Plan Review Details - Permit 16100885
Plan Review Stops For Permit 16100885
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-02 Cont ID  
Sent By vperez Date 2016-12-02 Time 07:46 Rev Time 0.00
Received By vperez Date 2016-12-02 Time 07:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-03 Cont ID  
Sent By vperez Date 2016-11-03 Time 09:39 Rev Time 0.00
Received By vperez Date 2016-11-03 Time 09:38 Sent To  
Notes
2016-11-03 09:40:14PLEASE ADDRESS FIRE COMMENTS FOR AN ELECTRICAL
 APPROVAL.
  
 VAL PEREZ
 *6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-11-23 Cont ID  
Sent By pleduc Date 2016-11-23 Time   Rev Time 0.00
Received By pleduc Date 2016-11-23 Time 11:59 Sent To E
Notes
2016-11-23 12:00:32THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHOP DRAWINGS ARE REQUIRED TO BE SUBMITTED AND
 APPROVED PRIOR TO INSTALLATION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-11-01 Cont ID  
Sent By pleduc Date 2016-11-01 Time   Rev Time 0.00
Received By pleduc Date 2016-11-01 Time 09:16 Sent To E
Notes
2016-11-01 09:43:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROPOSED PROJECT INDICATES MULTIPLE NEW FIRE
 ALARM DEVICES THAT WERE NOT EXISTING REPLACEMENTS.
  
 PLEASE PROVIDE REVISED VOLTAGE DROP AND BATTERY
 CALCULATIONS TO INCLUDE ALL NEW DEVICES.
  
  
  
 2) THERE WERE NO PRODUCTS SPECS OR SHEETS PROVIDED.
  
 PLEASE PROVIDE ALL APPLICABLE PRODUCTS SHEETS FOR ALL
 NEW DEVICES.
  
  
  
 3) THE NEW DEVICES ARE NOT SHOWN ON SYSTEM DIAGRAM.
  
 PLEASE PROVIDE A SYSTEM DIAGRAM INCLUDING ADDRESSABLE
 LABELS.
  
  
  
 4) THERE WERE NO WIRING DIAGRAMS PROVIDED.
  
 PLEASE PROVIDE NEW WIRING DIAGRAMS FOR ALL NEW DEVICES
 AND/OR ANY NEW WIRING INSTALLATIONS.
  
  
  
 5) THERE IS NO INDICATIONS THAT THE EXISTING FIRE ALARM
 WILL REMAIN FULLY FUNCTIONAL DURING CONSTRUCTION
 PERIOD.
  
 PER NFPA NFPA 101, CHAPTER 9, BUILDING SERVICE AND FIRE
 PROTECTION EQUIPMENT
  
 9.6.1.6* WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF
 SERVICE FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE
 AUTHORITY HAVING JURISDICTION SHALL BE NOTIFIED, AND
 THE BUILDING SHALL BE EVACUATED, OR AN APPROVED FIRE
 WATCH SHALL BE PROVIDED FOR ALL PARTIES LEFT
 UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE ALARM SYSTEM
 HAS BEEN RETURNED TO SERVICE.
  
 PLEASE PROVIDE A NOTE OF COMPLIANCE.
  
  
  
 6) A NFPA 72 INSPECTION AND FULL FIRE ALARM TEST SHALL
 BE REQUIRED FOR THIS PROPOSED INSTALLATION.
  
  
  
 7) PLEASE PROVIDE PLAN SHEET REVISION CLOUDS OR
 NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-02 Cont ID  
Sent By vperez Date 2016-12-02 Time 07:46 Rev Time 0.00
Received By vperez Date 2016-12-02 Time 07:46 Sent To  
Notes
2016-11-22 13:03:49RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-03 Cont ID  
Sent By vperez Date 2016-11-03 Time 09:39 Rev Time 0.00
Received By vperez Date 2016-11-03 Time 09:39 Sent To  
Notes
2016-10-31 10:08:19ROUTED TO FIRE INBOX