2016-10-24 17:28:24 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| JOB ADDRESS: 1142 OKEECHOBEE RD. |
| DESCRIPTION: INSTALL NEW 125 AMP SERVICE TO BAY 11 |
| MASTER PERMIT: 16100641 |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| |
| 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS TO THE |
| FBC-B REQUIRES THAT THE CONSTRUCTION DOCUMENTS BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE PROPOSED WORK AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR |
| SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL |
| INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE, |
| THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND |
| SIGNATURE SHALL APPEAR ON ALL DOCUMENTS). THE DRAWINGS |
| SHALL BE SIGNED, INCLUDE THE SCOPE OF WORK AND THE |
| APPLICABLE DESIGN CODE EDITION. |
| 2. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM |
| SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS |
| SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR |
| SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE |
| SITE SPECIFIC. |
| 3. NEC 230.72 GROUPING OF DISCONNECTS. (A) GENERAL. THE |
| TWO TO SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE |
| GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE |
| THE LOAD SERVED. |
| 4. NEC 408.4(A) REQUIRES THAT YOU PROVIDE A PANEL |
| SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING THE |
| SPECIFIC PURPOSE OF EVERY CIRCUIT. |
| 5. NEC 408.4(B) ALL SWITCHBOARDS AND PANELBOARDS |
| SUPPLIED BY A FEEDER IN OTHER THAN A ONE OR TWO FAMILY |
| DWELLING SHALL BE MARKED TO INDICATE THE LOCATION AND |
| TYPE OF THE SOURCE OF POWER. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |