Plan Review Details - Permit 16100738
Plan Review Stops For Permit 16100738
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-11-22 Cont ID  
Sent By cthroop Date 2016-11-22 Time 13:43 Rev Time 0.00
Received By cthroop Date 2016-11-22 Time 13:43 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-02 Cont ID  
Sent By cthroop Date 2016-11-02 Time 13:35 Rev Time 0.00
Received By cthroop Date 2016-11-02 Time 13:35 Sent To  
Notes
2016-11-02 13:39:06BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. VALUATION ? BASED ON THE MARSHALL-SWIFT VALUATION
 SERVICE YOUR STATED VALUE APPEARS LOW.
 THE STATED VALUATION APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE VALUATION
 ACCORDINGLY.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER TO VERIFY VALUE OR AN ITEMIZED LIST OF ALL LABOR,
 MATERIALS AND/OR EQUIPTMENT AND RENTALS.
  
 CITY OF WPB CHPT. 1
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-28 Cont ID  
Sent By mvaldes Date 2016-11-28 Time 08:37 Rev Time 0.00
Received By mvaldes Date 2016-11-28 Time 08:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-02 Cont ID  
Sent By mvaldes Date 2016-11-02 Time 09:49 Rev Time 0.00
Received By mvaldes Date 2016-11-02 Time 09:13 Sent To  
Notes
2016-11-02 09:48:191ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - THE PLANS SUBMMITTED DON'T CONTAIN ANY ELECTRICAL
 DETAILS, THE ONLY ELECTRICAL INFORMATION IS A NOTE FOR
 AN EXISTING 20 AMP DISCONNECT WHICH COMPLIES WITH NEC
 600.6. BELOW FIND A LIST OF ITEMS REQUIRED.
  
 1] PROVIDE A ELECTRICAL PLAN TO INCLUDE MINIMUM A 20
 AMP DEDICATED CIRCUIT FOR THE SIGN PER NEC 600.5
  
 2] ADD A BLOCK NOTE FOR ALL GROUNDING AND BONDING TO
 COMPLY WITH NEC 600.7
  
 3] LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. FBC-E
 SECTION C405.2.4 EXTERIOR LIGHTING CONTROLS (SHOW
 COMPLIANCE)
  
 4] THE PERMIT VALUATION AND PERMIT FEE MUST
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE VALUATION
 ACCORDINGLY AND SHOW PROOF WITH AN OWNER SIGNED
 CONTRACT. FBC- 109.3
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-28 Cont ID  
Sent By mvaldes Date 2016-11-28 Time 08:37 Rev Time 0.00
Received By mvaldes Date 2016-11-16 Time 15:50 Sent To  
Notes
2016-11-16 15:50:53RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-02 Cont ID  
Sent By cthroop Date 2016-11-02 Time 13:35 Rev Time 0.00
Received By cthroop Date 2016-10-25 Time 14:25 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-11-21 Cont ID  
Sent By njwira Date 2016-11-21 Time 17:57 Rev Time 0.00
Received By njwira Date 2016-11-17 Time 13:54 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-10-31 Cont ID  
Sent By cthroop Date 2016-11-02 Time 13:35 Rev Time 0.00
Received By njwira Date 2016-10-25 Time 16:58 Sent To E
Notes
***NONE***