Plan Review Details - Permit 16100641
Plan Review Stops For Permit 16100641
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-27 Cont ID  
Sent By albarran Date 2016-10-27 Time 20:55 Rev Time 0.00
Received By albarran Date 2016-10-27 Time 20:52 Sent To I
Notes
2016-10-27 20:55:50APPROVED ELECTRICAL REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-24 Cont ID  
Sent By albarran Date 2016-10-24 Time 17:27 Rev Time 0.00
Received By albarran Date 2016-10-24 Time 17:13 Sent To I
Notes
2016-10-24 17:28:24ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB ADDRESS: 1142 OKEECHOBEE RD.
 DESCRIPTION: INSTALL NEW 125 AMP SERVICE TO BAY 11
 MASTER PERMIT: 16100641
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS TO THE
 FBC-B REQUIRES THAT THE CONSTRUCTION DOCUMENTS BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE PROPOSED WORK AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS). THE DRAWINGS
 SHALL BE SIGNED, INCLUDE THE SCOPE OF WORK AND THE
 APPLICABLE DESIGN CODE EDITION.
 2. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM
 SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS
 SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR
 SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE
 SITE SPECIFIC.
 3. NEC 230.72 GROUPING OF DISCONNECTS. (A) GENERAL. THE
 TWO TO SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE
 GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE
 THE LOAD SERVED.
 4. NEC 408.4(A) REQUIRES THAT YOU PROVIDE A PANEL
 SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING THE
 SPECIFIC PURPOSE OF EVERY CIRCUIT.
 5. NEC 408.4(B) ALL SWITCHBOARDS AND PANELBOARDS
 SUPPLIED BY A FEEDER IN OTHER THAN A ONE OR TWO FAMILY
 DWELLING SHALL BE MARKED TO INDICATE THE LOCATION AND
 TYPE OF THE SOURCE OF POWER.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-27 Cont ID  
Sent By albarran Date 2016-10-27 Time 20:56 Rev Time 0.00
Received By albarran Date 2016-10-27 Time 14:21 Sent To  
Notes
2016-10-27 20:57:3710/27/16 APPROVED ELECTRICAL REVIEW. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL READY BIN D. MA
2016-10-27 14:21:15ALBARRAN'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-24 Cont ID  
Sent By albarran Date 2016-10-24 Time 17:30 Rev Time 0.00
Received By albarran Date 2016-10-21 Time 13:10 Sent To  
Notes
2016-10-24 17:31:1910/24/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL FILE SENT TO SMALL DENIED DRAWER D.
 MA
2016-10-24 13:11:03ELEC <5K