Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-11-01 Cont ID  
Sent By ccole Date 2016-11-01 Time 07:35 Rev Time 0.00
Received By ccole Date 2016-11-01 Time 07:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-26 Cont ID  
Sent By ccole Date 2016-10-26 Time 15:02 Rev Time 0.00
Received By ccole Date 2016-10-26 Time 15:02 Sent To  
Notes
2016-10-26 15:08:111ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100716
 10/25/16
  
 1) PROVIDE AN AHRI CERTIFICATE FOR THE REVISED GOODMAN
 SYSTEM.
  
 2) THE 8" ROUND DUCT SUPPLYING 303 CFM'S IN THE DINING
 ROOM IS UNDERSIZED PER THE MANUAL J CALCULATIONS
 SUBMITTED UNDER THE MASTER PERMIT #15120534- MINIMUM 9"
 DUCT REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  