Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-10-31 Cont ID  
Sent By pleduc Date 2016-10-31 Time   Rev Time 0.00
Received By pleduc Date 2016-10-31 Time 17:10 Sent To M
Notes
2016-10-31 17:25:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED APPLICATION AND DRAWINGS INDICATE THAT
 ALL SIDEWALL HEADS WERE CHANGED TO PENDANTS.
  
 HOW MANY SIDEWALL HEADS WERE REPLACED?
  
 WHAT WERE THE SPECIFIC LOCATIONS?
  
 2) THESE MODIFICATIONS ADD AN INCREASED DEMAND ON THE
 PREVIOUSLY DESIGNED AND APPROVED SYSTEM.
  
 3) NEW BRANCH LINES HAVE BEEN ADDED AND ARE MORE THAN
 RELOCATED DROPS.
  
 HOW WILL THE NEW INSTALLTION BE TESTED?
  
 CAN THE FLOOR OR SPACE BE ISOLATED ?
  
 4) THESE MODIFICATIONS MAY NOT BE IN THE SCOPE AND/OR
 APPROVAL OF THE ENGINEER OF RECORD DESIGN CRITERIA.
  
 5) PROVIDE RECALCULATED HYDRALIC CALCULATIONS SHOWING
 APPICABLE DEMAND REQUIRMENTS.
  
 6) PROVIDE APPROVAL AND/OR REVIEW FROM ENGEER OF
 RECORD.
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-07 Cont ID  
Sent By ccole Date 2016-11-07 Time 09:52 Rev Time 0.00
Received By ccole Date 2016-10-27 Time 13:39 Sent To  
Notes
2016-10-28 13:39:30REVISION ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-11-07 Cont ID  
Sent By ccole Date 2016-11-07 Time 09:52 Rev Time 0.00
Received By ccole Date 2016-11-07 Time 09:52 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved