITH THIS CODE AS
 A SINGLE BUILDING.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2017-11-30 Cont ID  
Sent By gjohnson Date 2017-11-30 Time 10:26 Rev Time 0.00
Received By gjohnson Date 2017-11-30 Time 10:15 Sent To  
Notes
2017-11-30 10:25:374TH REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENT NOT COMPLIED. 4TH REQUEST
  
 8. THE VALUATION OF THE JOB APPEARS TO BE A LITTLE LOW
 PLEASE PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL. PER WPB AMEND TO FBC 109.3
  
 NEW COMMENTS:
  
 1. SHT. S-01 AND S-2 IN THE TITLE BLOCK IT STATES THIS
 IS A REMODEL OF 1 STORY RESIDENCE THERE IS 2 BUILDING 1
 IS 2 STORY'S PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 2. THE BRANCH DRAIN FOR THE WASHING MACHINE IN THE 2
 STORY BUILDING SHALL BE 3". PER FBC PL 406.2 AND THE
 INSTILLATION GUIDE FOR STUDOR VENTS
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-08-29 Cont ID  
Sent By gjohnson Date 2017-08-29 Time 18:23 Rev Time 0.00
Received By gjohnson Date 2017-08-29 Time 12:01 Sent To  
Notes
2017-08-29 18:24:503RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENT NOT COMPLIED. 3RD REQUEST
  
 8. THE VALUATION OF THE JOB APPEARS TO BE A LITTLE LOW
 PLEASE PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL. PER WPB AMEND TO FBC 109.3
  
 PREVIOUS COMMENTS 2ND REQUEST NOT COMPLIED
  
 1. VALVES FOR THE STACKABLE WASHING MACHINES SHALL BE
 ACCESSIBLE. PER FBC PL 606.3
  
 2.SHT. S2 #7 UNDER PLUMBING NOTES AIR CHAMBERS ARE NOT
 APPROVED A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. PER FBC PL
 604.9
  
 3.THE UPSTAIRS BATHROOM WITH A TUB IS NOT SHOWN ON THE
 RISER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-02-16 Cont ID  
Sent By gjohnson Date 2017-02-16 Time 09:08 Rev Time 0.00
Received By gjohnson Date 2017-02-16 Time 09:08 Sent To  
Notes
2017-02-16 09:10:552ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENT NOT COMPLIED.
  
 8. THE VALUATION OF THE JOB APPEARS TO BE A LITTLE LOW
 PLEASE PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL. PER WPB AMEND TO FBC 109.3
  
 NEW COMMENTS:
  
 1. VALVES FOR THE STACKABLE WASHING MACHINES SHALL BE
 ACCESSIBLE. PER FBC PL 606.3
  
 2.SHT. S2 #7 UNDER PLUMBING NOTES AIR CHAMBERS ARE NOT
 APPROVED A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. PER FBC PL
 604.9
  
 3.THE UPSTAIRS BATHROOM WITH A TUB IS NOT SHOWN ON THE
 RISER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-16 Cont ID  
Sent By gjohnson Date 2016-11-16 Time 15:04 Rev Time 0.00
Received By gjohnson Date 2016-11-15 Time 15:38 Sent To  
Notes
2016-11-16 15:50:041ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. COVER SHEET IN THE SCOPE OF WORK PLEASE LIST UNDER
 PLUMBING ALL NEW WORK BEING DONE THE BATHROOM ADDITIONS
 AND LAUNDRY ADDITIONS. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. S2 WASHING MACHINE DETAIL SHOWS A 3" STANDPIPE
 THE RISER SHOWS A 2" STAND PIPE PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 3. SHT S1 BAR SINK NOT SHOWN ON FLOOR PLAN PLEASE
 PROVIDE. PER WPB AMEND TO FBC 107.2.1
  
 4. SHT S1 SHOW BATH #3 WITH A TUB ON THE RISER DIAGRAM
 BATH #3 IS SHOWN WITH A SHOWER PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 5. PROVIDE A RISER DIAGRAM FOR HOT AND COLD WATER. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 6. WASHING MACHINES AND DRYERS SHALL COMPLY WITH FBC
 ACC 214
  
 7. THE WASHING MACHINE IN THE TWO STORY DWELLING NEEDS
 TO BE SHOWN ON RISER DIAGRAM. PER WPB AMEND TO FBC
 107.2.1
  
 8. THE VALUATION OF THE JOB APPEARS TO BE A LITTLE LOW
 PLEASE PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL. PER WPB AMEND TO FBC 109.3
  
 9. PLEASE INDICATE ON THE PLAN THE WATER HEATERS TO BE
 EXITING TO REMAIN IN SAME LOCATION O R NEW. PER WPB
 AMEND TO FBC 107.2.1
  
 10. THE LOCATION OF FIXTURE AND APPLIANCES IN LAUNDRY
 ROOM DON'T MATCH FROM S1 AND E1 PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-01-10 Cont ID  
Sent By cthroop Date 2017-01-10 Time 13:04 Rev Time 0.00
Received By cthroop Date 2017-01-10 Time 13:03 Sent To  
Notes
2017-01-10 13:04:49PRODUCT APPROVALS FOR ROOFING SUBMITTED, REVIEWED AND
 APPROVED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-12-09 Cont ID  
Sent By cthroop Date 2016-12-09 Time 13:05 Rev Time 0.00
Received By cthroop Date 2016-12-09 Time 12:18 Sent To  
Notes
2016-12-09 13:07:05BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW ROOF SYSTEM.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  
2016-12-06 08:48:54ROOFING

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By AW Date 2017-11-27 Time   Rev Time 0.00
Received By   Date 2017-11-27 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2017-08-11 Time   Rev Time 0.00
Received By   Date 2017-08-11 Time   Sent To  
Notes
2017-08-11 12:55:59*************************ZONING
 REVIEW****************************************
  
 REPEAT COMMENT
  
 ******ZONING FAILED*************
  
 THE REAR SETBACK REQUIRED BY CODE FOR ADDITION IS 15
 FEET OR 10% OF LOT DEPTH, WHICHEVER IS LESS. A MINIMUM
 OF 10.5 FEET IS REQUIRED FOR ADDITION.
  
 PLEASE LET ME KNOW WHAT QUESTIONS YOU MAY HAVE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING AND ZONING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2017-02-15 Cont ID  
Sent By awooten Date 2017-02-15 Time 14:59 Rev Time 0.00
Received By awooten Date 2017-02-15 Time   Sent To  
Notes
2017-02-15 14:58:48******ZONING FAILED*************
  
 THE REAR SETBACK REQUIRED BY CODE FOR ADDITION IS 15
 FEET OR 10% OF LOT DEPTH, WHICHEVER IS LESS. A MINIMUM
 OF 10.5 FEET IS REQUIRED FOR ADDITION.
  
 PLEASE LET ME KNOW WHAT QUESTIONS YOU MAY HAVE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING AND ZONING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2016-12-08 Cont ID  
Sent By ajones Date 2016-12-08 Time 16:33 Rev Time 0.00
Received By ajones Date 2016-12-08 Time 16:33 Sent To  
Notes
2016-12-08 16:39:3312/8/16- FAILED
 THE REAR SETBACK REAR SETBACK IS 15 FEET OR 10% PERCENT
 OF THE LOT DEPTH WHICHEVER IS LESS. A MINIMUM OF 10.5
 FEET IS REQUIRED.
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]
  