Plan Review Details - Permit 16100755
Plan Review Stops For Permit 16100755
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-05 Cont ID  
Sent By shill Date 2016-12-05 Time 07:00 Rev Time 0.00
Received By shill Date 2016-12-05 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-31 Cont ID  
Sent By shill Date 2016-10-31 Time 09:03 Rev Time 0.00
Received By shill Date 2016-10-31 Time 08:54 Sent To  
Notes
2016-10-31 09:04:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. OFFICE 1, 18 INCH MANEUVERING CLEARANCE, PULL SIDE,
 IS REQUIRED PER FBC 5TH EDITION ACCESSIBILITY 404.2.1,
 REVISE TO SHOW REQUIRED DIMENSION.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-11-03 Cont ID  
Sent By rlecky Date 2016-11-03 Time 14:04 Rev Time 0.00
Received By rlecky Date 2016-11-03 Time 13:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-12-12 Cont ID  
Sent By pleduc Date 2016-12-12 Time   Rev Time 0.00
Received By pleduc Date 2016-12-09 Time 16:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-10-26 Cont ID  
Sent By pleduc Date 2016-10-26 Time   Rev Time 0.00
Received By pleduc Date 2016-10-26 Time 14:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-14 Cont ID  
Sent By gjohnson Date 2016-12-14 Time 12:45 Rev Time 0.00
Received By gjohnson Date 2016-12-01 Time 09:21 Sent To  
Notes
2016-12-02 09:21:27B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-19 Cont ID  
Sent By tklarge Date 2016-11-19 Time 05:37 Rev Time 0.00
Received By tklarge Date 2016-10-25 Time 16:08 Sent To  
Notes
2016-10-25 16:08:17B13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-05 Cont ID  
Sent By ccole Date 2016-12-05 Time 17:32 Rev Time 0.00
Received By ccole Date 2016-12-05 Time 17:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-10-31 Cont ID  
Sent By ccole Date 2016-10-31 Time 09:30 Rev Time 0.00
Received By ccole Date 2016-10-31 Time 09:17 Sent To  
Notes
2016-10-31 09:37:501ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16100755
 10/31/16
  
 1) PROVIDE SIZING CALCULATIONS FOR THE NEW AHU'S 1 & 2-
 SECTION 403.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) THE O/A TO ALL UNITS REQUIRES AUTOMATIC CONTROL AS
 OUTLINED IN SECTION C403.2.4.4.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-12-14 Cont ID  
Sent By gjohnson Date 2016-12-14 Time 12:41 Rev Time 0.00
Received By gjohnson Date 2016-12-14 Time 12:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-19 Cont ID  
Sent By tklarge Date 2016-11-19 Time 05:37 Rev Time 0.00
Received By tklarge Date 2016-11-19 Time 05:21 Sent To  
Notes
2016-11-19 05:34:351) A SERVICE SINK AND DRINKING FOUNTAIN ARE REQUIRED IN
 THIS SPACE PER THE 2014 FPC TABLE 403.1 IF THEY ARE NOT
 PROVIDED IN THE COMMON AREA. IF THEY ARE LOCATED IN THE
 COMMON AREA, SUBMIT A PLAN THAT SHOWS THE LOCATION OF
 THE FIXTURES. AMINIMUM OF 2 DRINKING FOUNTAINS SHALL BE
 PROVIDED. FPC TABLE 403.1 FOOTNOTE # F & FAC SEC.211.2.
 2) AIR ARRESTORS ARE REQUIRED ON THE DISHWASHER WATER
 SUPPLY PER 2014 FPC SEC.604.9.
 3) BACKFLOW PREVENTERS ARE REQUIRED ON THE WATER LINE
 TO THE REFRIGERATOR & COFFE MAKER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2016-11-17 Cont ID  
Sent By aaponte Date 2016-11-17 Time 14:40 Rev Time 0.00
Received By aaponte Date 2016-11-17 Time 14:40 Sent To  
Notes
***NONE***