Plan Review Details - Permit 16100844
Plan Review Stops For Permit 16100844
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-11-14 Cont ID  
Sent By skennedy Date 2016-11-14 Time 11:21 Rev Time 0.00
Received By skennedy Date 2016-11-14 Time 11:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-10 Cont ID  
Sent By cthroop Date 2016-11-10 Time 11:53 Rev Time 0.00
Received By cthroop Date 2016-11-10 Time 11:53 Sent To  
Notes
2016-11-10 12:09:31BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. DESIGNER SHALL PROVIDE THEIR PRINTED NAME AND
 SIGNATURE ON THE PLAN PER FBC 107.
 2. PLANS SUBMITTED IN PENCIL ARE NOT ACCEPTABLE PER FBC
 107.2.1.4.
 3. PROVIDE ASTM'S E-90 (SOUND) AND E-492 (IMPACT) FOR
 FLOORING UNDERLAYMENT (WHISPERMAT-CS).
 4. STATE GOVERNING CODES ON PLANS.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 49
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-14 Cont ID  
Sent By skennedy Date 2016-11-14 Time 11:21 Rev Time 0.00
Received By skennedy Date 2016-11-14 Time 11:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-31 Cont ID  
Sent By cthroop Date 2016-11-10 Time 11:53 Rev Time 0.00
Received By vperez Date 2016-10-31 Time 11:52 Sent To P
Notes
2016-10-31 11:52:49INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE SHOW JACUZZI TO BE PROTECTED BY GFCI BREAKER
 TO BE READILY ACCESSIBLE. A NOTE WILL SUFFICE.
 2. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER RESISTANT
 RECEPTACLE. FBC RES E4002.14
 3. PROVIDE A NOTE TO PROVIDE AFCI PROTECTION PER FBC
 RES E3902.12
 4. PROVIDE THE EXISTING PANEL SCHEDULE REFLECTING NEW
 JACUZZI AND WATER VALVE LOADS. FBC 107.3.5
 5. CLARIFY IF THERE ARE EXISTING SMOKE DETECTORS IN
 UNIT IF NOT SHOW AND PROVIDE ON DRAWINGS. FBC RES 315
 6. PROVIDE SPEC SHEETS FOR THE NEW 120V ELECTRONIC
 SHOWER CONTROL VALVE.
 7. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-14 Cont ID  
Sent By skennedy Date 2016-11-14 Time 11:20 Rev Time 0.00
Received By skennedy Date 2016-11-14 Time 11:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-10 Cont ID  
Sent By cthroop Date 2016-11-10 Time 11:53 Rev Time 0.00
Received By cthroop Date 2016-10-27 Time 15:24 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-14 Cont ID  
Sent By skennedy Date 2016-11-14 Time 11:21 Rev Time 0.00
Received By skennedy Date 2016-11-14 Time 11:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-07 Cont ID  
Sent By tklarge Date 2016-11-07 Time 06:14 Rev Time 0.00
Received By tklarge Date 2016-11-07 Time 06:02 Sent To  
Notes
2016-11-07 06:13:021) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE JACUZZI
 TUB AND ALSO THE ELECTRONIC SHOWER CONTROL VALVE. WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) THERE ARE PENCILED NOTES ON ONE SHEET OF THE PLANS.
 NOTES IN PENCIL ARE NOT ACCEPTABLE.
 3) SHOW THE LENGTH AND WIDTH OF THE PROPOSED SHOWER IN
 BATH #2. COMPLY WITH FPC SEC.417.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  