Plan Review Stops For Permit 16100726 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-11-10 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-11-10 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-11-10 |
Time |
10:59 |
Sent To |
M |
|
Notes |
2016-11-10 11:22:36 | ROUTED TO JV. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-11-03 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-11-03 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-11-03 |
Time |
11:11 |
Sent To |
|
|
Notes |
2016-11-03 11:15:56 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] PLEASE CLARIFY THE ELECTRICAL SCOPE OF WORK. IF | | RUNING NEW CICUITS SHOW A SMALL ONE LINE DIAGRAM | | REFLECTING CONDUCTOR AND RACEWAY ROUTING PLUS A PANEL | | SCHEDULE IDENTIFYING CIRCUIT # WITH OVERCURRENT | | PROTECTION AMPERE RATING. | | | | 2] PROVIDE MANUFACTURE SPECIFICATIONS INDICATING | | NAMEPLATE RATING OF EQUIPMENT IDENTIFYING MINIMUM | | AMPERE RATING AND MAXIMUM OVERCURRENT DEVICE PER NEC | | 440. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2017-04-18 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2017-04-18 |
Time |
08:39 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-04-12 |
Time |
09:47 |
Sent To |
|
|
Notes |
2017-04-13 09:48:10 | RESUB ROUTED TO HMOSER |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-11-16 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2016-11-16 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2016-11-07 |
Time |
10:00 |
Sent To |
|
|
Notes |
2016-11-08 10:00:51 | RESUB ROUTED TO MVALDES |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-11-03 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-11-03 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-10-25 |
Time |
14:35 |
Sent To |
|
|
Notes |
2016-11-02 18:47:34 | ROUTED TO MARIO VALDEZ 11/02/2016 - JORGE V. | 2016-10-25 14:35:56 | MECH -$5000 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2018-06-12 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2018-06-12 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2018-06-12 |
Time |
13:21 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2017-04-18 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2017-04-18 |
Time |
08:39 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-04-18 |
Time |
08:27 |
Sent To |
|
|
Notes |
2017-04-18 08:39:32 | DENIED | | 1) NO MECHANICAL PLAN SUBMITTED. SHOW LOCATION OF THE | | AIR HANDLER, CONDENSER ON THE PLAN. PROVIDE TWO COPIES | | OF | | THE LOT SURVEY FOR ZONING. PER SECTION 107 FBC | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2016-11-15 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2016-11-15 |
Time |
19:33 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2016-11-15 |
Time |
19:27 |
Sent To |
|
|
Notes |
2016-11-15 19:29:07 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | (1) PROVIDE MECHANICAL PLANS. | | (2) PROVIDE FLOOR PLAN WITH LOCATION OF AHU AND | | LOCATION OF CONDENSER. | | (3) PROVIDE EQUIPMENT SCHEDULE ON PLANS. | | | | FLORIDA ENERGY CODE FBC 2014 | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-11-02 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2016-11-02 |
Time |
18:45 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2016-11-02 |
Time |
18:29 |
Sent To |
|
|
Notes |
2016-11-02 18:40:53 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | (1) PROVIDE (AS PER CITY OF WEST PALM BEACH | | REQUIREMENTS) EQUIPMENT CHANGEOUT COMPLIANCE FORM IF | | THIS IS A CHANGEOUT. | | (2) PROVIDE MECHANICAL PLANS WITH ALL REQUIRED | | INFORMATION IF THIS IS A NEW INSTALLATION. | | (3) PROVIDE CONDENSER TIE DOWN DETAIL. | | | | FLORIDA ENERGY CODE FBC 2014 | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | | | | | | | |
|
|